AP7564 - Rack PDU, Basic, Zero U, 5.7kW, 208V, (36)C13 & (6)C19
APC Basic Rack PDU , Input: 208V 3PH , Input Connections: NEMA L21-20P , Cord Length: 3 feet ( 0.91 meters ) , Output: 208V , Output Connections: IEC 320 C13,IEC 320 C19
Includes: Installation guide, Rack Mounting brackets, Toolless Mounting Kit
Standard Lead Time: Usually in Stock
Output
| Nominal Output Voltage |
208V |
| Maximum Total Current Draw per Phase |
20A |
| Output Connections |
| (36) IEC 320 C13 |
|
| (6) IEC 320 C19 |
| |
| Always on Outlets |
42 |
| Overload Protection |
No |
Input
| Nominal Input Voltage |
208V 3PH |
| Input Frequency |
50/60 Hz |
| Regulatory Derated Input Current |
16A |
| Input Connections |
|
| Cord Length |
0.91 meters |
| Number of Power Cords |
1 |
| Maximum Input Current per phase |
20A |
| Load Capacity |
5700 VA |
Physical
| Net Weight |
5.45 KG |
| Maximum Height |
1778.00 mm |
| Maximum Width |
56.00 mm |
| Maximum depth |
44.00 mm |
| Shipping Weight |
6.36 KG |
| Shipping Height |
2134.00 mm |
| Shipping Width |
152.00 mm |
| Shipping Depth |
127.00 mm |
| Color |
Black |
Environmental
| Operating Environment |
0 - 45 °C |
| Operating Relative Humidity |
5 - 95% |
| Operating Elevation |
0-3000 meters |
| Storage Temperature |
-25 - 65 °C |
| Storage Relative Humidity |
5 - 95% |
| Storage Elevation |
0-15000 meters |
Conformance
| Regulatory Approvals |
cUL Listed,CSA C22.2 No. 60950-1-03,UL 60950-1,UL Listed |
| Standard Warranty |
2 years repair or replace |
|
|