SUA500JB APC Smart-UPS 500VA USB & Serial 100V Black![]()
APC Smart-UPS, 360 Watts / 500 VA,Input 100V / Output 100V, Interface Port DB-9 RS-232, Smart-Slot, USB
Includes: Smart UPS signalling RS-232 cable, User Manual Standard Lead Time: Usually in Stock OutputOutput Power Capacity
360 Watts / 500 VA Max Configurable Power
360 Watts / 500 VA Nominal Output Voltage
100V Output Voltage Distortion
Less than 5% at full load Output Frequency (sync to mains)
47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal Crest Factor
up to 5 : 1 Waveform Type
Sine wave Output Connections
InputNominal Input Voltage
100V Input Frequency
50/60 Hz +/- 5 Hz (auto sensing) Input Connections
Cord Length
1.83 meters Maximum Input Current
6A Input Breaker Capacity
10A Batteries & RuntimeBattery Type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof Typical recharge time
3 hour(s) Replacement Battery
RBC48L RBC™ Quantity
1 Extended Run Options
APC Smart-UPS 500VA USB & Serial 100V Black Communications & ManagementInterface Port(s)
DB-9 RS-232,Smart-Slot,USB Available SmartSlot™ Interface Quantity
1 Control panel
-- Audible Alarm
-- Emergency Power Off (EPO)
Optional Surge Protection and FilteringSurge energy rating
540 Joules Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 PhysicalMaximum Height
162.00 mm Maximum Width
140.00 mm Maximum Depth
358.00 mm Net Weight
12.50 KG Shipping Weight
14.00 KG Shipping Height
279.00 mm Shipping Width
273.00 mm Shipping Depth
495.00 mm Color
Black Units per Pallet
40.00 EnvironmentalOperating Environment
0 - 40 °C Operating Relative Humidity
0 - 95% Operating Elevation
0-3000 meters Storage Temperature
-15 - 45 °C Storage Relative Humidity
0 - 95% Storage Elevation
0-15000 meters Audible noise at 1 meter from surface of unit
45.00 dBA Online Thermal Dissipation
70.00 BTU/hr ConformanceRegulatory Approvals
UL 1778,UL Listed,VCCI Standard Warranty
2 years repair or replace Environmental Compliance
RoHS 7b Exemption **The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS. | ||||