Models |
1kVA |
1.5kVA |
2kVA |
3kVA |
| Part
Number |
0620-1000RE |
0620-1500RE |
0620-2000RE |
0620-3000RE |
| Capacity
VA/Watts |
1000/700 |
1500/1050 |
2000/1400 |
3000/2100 |
Dimensions
inches
mm
HxWxD |
3.35 x 19 x 19.3
85 x 483 x 490 |
Weight
lbs
kg |
41
18.5 |
48
21.6 |
28
12.7 |
29
13.2 |
| Input
Connection |
C14
(10A) Plug |
C20
(16A) Plug |
Output
Receptacle
quantity/type |
(4)
C13 (10A) |
(4)
C13 (10A)
(1) C19 (16A) |
Typical
Runtime
full load
half load
(minutes) |
9
24 |
8
23 |
14**
39 |
7**
24 |
| Operation |
|
Nominal Input Voltage |
230
VAC |
|
Input Voltage Range (for on-line operation) |
160
- 276 VAC |
| Operating
Frequency (on-line) |
50/60Hz
±5Hz, autosensing (±2% and ±7% user adjustable) |
| Nominal
Output Voltage |
208/220/230/240VAC
Dip Switch Selectable |
Output
Voltage Regulation
(on line) |
±3% of
nominal |
| Overload
Capacity |
Up
to 110% for 10 seconds then transfer to inverter |
| Transfer
Time |
0
ms |
| On-Battery
Voltage |
230VAC
± 3% selected nominal voltage |
| Operating
Frequency |
Phase
locked to input under normal conditions, ±0.5% on
battery |
| Output
Voltage Waveform |
Sine
wave |
| Output
Protection |
Electronic
overload and short circuit protector |
| Input
Protection |
Fuse
or Circuit Breaker |
| Recharge
Time (to 90%)) |
8
hours |
| Lightning
& Surge Protection |
IEC
801-2, 801-3, 801-4, 801-5 |
| Efficiency |
>87%
on-line (full load, fully charged > load 50%) |
| Safety
Certification |
EN50091-1
(1994.4) and EN60950 (1992.8) |
| EMI
Compliance |
EN55022,
Class B, CD EMC directive |
| Communications |
BestDockô
slot. DB9 male for RS-232 communications and contact
closure. |
| Testing
Standards |
IEEE/ANSI
C62.45 (1991) |
| Indicators |
Load levels (on AC), Battery discharge level (on batter),
Fault indicator & LED mimic panel indicators |
| Audible
Alarms |
Battery
discharge, Low battery, Overload, UPS fault |
| Environmental |
|
Operating Temperature |
0ƒ
to 40ƒ C |
| UPS
Storage Temperature |
-15ƒ
to 50ƒ C (5ƒ to 122ƒ F) |
| Relative
Humidity |
0
to 95%, non-condensing |
| Audible
Noise at one meter |
<50
dBA |
| Altitude |
3000m
(10,000 ft.) without derating |
| All specifications
subject to change without notice. |