Product Overview
Description APC Smart-UPS, 2200VA/1980W, Input  230V/ Output  230V, Interface Port DB-9 RS-232, SmartSlot, USB
Features Audible Alarms, Automatic Voltage Regulation (AVR), Built-in SmartSlot, EPO, Hot Swap Batteries, Intelligent Battery Management, Line-interactive, Overload Indicator, Rack Mount, Replace Batt Indicator, Sine-wave output, Software, Status Indicator LED's, Surge Protection, USB Connectivity, User Replaceable batteries
Includes CD with software, Rack Mounting Brackets, Smart UPS signaling RS-232 cable, User Manual, USB cable
Options For optional AC connections, baying, management devices, service, or software please contact Bomara Associates
Technical Specifications
Output
Output power capacity 2,200 VA
Output power capacity 1,980 Watts
Nominal output voltage 230 V
Output Voltage Note Configurable for 220 : 230 or 240 nominal output voltage
Waveform type Sinewave
Output Connections
(8)IEC 320 C13
(3)IEC Jumpers
(1)IEC 320 C19
Input
Nominal input voltage 230 V
Input frequency 50/60 Hz +/- 3 Hz (auto sensing)
Input Connection Type
IEC-320 C20
Schuko CEE 7 / EU1-16P
British BS1363A
Input voltage range for main operations 160 - 286 V
Input voltage adjustable range for main operations 151 - 302 V
Batteries
Battery type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time ** 3 hour(s)
Replacement battery cartridge UPS Battery Replacement
Communications & Management
Interface port DB-9 RS-232, SmartSlot, USB
Available Smart Slot Interface Quantity 1
Control panel LED status display with load and battery bar-graphs and On Line : On Battery : Replace Battery : and Overload Indicators
Audible alarm Alarm when on battery : distinctive low battery alarm : configurable delays
Emergency Power Off (EPO) Yes
Included Software PowerChute Smart-UPS Bundle
Surge energy rating (joules)  
Surge energy rating 480 joules
Filtering Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
Runtime
Typical backup time
at half load
15.7 minutes (990 Watts)
Typical backup time
at full load
5.2 minutes (1980 Watts)
Runtime Chart Smart-UPS Rackmount
Physical
Maximum height dimensions 3.50 inches ( 8.89 cm)
Maximum width dimensions 19.00 inches ( 48.26 cm)
Maximum depth dimensions 26.00 inches ( 66.04 cm)
Net weight 96.00 lbs ( 43.64 kg)
Shipping Weight 125.00 lbs ( 56.82 kg)
Shipping Height 10.00  inches ( 25.40 cm)
Shipping Width 24.50  inches ( 62.23 cm)
Shipping Depth 38.60  inches ( 98.04 cm)
Color Black
Units per Pallet 8.0
Environmental
Operating Environment 0 - 40 °C (32 - 104°F)
Operating Relative Humidity 0 - 95%
Operating Elevation 0-10000 feet (0-3000 m)
Storage Temperature -15 - 45 °C (5 - 113°F)
Storage Relative Humidity 0 - 95% Non-condensing
Storage Elevation 0-50000 feet (0-15000 m)
Audible noise at 1 meter from surface of unit 47 dBA
Online thermal dissipation 300 BTU/hr
Conformance  
Approvals C-tick, CE, EN 50091-1, EN50091-2, GOST, PCBC, VDE
Standard warranty 2 years repair or replace, optional on-site warranties available , optional extended warranties available

** The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.