Bomara Associates Logo
Best Power - Presented by Bomara Associates
Loading
Bomara Associates Homepage



 

 
Models
700VA
1kVA
1.5kVA
2kVA
3kVA
6kVA
10kVA

Part Number

B610-0700
U
B610-1000U
B610-1500U
B610-2000U
B610-3000U
B610-6000U
B610-010KU
Capacity
(VA/Watts)
700/450 1050/670 1425/950 2250/1600 1700/1275 3000/2250 3000/2250
Dimensions
inches
mm
HxWxD


8.9x5.7x15.1
225x145x400


8.9x5.7x18.3
225x145x465

13.25x7.7x20.2
336x194x511


31.5x10.2x21.9
800x260x555


37.8x13.4x25.6
960x340x650
Weight
lbs
kg

25.4
11.5

30.8
14

42.9
19.5

72.6
33


77
35


266.2
121

517
235
Input Connection

NEMA 5-15P

NEMA L5-20P

NEMA L5-30P

Hardwired

Hardwired*
Output Receptacles
quantity
type


(4) 
NEMA 5-15R


(4) 
NEMA 5-15R
(2) 
NEMA 5-20R

 (4) 
NEMA 5-15R
(2) 
NEMA 5-20R
 

Hardwired

Hardwired*
Typical Runtime
full load
half load
(minutes)


6
18


7
20


6
17


12
29


6
18


7
21


11
27
Operation
Nominal Input Voltage 120 VAC  230 VAC
Input Voltage Range
(for on-line operation)
80 to 138 VAC  176 to 276 VAC
Operating Frequency (on-line) 50/60Hz ± 5Hz, autosensing
Nominal Output Voltage 100/110/120/127VAC
Dip Switch Selectable
208/104, 220/110, 230/115, 240/120VAC
Dip Switch Selectable**
Output Voltage Regulation
(on line)

± 3% of nominal

Overload Capacity

Up to 110% for 10 seconds then transfer to bypass

Transfer Time

0 ms

On-Battery Voltage 120 VAC ± 3% selected nominal voltage
Operating Frequency

Phase locked to input under normal conditions, ±0.5% on battery

Output Voltage Waveform

Sine wave

Output Protection

Electronic overload and short circuit protector

Input Protection

Fuse or Circuit Breaker

Recharge Time (with half load) 8 hours
Lightning & Surge Protection

IEC 801-2, 801-3, 801-4, 801-5

Efficiency >85% on-line (full-load, fully charged > load 50%)
Safety Certification UL1778
EMI Compliance FCC Class A
Communi-
cations

BestDockô slot.  DB9 male for
RS-232 communications and contact closure

Testing Standards

ANSI/IEEE C62.45 (1991)

Indicators

 Load level (on AC), Battery discharge level (on battery), Fault indicator & LED mimic panel indicators

Audible Alarms

Battery discharge, Low battery, Overload, UPS fault

Environmental
Operating Temperature

0† to 40† (32† to 104†F)

Storage Temperature

-15† to 50†C (5† to 122†F)

Relative Humidity

0-95% non-condensing

Audible Noise at
One Meter
<50 dBA
Altitude

3,000m (10,000 ft.) without derating

All specifications subject to change without notice.
* For hardwired unit, ad an "H" to the part number, i.e. B610-3000UH
** Dual voltage available through series or parallel connection of secondary wiring of the included isolation transformer.

   

Product Page | Spec Overview | Spec Details | Price List

 



Best Power Home
Bomara Homepage
Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
email: bobr@bomara.com      web: www.bomara.com