| Output
|
 |
| Output power
capacity |
3,000 VA
|
 |
| Output power
capacity |
2,250 Watts
|
 |
| Output Voltage
|
208 V
|
 |
| Output Voltage
Note |
2 NEMA 5-15R
receptacles provide a total of 400VA at 120Vac |
 |
| Output Connections
|
| (2)NEMA
5-15R |
|
| (1)NEMA
L6-20R |
|
| (2)NEMA
L6-30R |
|
|
 |
| Waveform type
|
SINE |
 |
 |
| Input
|
 |
| Nominal input
voltage |
208 V
|
 |
| Input frequency
|
50/60 Hz +/-
3 Hz (auto sensing) |
 |
| Input connection
type |
NEMA
L6-20P
|
 |
| Input voltage
range for main operations |
157 - 255 V
|
 |
| Input voltage
adjustable range for main operations |
151 - 268 V
|
 |
 |
| Batteries
|
 |
|
Typical backup time
at half load
| 18.0 minutes
|
 |
| Battery type
|
Maintenance-free
sealed Lead-Acid battery with suspended electrolyte : leakproof
|
 |
| Typical recharge
time |
5 hour(s) |
 |
| Replacement
battery cartridge |
(1) RBC11 |
 |
 |
| Communications
& Management |
 |
| Interface port
|
DB-9 RS-232;Smart-Slot
card |
 |
| Management
Software included |
PowerChute
Smart-UPS Bundle |
 |
| Control panel
|
LED status
display with load and battery bar-graphs and On Line : On Battery
: Replace Battery : and Overload Indicators |
 |
| Audible alarm
|
Alarm when
on battery : distinctive low battery alarm : configurable delays
|
 |
| Emergency Power
Off (EPO) |
Optional |
 |
 |
| Surge
Protection and Filtering |
 |
| Surge energy
rating (Joules) |
480 |
 |
| Filtering |
Full time multi-pole
noise filtering : 0.3% IEEE surge let-through : zero clamping
response time : meets UL 1449 |
 |
 |
| Physical
|
 |
| Maximum height
dimensions |
17.00 inches,
43.2 cm |
 |
| Maximum width
dimensions |
7.70 inches,
19.6 cm |
 |
| Maximum depth
dimensions |
21.50 inches,
54.6 cm |
 |
| Net weight
|
137 lbs,
62.2 kg |
 |
| Shipping weight
|
156 lbs,
70.8 kg |
 |
| Color |
Beige |
 |
 |
| Environmental
|
 |
| Operating Temperature
|
0 - 40 °C
|
 |
| Operating Relative
Humidity |
0 - 95% |
 |
| Operating Elevation
|
0-10000 feet
|
 |
| Storage Temperature
|
-15 - 45 °C
|
 |
| Storage Relative
Humidity |
0 - 95% |
 |
| Storage Elevation
|
0-50000 feet
|
 |
| Audible noise
at 1 meter from surface of unit |
53 dBA
|
 |
| Online thermal
dissipation |
375 BTU/hr
|
 |
 |
| Conformance
|
|
 |
| Approvals |
CSA;FCC A;UL
1778 |
 |
| Standard warranty
|
2 years repair
or replace;optional on-site warranties available;optional extended
warranties available |
 |
| Equipment protection
policy |
$25000 lifetime
equipment protection policy |
 |
 |