Models |
0650
|
| Capacity
VA/Watts |
3.0/2.1 |
6.0/4.2 |
9.0/6.3 |
12.0/8.4 |
15.0/10.5 |
18.0/12 |
Dimensions
HxWxD
3-Slot Cabinet |
17.8x17x25.4
in
453x432x645
mm
|
|
| 6-Slot
Cabinet |
31.5x17x25.4
in
800x432x645
mm |
|
| 9-Slot Cabinet |
47x24x28.4
in
1194x610x724 mm |
| 12-Slot Cabinet |
60.7x24x28.4
in
1542x610x724 mm |
| Input Connection |
Hardware
input standard (Optional input cords available) |
Hardwired |
| Output Connection |
Hardware
output standard (Optional internal output
distribution available) |
Typical Runtime
full/half load |
8-10/20-25
minutes typical (Optional internal and external
runtime available
|
| Battery
Type |
Hot-swappable,
sealed, maintenance-free lead acid batteries
with 3-5 year typical lifetime |
| Operation |
| Nominal Input Voltage |
208-240VAC
or 200/100, 208/120, 220/127, 220/110, 240/120 |
| Input Voltage
Range |
176-276VAC |
| Input
Power Factor |
>0.98 |
| Input
Current THD |
<
10% at 100% load |
| Operating Frequency |
50/60Hz
(±3Hz) |
| Nominal Output Voltage |
208-240
or 200/100, 208/120, 220/127, 220/110, 240/120 |
| Output Voltage Regulation |
±3%
of nominal |
| Output Voltage Waveform |
Sine
wave |
| Output Voltage THD |
<
3% THD (linear loads) |
| Overload Capacity |
150%
for 10 seconds, 300% for 12 cycles |
| Recharge Time |
<
4 hours standard |
| Lightning & Surge
Protection |
ANSI/IEEE
C62.41 (1991); ANSI/IEEE C62.45 (1987)
Category B. Meets IEC 61000-4-5
|
| Efficiency |
>
88% (97%) |
| Safety Certification |
UL,
CSA (cUL), TUV, CE |
| EMC Emissions |
FCC
and CSPR 22 class A |
| EMC Immunities |
EN/IEC
61000-4-2, -3, -4, -5, and -2-2 |
| Other
Standards |
ISO9000
And Year 2000 compliant |
| Communications |
| LCD
Display |
Programmable
4 x 20 character backlit LCD
Multiple Languages (English, French, Spanish,
German) |
| Communication
Slots |
2
BestDock™ Slots |
| Communications
Port |
RS-232
serial port (DB-9) plus contact closures |
| SNMP
Capability |
Yes |
| Contact
Closure |
Yes |
| Emergency
Power Off (EPO) |
Input
for external EPO closure |
| Environmental |
| Operating Temperature |
0
to 40°C, 32 to 104°F (derate 1° C per 300m above
1525m) |
| Storage Temperature |
-20
to 40°C (60°C without batteries)
-4 to 104°F (140°F without batteries) |
| Relative Humidity |
5
- 95% non-condensing |
| Audible Noise at One Meter |
<
50dBA |
| Altitude |
3,050m
(10,000ft.) above sea level |
| All specifications
subject to change without
notice. |