Bomara Associates Logo
Best Power - Presented by Bomara Associates
Loading
Bomara Associates Homepage


 

 

 
Models
700VA
1kVA
1.5kVA
2kVA
3kVA
6kVA
10kVA

Part Number

B610-0700
E
B610-1000
E
B610-1500
E
B610-2000
E
B610-3000
E
B610-6000
E
B610-010K
E
Capacity
(VA/Watts)
700/450 1050/670 1425/950 2250/1600 1700/1275 3000/2250 3000/2250
Dimensions
inches
mm
HxWxD


8.9x5.7x15.1
225x145x400


8.9x5.7x18.3
225x145x465

13.25x7.7x20.2
336x194x511


31.5x10.2x21.9
800x260x555


37.8x13.4x25.6
960x340x650
Weight
lbs
kg

25.4
11.5

30.8
14

42.9
19.5

72.6
33


77
35


200.2
91

396
180

Input Connection

C14 (10 amp) C20 (16 amp) Hardwired
Output Receptacles
quantity
type


(4)
C13 (10 amp)



(4)
C19 (16 amp)

Hardwired

Typical Runtime
full load
half load
(minutes)


6
18


7
20


6
17


12
29


6
18


7
21


11
27
Operation
Nominal Input Voltage 230 VAC  176 - 276 VAC
Input Voltage Range
(for on-line operation)
160 - 276 VAC  176 to 276 VAC
Operating Frequency (on-line) 50/60Hz ± 5Hz, autosensing
Nominal Output Voltage 208/220/230/240VAC
Dip Switch Selectable
Output Voltage Regulation
(on line)

± 3% of nominal

Overload Capacity

Up to 110% for 10 seconds then transfer to bypass

Transfer Time

0 ms

On-Battery Voltage 230 VAC ± 3% selected nominal voltage
Operating Frequency

Phase locked to input under normal conditions, ±0.5% on battery

Output Voltage Waveform

Sine wave

Output Protection

Electronic overload and short circuit protector

Input Protection

Fuse or Circuit Breaker

Recharge Time (with half load) 8 hours
Lightning & Surge Protection

IEC 801-2, 801-3, 801-4, 801-5

Efficiency >85% on-line (full-load, fully charged > load 50%)
Safety Certification EN50091-1 (1994.4) & EN60950 (1992.8)
EMI Compliance EN50081-1 (1992.2)
Communi-
cations

BestDock™ slot.  DB9 male for
RS-232 communications and contact closure

Testing Standards

ANSI/IEEE C62.45 (1991) & IEC 801-2, 801-3, 801-4, 801-5

Indicators

 Load level (on AC), Battery discharge level (on battery), Fault indicator & LED mimic panel indicators

Audible Alarms

Battery discharge, Low battery, Overload, UPS fault

Environmental
Operating Temperature

0º to 40º (32º to 104ºF)

Storage Temperature

-15º to 50ºC (5º to 122ºF)

Relative Humidity

0-95% non-condensing

Audible Noise at
One Meter
<50 dBA
Altitude

3,000m (10,000 ft.) without derating

All specifications subject to change without notice.

   

Product Page | Spec Overview | Spec Details | Price List

 



Best Power Home
Bomara Homepage
Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
email: bobr@bomara.com      web: www.bomara.com
Serving the marketplace for over 35 years