| APC Symmetra LX 4kVA Scalable to 8kVA N+1 Tower, 208/240V Input, 208/240V and 120V Output |
| APC Symmetra LX, 4000VA/3200W, Input 208V/Output 120V, 208V, Interface Port DB-9 RS-232, Smart-Slot, Extended runtime model |
| Includes: CD with software, Documentation CD, Installation Guide, User Manual, Web/SNMP Management Card |
Part Number : SYA4K8P
|
Runtime Chart |
Additional Information
Product Overview
|
|
|
| Technical Specifications |
Output
|
| Output power capacity |
4,000 VA |
| Output power capacity |
3,200 Watts |
| Max Configurable Power |
8,000 VA |
| Max Configurable Power |
6,400 Watts |
| Nominal output voltage |
120V, 208V |
| Output Voltage Note |
Configurable for 208 or 240 nominal output voltage |
| Output Voltage Distortion |
less than 5% at full load |
| Output Frequency (sync to mains) |
47-63Hz |
| Crest Factor |
up to 5 : 1 |
| Waveform type |
Sinewave |
| Output Connections |
| (1) Hard Wire 4-wire (2PH + N +G) |
|
|
|
| |
Input
|
|
| |
Batteries & Runtime
|
| Battery type |
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof |
| Pre-Installed Batteries |
1 |
| Battery Slots Empty |
1 |
| Replacement battery cartridge |
SYBT5 |
| RBC™ Quantity |
2 |
Typical backup time
at half load |
16.9 minutes (1600 Watts) |
Typical backup time
at full load |
5.9 minutes (3200 Watts) |
| Runtime Chart |
Symmetra LX |
| Extended run options |
SYA4K8P 1 hrs 1 mins
SYA4K8P + (1)SYBT5 2 hrs 15 mins
SYA4K8P + (1)SYXR12B12-BX120 16 hrs 41 mins
SYA4K8P + (2)SYXR12B12-BX120 34 hrs 0 mins
SYA4K8P + (3)SYXR12B12-BX120 52 hrs 8 mins
SYA4K8P + (4)SYXR12B12-BX120 70 hrs 48 mins
SYA4K8P + (5)SYXR12B12-BX120 89 hrs 53 mins
SYA4K8P + (6)SYXR12B12-BX120 109 hrs 19 mins
SYA4K8P + (7)SYXR12B12-BX120 129 hrs 2 mins |
|
| |
Communications & Management
|
| Interface port |
DB-9 RS-232, Smart-Slot |
| Available Smart Slot Interface Quantity |
1 |
| Pre-Installed SmartSlot Cards |
AP9619 |
| Control panel |
Multi-function LCD status and control console |
| Audible alarm |
Audible and visible alarms prioritized by severity |
| Emergency Power Off (EPO) |
Yes |
|
| |
Physical
|
| Maximum height |
26 inches ( 66 cm ) |
| Maximum width |
19 inches ( 48 cm ) |
| Maximum depth |
29 inches ( 73 cm ) |
| Net weight |
347 lbs. ( 158 kg ) |
| Shipping Weight |
394 lbs. ( 179 kg ) |
| Shipping Height |
36 inches ( 91 cm ) |
| Shipping Width |
24 inches ( 60 cm ) |
| Shipping Depth |
39 inches ( 100 cm ) |
| Color |
Black, Silver |
| Units per Pallet |
1 |
|
| |
Environmental
|
| Operating Environment |
0 - 40 °C ( 32 - 104 °F ) |
| Operating Relative Humidity |
0 - 95 % |
| Operating Elevation |
0-10000 feet ( 0-3000 meters ) |
| Storage Temperature |
-15 - 45 °C ( 5 - 113 °F ) |
| Storage Relative Humidity |
0 - 95 % |
| Storage Elevation |
0-15000 feet ( 0-4500 meters ) |
| Online thermal dissipation |
3,485 BTU/hr |
|
| |
Conformance
|
|
| |
|
Options: Batteries
Battery Cables
Internal BackPlate Kits
Management Devices
MasterSwitches/Outlet Strips
Power Cords
Power Modules
Service Bypass Panels
Services
Software
|
| |
| General Features: Audible Alarms
Automatic internal bypass
Automatic restart of loads after UPS shutdown
Automatic self-test
Battery modules connected in parallel
Cold-start capable
Configurable for N+1 internal redundancy
Disconnected battery notification
Field-replaceable power distribution panel
Frequency and voltage regulation
Generator Compatible
Hot-swappable batteries
Hot-swappable intelligence modules
Hot-swappable power modules
InfraStruXure Manager Compatible
Input Power Factor Correction
Intelligent Battery Management
LCD display
Manageable external batteries
Modular design
Network manageable
Plug-and-Play external batteries
Power conditioning
Power Modules connected in parallel
Predictive failure notification
Programmable Frequency
Rack/Tower Convertible
Redundant Intelligence Modules
Removable input/output wiring tray
Resettable circuit breakers
Safety-agency approved
Scalable Power Capacity
Scalable runtime
Shippable with modules installed
SmartSlot
User-replaceable batteries
User-replaceable intelligence modules
User-replaceable power modules
more details... |
| Topology: Double Conversion Online |
|
|
|
|