APC Smart-UPS RT, 4200 Watts / 6000 VA,Input 208V / Output 208V, Interface Port Smart-Slot, Extended runtime model, Rack Height 3 U
Includes: CD with software, Smart UPS signalling RS-232 cable, User Manual, Web/SNMP Management Card
Standard Lead Time: Usually in Stock
Output
| Output Power Capacity |
4200 Watts / 6000 VA |
| Max Configurable Power |
4200 Watts / 6000 VA |
| Nominal Output Voltage |
208V |
| Output Voltage Note |
Configurable for 208 or 240 nominal output voltage |
| Efficiency at Full Load |
92.00% |
| Output Voltage Distortion |
Less than 3% |
| Output Frequency (sync to mains) |
50/60 Hz +/- 3 Hz user adjustable +/- 0.1 |
| Crest Factor |
3 : 1 |
| Waveform Type |
Sine wave |
| Output Connections |
| (2) NEMA L6-20R |
|
| (2) NEMA L6-30R |
| |
Input
| Bypass |
Internal Bypass (Automatic and Manual) |
| Nominal Input Voltage |
208V |
| Input Frequency |
50/60 Hz +/- 5 Hz (auto sensing) |
| Input Connections |
| NEMA L6-30P |
| |
| Cord Length |
3.05 meters |
| Input voltage range for main operations |
160 - 280V |
| Input voltage adjustable range for mains operation |
100 - 280V |
| Other Input Voltages |
240 |
Batteries & Runtime
| Battery Type |
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof |
| Included Battery Modules |
2 |
| Typical recharge time |
2.50 hour(s) |
| Replacement battery cartridge |
RBC44 |
| RBC™ Quantity |
1 |
Typical Backup Time at Half Load |
15.8 minutes (2100 Watts) |
Typical Backup Time at Full Load |
5.3 minutes (4200 Watts) |
| Runtime Chart |
Smart-UPS RT |
| Extended Run Options |
APC Smart-UPS RT 6000VA 208V |
Communications & Management
| Interface Port(s) |
Smart-Slot |
| Pre-Installed SmartSlot™ Cards |
AP9619 |
| Control panel |
LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : Overload and Bypass Indicators |
| Audible Alarm |
Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
| Emergency Power Off (EPO) |
Yes |
Surge Protection and Filtering
| Surge energy rating |
480 Joules |
| Filtering |
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449 |
Physical
| Maximum Height |
432.00 mm |
| Maximum Width |
130.00 mm |
| Maximum depth |
660.00 mm |
| Rack Height |
3U |
| Net Weight |
54.55 KG |
| Shipping Weight |
63.64 KG |
| Shipping Height |
347.00 mm |
| Shipping Width |
603.00 mm |
| Shipping Depth |
980.00 mm |
| Color |
Black |
| Units per Pallet |
6.00 |
Environmental
| Operating Environment |
0 - 40 °C |
| Operating Relative Humidity |
0 - 95% |
| Operating Elevation |
0-3000 meters |
| Storage Temperature |
-15 - 45 °C |
| Storage Relative Humidity |
0 - 95% |
| Storage Elevation |
0-15000 meters |
| Audible noise at 1 meter from surface of unit |
55.00 dBA |
| Online Thermal Dissipation |
1040.00 BTU/hr |
Conformance
| Regulatory Approvals |
CSA,FCC Part 15 Class A,UL 1778 |
| Standard Warranty |
2 years repair or replace |
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.