| Description |
High reliability rectifier for low power telco and other network
applications |
 |
| Features |
Hot-swap rectifiers, Input Power Factor Correction, Paralleling
Capability, Rack Mount |
 |
|
| Output
|
 |
| Base Rated Power |
500 Watts |
 |
| Base Rated Current |
11 Amps |
 |
| Nominal output voltage |
48 V |
 |
| Output Voltage Note |
48 - 58V operating voltage |
 |
| Grounding Polarity |
Floating |
 |
| Output Noise, Psophometric,
CCITT |
2 mV |
 |
| Output Noise, Psophometric,
C Weighted |
32 dBrnC |
 |
| Output Noise, Psophometric,
LF, 10Hz - 100Hz |
50 mV p-p |
 |
| Protection Device 2 Quantity |
0 |
 |
| Protection Device 3 Quantity |
0 |
 |
| Output Connection Type |
Hot plug blind mate rear connector |
 |
| Factory Set Voltage |
0.0 |
 |
 |
| Input
|
 |
| Nominal input voltage |
100, 120, 208, 230, 240 V |
 |
| Input frequency |
50/60 Hz |
 |
| Input Connection Type * |
Hot plug blind mate rear connector |
 |
| Input voltage range for main
operations |
88 - 264 V |
 |
| Input Power Factor at Full Load |
0.99 |
 |
| Maximum Input Current per phase |
6 |
 |
| Input Overcurrent Protection |
Integral fuse in each rectifier |
 |
 |
 |
| Communications
& Management |
 |
| Visible Alarms |
Output OK |
 |
| Form C Relay Alarms |
Output OK |
 |
 |
 |
| Conformance
|
|
 |
| Approvals |
CE, CSA 22.2 No. 950, EN 60950, UL 1950 |
 |
| Standard warranty |
2 years repair or replace |
 |