APC Home » Galaxy VM

 APC Galaxy VM Series: Galaxy VM 160-225kVA 3 Phase UPS 480-480VAC, Start up 5x8 included

• Highly compact, energy efficient Three-phase UPS for data center, facility and industrial applications





Description:

Galaxy VM is a key component in the comprehensive Schneider Electric energy Management solution for data center and industrial applications. Galaxy VM deploys state of the art technology to lower energy cost through very high efficiency ratings and the newly innovative ECOnversion mode. Galaxy VM seamlessly links to your electrical network using state of the art electrical performances like very wide input voltage range, high overload and short circuit capacity and integrated back feed protection providing excellent power quality. The highly compact Galaxy VM also links in with your facility monitoring systems and smart grid requirements and offers both traditional and modular energy storage flexibility that allows tailoring of the solution to specific needs. Galaxy VM features top and bottom cable entry without the need for an additional side cabinet, full front service access, back to the wall installation and included start up service making it one of the easiest UPS’s in its class to deploy, install and maintain.



  • Ordering Info
  • Features
  • Specifications
  • Battery Runtime
  • Communication
  • Physical
  • Gallery



Ordering Information for the Galaxy VM:

Part Number Products
GVMBBB600UL Galaxy VM Breaker Box 600A UL
GVMBBK250UL Galaxy VM battery breaker kit 250A UL
GVMBBK400UL Galaxy VM battery breaker kit 400A UL
GVMCBC2WUE Galaxy VM back up time cabinet UL 2 X wide E
GVMCBC2WUF Galaxy VM back up time cabinet UL 2 X wide F
GVMCBC3WUF Galaxy VM back up time cabinet UL 3 X wide F
GVMCBCABWE Galaxy VM UPS Classical Battery Cabinet wide Empty
GVMCBCWUE Galaxy VM back up time cabinet UL wide E
GVMDFW-KIT Galaxy VM Dust Filter Kit Narrow Power Cabinet
GVMFU800WW Fuse kit 160 to 225kVA WW
GVMMBTU Galaxy VM UPS Modular Battery String
GVMMODBCN Galaxy VM UPS Modular Battery Cabinet Narrow for 6 battery modules
GVMMODBCNS Galaxy VM UPS Modular Battery Cabinet Narrow for 6 battery modules, Start up 5x8
GVMMODBCW Galaxy VM UPS Modular Battery Cabinet wide for 12 battery modules
GVMMODBCWS Galaxy VM UPS Modular Battery Cabinet wide for 12 battery modules, Start up 5x8
GVMPB160KGS Galaxy VM 160 kVA UPS Parallel 480-480 V, Start up 5x8
GVMPB180KGS Galaxy VM 180 kVA UPS Parallel 480-480 V, Start up 5x8
GVMPB225KGS Galaxy VM 225 kVA UPS Parallel 480-480 V, Start up 5x8
GVMRB160KGS Galaxy VM 160 kVA Additional UPS for 1+1 480-480 V, Start up 5x8
GVMRB180KGS Galaxy VM 180 kVA Additional UPS for 1+1 480-480 V, Start up 5x8
GVMRB225KGS Galaxy VM 225 kVA Additional UPS for 1+1 480-480 V, Start up 5x8
GVMSB160KGS Galaxy VM 160 kVA UPS Single 480-480 V, Start up 5x8
GVMSB180KGS Galaxy VM 180 kVA UPS Single 480-480 V, Includes start up 5x8
GVMSB225KGS Galaxy VM 225 kVA UPS Single 480-480 V, Start up 5x8
GVMSBC450KG Galaxy VM System Bypass Cabinet 450K 480V
GVMSBC675KG Galaxy VM System Bypass Cabinet 675K 480V
GVMSBCLB675KG Galaxy VM System Bypass Cabinet 675K 480V with load bank breaker



Features for the Galaxy VM:


Availability 
Advanced electrical features Excellent power conditioning, very low harmonic distortion through IGBT rectifier, input power factor correction, and high power efficiency
Parallel-capacity capable Increases total power capacity by using multiple uninterruptible power supplies simultaneously.
Parallel-redundant capable Power the connected equipment with multiple uninterruptible power supplies to increase system redundancy
Generator compatible Ensures clean, uninterrupted power to protected equipment when generator power is used.
Life Cycle monitoring Allows predictive maintenance notification to ensure continuity on the entire UPS system.
Hot swappable fan replacement Allows replacement of individual fans without going to bypass increasing availability and load protection.
Modular battery offer Allows replacement of batteries without the need to go to Maintenance bypass while maintaining availability and continuous protection of the load
Energy storage flexibility Conventional flooded and modular battery offer along with different charging modes allows tailoring to specific back-up requirements.
Adaptability 
Flexible Design Available in a wide range of configurations to suit any operating environment
Safety 
Internal back feed protection Increase system defense from power anomalies.
Seismic compliance These all-steel enclosures meet IBC Zone 2 seismic rating.
Convenience 
Top and bottom cable entry Allows cabling from the top and bottom without the need of additional cabinets providing footprint savings and flexibility to the installation.
5x8 Start-up service included Required for full coverage of factory warranty
Swappable batteries Allows quick addition of runtime capacity or replacement of existing battery modules. Installed modules are automatically recognized by the system.
Wheel mounted Allows for ease of handling during installation.
Manageability 
LCD graphics touch screen display Full color text and mimic diagrams that easily display modes of operation, systems parameters and alarms.
LED status indicators Quickly understand unit and power status with visual indicators.
Integrated network Management Provides complete remote monitoring and control of the UPS. Enables you to monitor remote UPS's from a web browser or industry standard Network Management System.
Mimic Diagram Allows instant access to the status of the UPS.
Modbus Protocol Capable Enables remote monitoring and interface with StruxureWare Central and other Management systems.
Serviceability 
Front-access servicing Simplifies installation and UPS maintenance while minimizing space requirements.
Multiple levels of service With the option of packages or individual service components, our services are structured to allow you to pick and choose what you would like APC to do for you.
Technical support Our experienced technical support engineers are available to answer your questions, giving you peace of mind knowing the help you need is there when you need it.
Low Mean Time To Repair (MTTR) Front-access battery design places all of the connection points in easy reach to speed battery replacement.
Total Cost of Ownership 
High efficiency High efficiency rates that remain stable even at lower operating power levels
ECOnversion mode
(available Q2 2014)
Operating mode that ensures ultra high efficiency while charging the batteries, conditioning the load power factor and ensuring a Class 1 output voltage regulation.
ECO Mode Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection
Robust operation No power derating in kW up to 40 degrees C or 104 degrees F.
Wide input voltage range Designed for harsh electrical environments to save battery life.
Input power factor correction Minimizes installation costs by enabling the use of smaller generators and cabling.


 



Galaxy VM Specifications:



Input Specifications:

  180 kVA 225 kVA
Connection type 3–wire (3PH + G)
Input voltage (V) 480 –25/+20% @100% load
Voltage Range (V) 360–576
Nominal input voltage (V) 480
Frequency range (Hz) 40 - 70
Nominal input current (A) 204 255
Maximum input current (A) 278 347
Input current limitation (A) 278 347
Total Harmonic Distortion (THDI) <3%@100% load
<4%@50% load
<6%@25% load
Input power factor correction 0.97 > 10% load
0.98 > 20% load
0.99 > 40% load
Maximum input short-circuit
withstand (kA)
65 kA@required breaker
See Required Upstream Breakers, page 21
Protection Built-in back feed Contactor
Ramp-in Adaptive 1 - 40 Sec


Bypass Specifications:

  180 kVA 225 kVA
Connection type 4–wire (3PH + N + G)
3–wire (3PH + G)
Nominal bypass voltage (V) 480
Frequency (Hz) 50 or 60
Frequency Range (Hz) +/-0.1, +/-3, +/-10 (user selectable). Default is +/-3
Nominal bypass current (A) 217 271
Protection Built-in back feed Contactor


Output Specifications:

  180 kVA 225 kVA
Nominal output voltage (V) 480
Connection type 4–wire (3PH + N + G)
3–wire (3PH + G)
Overload capacity 150% for 1 minute (normal operation) at 40°C
125% for 10 minutes (normal operation) at 40°C
150% for 1 second (battery operation) at 40°C
125% for 1 minute (battery operation) at 40°C
1000% for 100 ms (bypass operation)
Output voltage range Symmetric load (0–100%):
+/- 1% static
+/- 5% after 2 ms
+/- 1% after 50 ms
Output power factor 0.9
Nominal output current (A) 217 271
Total Harmonic Distortion (THDU) <2% at 100% linearload
<3% at 100% non–linearload
Output Frequency (Hz) 50/60 (sync to bypass)
50/60 Hz +/-0.1% (free-running)
Slew rate (Hz/sec) Programmable: 0.25, 0.5, 1, 2, 4, 6
Load Crest Factor Unlimited
Load Power Factor 0.7 leading to 0.5 lagging without derating


Battery Specifications:

  180 kVA 225 kVA
Charging power in % of output
power
40% charge ≤ 80% load
20% charge ≤ 100% load
Nominal battery voltage (VDC) 480
Nominal float voltage (VDC) 545
End of discharge voltage
(full load) (VDC)
384
End of discharge voltage
(no load) (VDC)
420
Battery current at full load and
nominal battery voltage (A)
352 440
Battery current at full load and
minimum battery voltage (A)
440 549
Battery test Manual/automatic (selectable)
Deep discharge protection Yes
Recharge according to battery
temperature
Yes
Cold start Yes


Input Power Factor: Power factor(PF) is given for a 480Vnormal AC source for linear/non-linear load

  180 kVA 225 kVA
25% load 0.97 0.97
50% load 0.99 0.99
75% load 0.99 0.99
100% load 0.99 0.99


Efficiency: Efficiency in Normal Operation

The table below provides average system efficiencies with a balanced linear load, and a power factor of 0.9.

  180 kVA 225 kVA
25% load 95.6 95.8
50% load 96.4 96.4
75% load 96.6 96.6
100% load 96.4 96.4


Efficiency: Efficiency in ECO Mode

  180 kVA 225 kVA
25% load 98.2 98.5
50% load 99.0 99.1
75% load 99.2 99.4
100% load 99.5 99.5


Efficiency: Efficiency in Battery Operation

  180 kVA 225 kVA
25% load 96.4 96.3
50% load 96.5 96.2
75% load 96.2 96.0
100% load 95.8 95.7


Recommended Cable Sizes:


The UPS system can be supplied from a 3–wire or 4–wire service. If the load requires a 4–wire service, a 3–wire bypass is not permitted. In systems with a 4– wire service, connect the bypass input neutral, the output neutral, and inverter midpoint in the I/O Cabinet by the bus bar jumper 880–3102.

NOTE: All wiring must comply with all applicable national and/or electrical code.
The maximum allowable conductor size is 300 kcmil for AC cables and 500 kcmil
for DC cables.

Cable sizes in this manual are based on Table 310.15 of the National Electrical
Code 2011 (NEC) with the following assertions:

• 90 °C conductors (THHN) for 75 °C termination
• 4 current carrying conductors
• An ambient temperature of 30 °C
• Use of copper conductors

If the ambient room temperature is greater than 30 °C, larger conductors are to be
selected in accordance with the correction factors of the NEC.

Equipment Grounding Conductors (EGC) are sized in accordance with NEC Article
250.122 and Table 250.122.

  180 kVA 225 kVA
  80% rated
breakers
100% rated
breakers
80% rated
breakers
100% rated
breakers
Input (2) 2/0AWG (2) 1/0AWG (2) 4/0AWG (2) 2/0AWG
Bypass (2) 2/0AWG 250 kcmil (2) 3/0AWG (2) 2/0AWG
Output (2) 2/0AWG 250 kcmil (2) 3/0AWG (2) 2/0AWG
Battery (2) 4/0AWG (2) 4/0AWG (2) 350 kcmil (2) 350 kcmil

 

Recommended Bolt and Lug Sizes:

NOTICE
HAZARD OFEQUIPMENT DAMAGE

Use only UL approved cable lugs

Failure to follow these instructions can result in equipment damage


Cable Size Terminal Bolt Diameter Cable Lug Type Crimping Tool/Die
2/0 AWG M10 LCA2/0-12-X CT-720/CD-720-2
3/0 AWG M10 LCA3/0-12-X CT-720/CD-720-2
4/0 AWG M10 LCA4/0-12-X CT-720/CD-720-3
250 kcmil M10 LCA250-12-X CT-720/CD-720-3
300 kcmil M10 LCA300-12-X CT-720/CD-720-4
400 kcmil M10 LCA400-12-X CT-720/CD-720-5
500 kcmil M10 LCA500-12-X CT-720/CD-720-6


 



Galaxy VM Battery Runtime: The battery runtimes are intended as a guide only


Typical Battery Runtimes in Minutes for Systems with Modular Battery Cabinets
Number of Battery Modules 180 KVA 225 kVA
12 7.4 NA
14 9.3 6.6
18 13.0 9.7
24 19.5 14.5
36 32.5 24.5
48 46.5 35.5
60 61.0 46.5
72 76.5 58.0
84 92.0 70.0
96 105 82.5
Typical Battery Runtimes in Minutes for Systems with Modular Battery Cabinets
Runtime Needed UPS System Battery Solution
5 minutes 180 kVA GVMCBCWUE
225 kVA GVMCBC2WUF
10 minutes 180 kVA GVMCBC2WUF
225 kVA GVMCBC2WUE
15 minutes 180 kVA GVMCBC2WUE
225 kVA GVMCBC3WUF



Galaxy VM Communication & Management:

Local Area Network 100 Mbps
Extensions 2x Rhodes 2 NMC Cards (optional)
MODBUS MODBUS(SCADA &ION-E)
Relay Outputs 12 of which 6 are configurable
Dry Contact Inputs 12 of which 6 are configurable
Standard Control Panel 7" Touch Screen Display
Audible alarm Yes
Emergency Power Off (EPO) Options:
• Normally Open
• Normally Closed
• External 24 VDC SELV
External switchgear Yes
External Synchronization Yes all 3 phases
Transformer compensation Yes
Battery Monitoring Available for modular battery cabinets



Overview of Input Contacts and Output Relay:

Input Contacts



IN 1 Configurable input
IN 2 Configurable input
IN 3 Configurable input
IN 4 Configurable input
IN 5 Configurable input
IN 6 Configurable input
IN 7 Transformer temperature switch
IN 9 Forced external synchronization input
IN 10 External synchronization input
IN 11 Use static bypass standby


Outputs Relays



OUT 1 Configurable output
OUT 2 Configurable output
OUT 3 Configurable output
OUT 4 Forced external synchronization output
OUT 5 External synchronization output
OUT 6 External synchronization requested output
OUT 7 UPS in inverter ON
OUT 8 Configurable output
OUT 9 Configurable output
OUT 10 Configurable output



EPO Connections:


 



Galaxy VM Physical Specifications (Unit and Shipping):



Unit Weights and Dimensions:


UPS Physical Specifications (weights and dimensions are for unit only, scroll down for shipping):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
180 kVA UPS
(GVMSB180KGS)
Power Cabinet
I/O Cabinet
469 (1031.8)
210 (463)
1970 (77.56) 1002 (39.45) 854 (33.62)
225 kVA UPS
(GVMSB225KGS)
Power Cabinet
I/O Cabinet
494 (1086.8)
210 (462)
1970 (77.56) 1002 (39.45) 854 (33.62)
180 kVAParallel UPS
(GVMPB180KGS)
Power Cabinet
I/O Cabinet
469 (1031.8)
210 (463)
1970 (77.56) 1002 (39.45) 854 (33.62)
225 kVAParallel UPS
(GVMPB225KGS)
Power Cabinet
I/O Cabinet
494 (1086.8)
210 (462)
1970 (77.56) 1002 (39.45) 854 (33.62)
180 kVAAdditional UPS
for 1 +1 configuration
(GVMRB180KGS)
Power Cabinet
I/O Cabinet
469 (1031.8)
210 (462)
1970 (77.56) 1002 (39.45) 854 (33.62)
225 kVAAdditional UPSfor 1
+1 configuration
(GVMRB225KGS)
Power Cabinet
I/O Cabinet
494 (1086.8)
210 (462)
1970 (77.56) 1002 (39.45) 854 (33.62)


Classic Battery Cabinet (weights and dimensions are for unit only, scroll down for shipping):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
Classic battery cabinet
solution with 1 x wide E
(GVMCBCWUE)
1816 (3995.2) 1970 (77.56) 1080 (42.52) 854 (33.62)
Classic battery cabinet
solution with 2 x wide E
(GVMCBC2WUE)
3635 (7997)1 1970 (77.56) 2160 (85.04) 854 (33.62)
Classic battery cabinet
solution with 2 x wide F
(GVMCBC2WUF)
2899 (6377.8)1 1970 (77.56) 2160 (85.04) 854 (33.62)
Classic battery cabinet
solution with 3 x wide F
(GVMCBC3WUF)
4354 (9578.80)2 1970 (77.56) 3240 (127.56) 854 (33.62)
ClassicBattery Cabinet wide
Empty (GVMCBCABWE)
303 (666.6) 1970 (77.56) 1080 (42.52) 854 (33.62)
1 Total weight for two cabinets
2 Total weight for three cabinets


Modular Battery Cabinets (weights and dimensions are for unit only, scroll down for shipping):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
Modular Battery Cabinet
wide up to 12 strings
(GVMMODBCWS)
210 (462) 1970 (77.56) 700 (27.56) 854 (33.62)
Modular Battery Cabinet
Narrow up to 6 strings
(GVMMODBCNS)
139 (305,8) 1970 (77.56) 370 (14.57) 854 (33.62)
Modular BatteryString
(GVMMBTU) containing four
modular batteries each with
the following dimensions
30 (66) 114 (4.49) 137 (5.39) 854 (33.62)


System Bypass Cabinet (weights and dimensions are for unit only, scroll down for shipping):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
System Bypass Cabinet
450K480V
(GVMSBC450KG)
485 (1067) 1970 (77.56) 1505 (59.25) 837 (32.95)
System Bypass Cabinet
675K480V
(GVMSBC675KG)
505 (1111) 1970 (77.56) 1505 (59.25) 837 (32.95)
System Bypass Cabinet
675K480V with load bank
breaker (GVMSBCLB675KG)
585 (1287) 1970 (77.56) 1785 (70.28) 837 (32.95)


Battery Breaker Box (weights and dimensions are for unit only, scroll down for shipping):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
Battery BreakerBox 600A UL
(GVMBBB600UL)
80 (176) 1280 (50.39) 850 (33.46) 854 (33.62)


Kits (weights and dimensions are for unit only, scroll down for shipping):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
Battery BreakerKit 250A UL
(GVMBBK250UL)
7.4 (16.28) 262 (10.31) 377 (14.84) 241 (9.49)
Battery BreakerKit 400A UL
(GVMBBK400UL)
11.4 (25.08) 262 (10.31) 377 (14.84) 766 (30.16)
Fuse kit 160 to 225kVAWW
(GVMFU800WW)
3.2 (7.04) 127 (5) 396 (15.59) 241 (9.49)





Shipping Weights and Dimensions
:

UPS Physical Specifications (weights and dimensions are for shipping only, scroll up for unit):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
180 kVA UPS
(GVMSB180KGS)
Power Cabinet
I/O Cabinet
484.5 (1068)
235 (518)
2156 (84.88)
2150 (84.64)
740 (29.13)
750 (29.53)
1052 (41.42)
1060 (41.73)
225 kVA UPS
(GVMSB225KGS)
Power Cabinet
I/O Cabinet
510 (1124)
235 (518)
2156 (84.88)
2150 (84.64)
740 (29.13)
750 (29.53)
1052 (41.42)
1060 (41.73)
180 kVAParallel UPS
(GVMPB180KGS)
Power Cabinet
I/O Cabinet
484.5 (1068)
227 (500)
2156 (84.88)
2150 (84.64)
740 (29.13)
750 (29.53)
1052 (41.42)
1060 (41.73)
225 kVAParallel UPS
(GVMPB225KGS)
Power Cabinet
I/O Cabinet
510 (1124)
227 (500)
2156 (84.88)
2150 (84.64)
740 (29.13)
750 (29.53)
1052 (41.42)
1060 (41.73)
180 kVAAdditional UPSfor 1
+1 configuration
(GVMRB180KGS)
Power Cabinet
I/O Cabinet
484.5 (1068)
227 (500)
2156 (84.88)
2150 (84.64)
740 (29.13)
750 (29.53)
1052 (41.42)
1060 (41.73)
225 kVAAdditional UPSfor 1
+1 configuration
(GVMRB225KGS)
Power Cabinet
I/O Cabinet
510 (1124)
227 (500)
2156 (84.88)
2150 (84.64)
740 (29.13)
750 (29.53)
1052 (41.42)
1060 (41.73)


Classic Battery Cabinet (weights and dimensions are for shipping only, scroll up for unit):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
Classic battery cabinet
solution with 1 x wide E
(GVMCBCWUE)
1873 (4129) 2045 (80.51) 1380 (54.33) 1156 (45.51)
Classic battery cabinet
solution with 2 x wide E
(GVMCBC2WUE)
3718 (8197)1 2045 (80.51) 2760 (54.33) 1156 (45.51)
Classic battery cabinet
solution with 2 x wide F
(GVMCBC2WUF)
2983 (6576)1 2045 (80.51) 2760 (54.33) 1156 (45.51)
Classic battery cabinet
solution with 3 x wide F
(GVMCBC3WUF)
4464 (9841)2 2045 (80.51) 4140 (54.33) 1156 (45.51)
ClassicBattery Cabinet wide
Empty (GVMCBCABWE)
366 (807) 2045 (80.51) 1380 (54.33) 1156 (45.51)
1 Total weight for two cabinets
2 Total weight for three cabinets


Modular Battery Cabinets (weights and dimensions are for shipping only, scroll up for unit):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
Modular Battery Cabinet
Wide (GVMMODBCWS)
252 (556) 252 (556) 990 (38.98) 1060 (41.73)
Modular Battery Cabinet
Narrow (GVMMODBCNS)
164 (362) 2150 (84.64) 750 (29.83) 1060 (41.73)
Modular BatteryString
(GVMMBTU) containing four
modular batteries each with
the following dimensions
31.5 (69.45) 186 (7.32) 209 (8.23) 924 (36.38)


System Bypass Cabinet (weights and dimensions are for shipping only, scroll up for unit):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
System Bypass Cabinet 450
K480V(GVMSBC450KG)
560 (1235) 2045 (80.57) 1805 (71.06) 1156 (45.51)
System Bypass Cabinet 675
K480V(GVMSBC675KG)
580 (1279) 2045 (80.57) 1805 (71.06) 1156 (45.51)
System Bypass Cabinet
675K480V with load bank
breaker (GVMSBCLB675KG)
675 (1488) 2045 (80.57) 2085 (82.09) 1156 (45.51)


Battery Breaker Box (weights and dimensions are for shipping only, scroll up for unit):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
Battery BreakerBox 600A
(GVMBBB600UL)
120 (265) 550 (21.65) 1380 (54.33) 950 (37.40)


Kits (weights and dimensions are for shipping only, scroll up for unit):

Part Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
Battery BreakerKit 250A
(GVMBBK250UL)
7.9 (17.42) 262 (10.31) 377 (14.84) 766 (30.16)
Battery BreakerKit 400A
(GVMBBK400UL)
11.9 (26.24) 262 (10.31) 377 (14.84) 766 (30.16)
Fuse kit 160 to 225 kVA
(GVMFU800WW)
3.5 (7.72) 127 (5) 396 (15.59) 241 (9.49)




Galaxy VM Gallery: Click on a image to open it in a new tab


Galaxy VM Front View of UPS Galaxy VM Front View of the System Bypass Cabinet Galaxy VM Narrow Modular Battery Cabinet Galaxy VM Wide Modular Battery Cabinet Galaxy VM Narrow Classic Battery Cabinet
Front View of UPS Front View of the System Bypass Cabinet Narrow Modular Battery Cabinet Wide Modular Battery Cabinet Narrow Classic Battery Cabinet
         
Galaxy VM Wide Classic Battery Cabinet Galaxy VM Battery Breaker Box Galaxy VM Configurations for a Single System Galaxy VM Configurations for a 1 + 1 Redundant System Galaxy VM Configurations for a Parallel System
Wide Classic Battery Cabinet Battery Breaker Box Configurations for a Single System Configurations for a 1 + 1 Redundant System Configurations for a Parallel System
         
GVMBBK250UL Rear View GVMBBK250UL Front View GVMBBK250UL Applications GVMBBK400UL Rear View GVMBBK400UL Front View
GVMBBK250UL
Rear View
GVMBBK250UL
Front View
GVMBBK250UL
with Face Plate
GVMBBK400UL
Rear View
GVMBBK400UL
Front View
         
GVMBBK400UL Applications GVMFU800WW Rear View GVMFU800WW Front View GVMFU800WW Applications GVMMBTU Rear View
GVMBBK400UL with Face Plate GVMFU800WW
Rear View
GVMFU800WW
Front View
GVMFU800WW
with Face Plate
GVMMBTU
Rear View
         
GVMMBTU Front View GVMMODBCNS Rear View GVMMODBCNS Front Left GVMMODBCNS Detailed GVMMODBCNS Application
GVMMBTU
Front View
GVMMODBCNS
Rear View
GVMMODBCNS
Front Left
GVMMODBCNS
Detailed
GVMMODBCNS
Application
         
GVMMODBCNS Application GVMMODBCNS Miscellaneous GVMMODBCNS Miscellaneous GVMMODBCWS Rear View GVMMODBCWS Front Left
GVMMODBCNS
with Face Plate
GVMMODBCNS
Miscellaneous
GVMMODBCNS
Miscellaneous
GVMMODBCWS
Rear View
GVMMODBCWS
Front Left
         
GVMMODBCWS Detailed GVMMODBCWS Application GVMMODBCWS Application GVMMODBCWS Miscellaneous GVMMODBCWS Miscellaneous
GVMMODBCWS
Detailed
GVMMODBCWS
with Face Plate
GVMMODBCWS
Application
GVMMODBCWS
Miscellaneous
GVMMODBCWS
Miscellaneous
         
GVMSB180KGS Rear View GVMSB180KGS Front View GVMSB180KGS Detailed GVMSB180KGS Application GVMSB180KGS Miscellaneous
GVMSB180KGS
Rear View
GVMSB180KGS
Front View
GVMSB180KGS
Detailed
GVMSB180KGS
with Face Plate
GVMSB180KGS
Miscellaneous
         
GVMSB225KGS Rear View GVMSB225KGS Front Left GVMSB225KGS Application    
GVMSB225KGS
Rear View
GVMSB225KGS
Front Left
GVMSB225KGS
with Face Plate
   




Call Us: 1-978-452-2299
First Name:
Last Name:
Company:
Address:
Mail Stop:
City:
State (if in US):
Province/Region (if outside US):
Country:
ZIP (Postal) Code:
E-mail:
Telephone:
Fax:
Questions/Comments:
Verification: Please type:
Please have a Bomara Associates representative contact me


View Full Site View Mobile Optimized