| Models |
4.3kVA |
5.3kVA
|
7kVA
|
10kVA
|
12.5kVA
|
18kVA
|
| Part Number |
QFE4.3 |
QFE5.3 |
QFE7 |
QFE10 |
QFE12.5 |
QFE18 |
| Capacity
(kVA/kW) |
4.3/3 |
5.3/3.7 |
7/5 |
10/7.5 |
12.5/10 |
18/15 |
Dimensions
inches
mm
HxWxD |
29.5 x 15.5 x 25
750 x 395 x 635 |
36.5 x 19 x 32*
930 x 485 x 815* |
Weight
lbs
kg |
360
163 |
505
229 |
605
274 |
875
397 |
1341
609 |
1300
589 |
| Input
Connection |
220V/19A
230V/18A
240V/17A |
220V/21A
230V/20A
240V/19A |
220V/27A
230V/26A
240V/24A |
220V/43A
230V/41A
240V/39A |
220V/55A
230V/53A
240V/51A |
220V/81A
230V/78A
240V/75A |
Output
Connection
|
Hardwired
output is standard. Contact Factory for receptacle
options. |
Typical
Runtime
full load
half load
(minutes) |
10
24 |
20
50 |
12
33 |
11
26 |
18
48 |
10
26 |
| Operation |
| Nominal
Input Voltage |
220/230/240 |
| Input
Voltage Range |
+15%,
-20% |
| Operating
Frequency |
50Hz
Nominal (adjustable limits ±0.01Hz to ±3Hz) |
| Nominal
Output Voltage |
220/230/240 |
| Output
Voltage Regulation |
±
3% for input voltages of + 15% to -20% |
| Output
Voltage Waveform |
Sine
wave |
| Output
Voltage THD |
5%
or less at rated kW load |
| Overload
Capacity |
150%
surge and 125% for 10 minutes on-line,
150% surge and 110% for 10 minutes on inverter
|
| Transfer
Time |
0
ms |
| Lightning,
Surge & Noise Protection |
2000:1
spike attenuation using ANSI/IEEE C62.41 Category A and
Category B tests.
Common Mode - >120dB. Normal Mode - >60dB
|
| Efficiency |
90 |
90 |
90 |
90 |
91 |
92 |
| Safety
Certification |
UL
1778, CSA (cUL), GS (TUV),
Complies with European Low Voltage Directive 73/23/EEC
|
| EMI
Compliance |
FCC
Class A,
Complies with European Electromagnetic Compatibility Directive
89/336/EEC |
| Testing
Standards |
ANSI/IEEE
C62.41 (1980); ANSI/IEEE C62.45 (1987); IEC 801-2, 801-3,
801-4, 801-5, EN 500081-1, EN 500082-1, EN 500091-1, EN
500091-2, EN 550022, EN 60950 |
| Communication |
RS-232
serial port (DB-25), plus contact closures |
| Environmental |
| Operating
Temperature |
0†
to 40† C |
| Storage
Temperature |
-20†
C to +60† C |
| Relative
Humidity |
0
to 95% without condensation |
| Audible
Noise at 1m |
50 |
51 |
52 |
55 |
56 |
57 |
| Altitude |
3,050
m (10,000 ft) maximum |
| All
specifications subject to change without notice. |
|
*Batteries
in second cabinet. Contact factory for weights
and dimensions.
|