APC » Smart-UPS RM & Smart-UPS RMXL » SUM3000RMXLI2U APC Smart-UPS XL Modular 3000VA 230V Rackmount/Tower
SUM3000RMXLI2U APC Smart-UPS XL Modular 3000VA 230V Rackmount/Tower![]()
APC Smart-UPS, 2850 Watts / 3000 VA,Input 230V / Output 230V, Interface Port DB-9 RS-232, RJ-45 10/100 Base-T, USB, Extended runtime model, Rack Height 2 U
Includes: CD with software, Rack Mounting brackets, Rack Mounting support rails, Smart UPS signalling RS-232 cable, USB cable, User Manual Standard Lead Time: Usually in Stock OutputOutput Power Capacity
2850 Watts / 3000 VA Max Configurable Power
2850 Watts / 3000 VA Nominal Output Voltage
230V Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage Efficiency at Full Load
95% Output Voltage Distortion
Less than 5% at full load Output Frequency (sync to mains)
47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal Crest Factor
up to 5 : 1 Waveform Type
Sine wave Output Connections
Bypass
Internal Bypass (Automatic and Manual) InputNominal Input Voltage
230V Input Frequency
50/60 Hz +/- 5 Hz (auto sensing) Input Connections
Input voltage range for main operations
160 - 285V Input voltage adjustable range for mains operation
151 - 302V Batteries & RuntimeBattery Type
VRLA Included Battery Modules
1 Typical recharge time
3 hour(s) Replacement Battery
RBC43 RBC™ Quantity
1 Extended Run Options
APC Smart-UPS XL Modular 3000VA 230V Rackmount/Tower Communications & ManagementInterface Port(s)
DB-9 RS-232,RJ-45 10/100 Base-T,USB Pre-Installed SmartSlot™ Cards
AP9619 Control panel
LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators Audible Alarm
Alarm when on battery : distinctive low battery alarm : configurable delays Emergency Power Off (EPO)
Optional Surge Protection and FilteringSurge energy rating
490 Joules Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 PhysicalMaximum Height
86.00 mm Maximum Width
432.00 mm Maximum Depth
678.00 mm Rack Height
2U Net Weight
46.82 KG Shipping Weight
56.82 KG Shipping Height
250.00 mm Shipping Width
596.00 mm Shipping Depth
980.00 mm Color
Black Units per Pallet
8.00 EnvironmentalOperating Environment
0 - 40 °C Operating Relative Humidity
0 - 95% Operating Elevation
0-3000 meters Storage Temperature
-20 - 45 °C Storage Relative Humidity
0 - 95% Storage Elevation
0-9000 meters Audible noise at 1 meter from surface of unit
55.00 dBA Online Thermal Dissipation
300.00 BTU/hr ConformanceRegulatory Approvals
C-tick,CE,EN 50091-2,EN 55022 Class A,EN 61000-3-2,GOST Standard Warranty
2 years repair or replace Environmental Compliance
RoHS 7b Exemption,China RoHS,REACH: Contains No SVHCs **The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS. | ||||||||
| Request
Information |

email: bobr@bomara.com web: www.bomara.com
![]()