SPECIFICATIONS SU700X93 SU2200X93 SU3000RMX93
Communications interface x x x
AVR Boost x x x
AVR Trim x x x
QuickSwap x x x
UPS-Link Control Language x x x
Replace Battery Indicator x x x
Load Power and Voltage Meters x x x
Low Battery Indicator and Overload Indicator x x x
Software Configurable x x x
Test Switch x x x
SNMP Support Available x x x
Warranty 2 years, with Lifetime Equipment Protection
Approvals UL listed, CSA certified, FCC Class B compliance, Novell Labs approved
Input line 6 ft. attached
Output receptacles (NEMA 5-15R) 4 8 6
Maximum Dimensions (HxWxD) 6.2x5.4x14.1" 17.0x7.7x21.5"
Net Weight 29 lbs. 112 lbs 126 lbs
Shipping Weight 32 lbs 132 lbs 145 lbs
OPERATION SU700X93 SU2200X93 SU3000RMX93
Nominal Input voltage 120 Vac, single phase; 50 or 60 Hz (auto-selectable)
Transfer time (typical/max) 2/4 milliseconds, includes detection time
On-Battery Output voltage Pure sine wave output at 115 Vac +/-5%, -10% after low battery warning, synchronized to utility line
Smart Boost and Smart Trim Operation On-Line operation for input between 90 to 145 Vac. Output will be 103 to 132 VAC.
AVR Boost increases voltage 12% if input is 90 to 103 Vac. AVR Trim reduces voltage 12% below input if 145 to 132 Vac.
Double Pole Circuit breaker/Double Pole Switch Safety reasons dictate that the "Delta Power" shipboard Smart-UPS have a double pole circuit breaker and a double pole switch since both legs carry power.
Capacity (Volt-Amps, Watts) 700,450 2200, 1600 3000, 2250
Load power factor range, crest factor range 0.5 to 1.0, <5
Surge energy rating, peak current capability 320 Joules, 26kA 480 Joules, 39kA
Normal, common mode clamping response time 0 ns, <5 ns typical
Normal mode surge voltage let through when subjected to IEEE 587 Cat. A 6kV test <0.7% of peak typical <0.3% of peak typical
Normal/common mode noise suppression at 1.0MHz, 3.0MHz, 10.0MHz 68/50, 57/50, 50/27 dB 63/74, 54/48, 47/35 dB 58/60, 52/52, 54/28
Sealed, maintenance-free lead acid batteries with 3-6 year typical lifetime Two 12V, 6.5AH Four 12V, 17AH Eight 12V, 7AH
Recharge time to 90% capacity after discharge into 50% load 1 to 2 hours
Ambient operation 10,000 ft. (3,000 meters) max. elevation, 0-95% humidity non-condensing, 32-113 deg F (0-40 deg C)
Storage elevation 50,000 ft. (15,000 meters) max. 5-113 deg F (-15 - 45 deg C)
Max audible noise at 3 ft. from surface of unit <41 dBA <50 dBA
On line eff. 94%