SUA3000JB APC Smart-UPS 3000VA USB & Serial 100V Black![]()
APC Smart-UPS, 2700 Watts / 3000 VA,Input 100V / Output 100V, Interface Port DB-9 RS-232, USB, SmartSlot
Includes: User Manual Standard Lead Time: Usually in Stock OutputOutput Power Capacity
2700 Watts / 3000 VA Max Configurable Power
2700 Watts / 3000 VA Nominal Output Voltage
100V Efficiency at Full Load
95% Output Voltage Distortion
Less than 5% at full load Output Frequency (sync to mains)
47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal Crest Factor
up to 5 : 1 Waveform Type
Sine wave Output Connections
InputNominal Input Voltage
100V Input Frequency
50/60 Hz +/- 5 Hz (auto sensing) Input Connections
Cord Length
2.44 meters Maximum Input Current
33A Input Breaker Capacity
40A Batteries & RuntimeBattery Type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof Typical recharge time
4.50 hour(s) RBC™ Quantity
1 Extended Run Options
APC Smart-UPS 3000VA USB & Serial 100V Black Communications & ManagementInterface Port(s)
DB-9 RS-232,USB,SmartSlot Available SmartSlot™ Interface Quantity
1 Control panel
-- Audible Alarm
-- Emergency Power Off (EPO)
Yes Surge Protection and FilteringSurge energy rating
510 Joules Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 PhysicalMaximum Height
432.00 mm Maximum Width
196.00 mm Maximum Depth
546.00 mm Net Weight
55.90 KG Shipping Weight
64.50 KG Shipping Height
559.00 mm Shipping Width
381.00 mm Shipping Depth
762.00 mm Color
Black Units per Pallet
3.00 EnvironmentalOperating Environment
0 - 40 °C Operating Relative Humidity
0 - 95% Operating Elevation
0-3000 meters Storage Temperature
-15 - 45 °C Storage Relative Humidity
0 - 95% Storage Elevation
0-15000 meters Audible noise at 1 meter from surface of unit
45.00 dBA Online Thermal Dissipation
275.00 BTU/hr ConformanceRegulatory Approvals
UL 1778,VCCI Standard Warranty
2 years repair or replace,optional on-site warranties available,optional extended warranties available Environmental Compliance
RoHS 7b Exemption **The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS. | ||||||