| Models |
700VA
|
1kVA
|
1.5kVA
|
2kVA
|
3kVA
|
6kVA
|
10kVA
|
|
Part
Number |
B610-0700
E |
B610-1000
E |
B610-1500
E |
B610-2000
E |
B610-3000
E |
B610-6000
E |
B610-010K
E |
Capacity
(VA/Watts) |
700/450 |
1050/670 |
1425/950 |
2250/1600 |
1700/1275 |
3000/2250 |
3000/2250 |
Dimensions
inches
mm
HxWxD |
8.9x5.7x15.1
225x145x400
|
8.9x5.7x18.3
225x145x465 |
13.25x7.7x20.2
336x194x511 |
31.5x10.2x21.9
800x260x555
|
37.8x13.4x25.6
960x340x650 |
Weight
lbs
kg |
25.4
11.5
|
30.8
14
|
42.9
19.5
|
72.6
33
|
77
35
|
200.2
91
|
396
180 |
|
Input
Connection |
C14
(10 amp) |
C20
(16 amp) |
Hardwired |
Output
Receptacles
quantity
type |
(4)
C13 (10 amp) |
(4)
C19 (16 amp)
|
Hardwired |
Typical
Runtime
full load
half load
(minutes) |
6
18 |
7
20 |
6
17 |
12
29 |
6
18 |
7
21 |
11
27 |
| Operation |
| Nominal
Input Voltage |
230
VAC |
176
- 276 VAC |
Input
Voltage Range
(for on-line operation) |
160
- 276 VAC |
176
to 276 VAC |
| Operating
Frequency (on-line) |
50/60Hz
± 5Hz, autosensing |
| Nominal
Output Voltage |
208/220/230/240VAC
Dip Switch Selectable |
Output
Voltage Regulation
(on line) |
±
3% of nominal |
| Overload
Capacity |
Up
to 110% for 10 seconds then transfer to bypass |
| Transfer
Time |
0
ms |
| On-Battery
Voltage |
230
VAC ± 3% selected nominal voltage |
| Operating
Frequency |
Phase
locked to input under normal conditions, ±0.5% on battery |
| Output
Voltage Waveform |
Sine
wave |
| Output
Protection |
Electronic
overload and short circuit protector |
| Input
Protection |
Fuse
or Circuit Breaker |
| Recharge
Time (with half load) |
8
hours |
| Lightning
& Surge Protection |
IEC 801-2,
801-3, 801-4, 801-5 |
| Efficiency |
>85%
on-line (full-load, fully charged > load 50%) |
| Safety
Certification |
EN50091-1
(1994.4) & EN60950 (1992.8) |
| EMI
Compliance |
EN50081-1
(1992.2) |
Communi-
cations |
BestDock™
slot. DB9 male for
RS-232 communications and contact closure
|
| Testing
Standards |
ANSI/IEEE
C62.45 (1991) & IEC 801-2, 801-3, 801-4, 801-5 |
| Indicators |
Load
level (on AC), Battery discharge level (on battery),
Fault indicator & LED mimic panel indicators |
| Audible
Alarms |
Battery
discharge, Low battery, Overload, UPS fault |
| Environmental |
| Operating
Temperature |
0º
to 40º (32º to 104ºF) |
| Storage
Temperature |
-15º
to 50ºC (5º to 122ºF) |
| Relative
Humidity |
0-95%
non-condensing |
Audible
Noise at
One Meter |
<50
dBA |
| Altitude |
3,000m
(10,000 ft.) without derating |
| All