| Models |
750VA
|
1050VA
|
1425VA
|
1800VA
|
2250VA
|
| Part
Number |
0520-0750RU
|
0520-1050RU
|
0520-1425RU
|
0520-1800RU
|
0520-2250RU
|
| Capacity
(VA/Watts) |
750/450 |
1050/670 |
1425/950 |
1800/1260 |
2250/1600 |
Dimensions
inches
mm
HxWxD |
3.5x17.5x18
88x445x457
|
5.2x17.5x18
133x445x457
|
7x17.5x18
178x445x457
|
Weight
lbs
kg |
46
21 |
60
2
7 |
66
30 |
95
43 |
| Input
Connection* |
NEMA 5-15P
|
NEMA 5-20P
|
NEMA L5-30P
|
Output
Connection
quantity
type |
(6)
NEMA 5-15R
|
(4) NEMA 5-15R
(2) NEMA 5-20R
|
(4)
NEMA 5-15R
(2) NEMA 5-20R
(1)
NEMA L5-30R |
Typical
Runtime
full load
half load
(minutes) |
8
20 |
8
22 |
8
22 |
8.5
24 |
5
17 |
| Operation |
| Nominal
Input Voltage |
120
VAC Sincle-Phase (110 and 128 volts options, user-selectable) |
| Input
Voltage Range (for on-line operation) |
96
to 146 VAC nominal (up to 90 to 156 VAC, user-selectable) |
| Operating
Frequency (on-line) |
50/60Hz
± 5Hz, autosensing |
| Nominal
Output Voltage |
120VAC single phase (110 and 128 volt options, user-selectable) |
Output
Voltage Regulation
(on line) |
±
10% of nominal (at factory default setting) |
| Overload
Capacity |
110%
±8% |
|
Transfer
Time
|
Within
CBEMA limits, undetected by modern computer loads |
| On-Battery
Voltage |
120VAC
± 7%
|
| Output
Voltage Waveform |
Sine
wave |
| Output
Protection |
Automatic
current and overvolt protection |
| Input
Protection |
Circuit
Breaker |
| Recharge
Time (with half load) |
3
hours to 95% |
| Lightning
& Surge Protection |
Tested
to ANSI/IEEE C62.41 categories A & B |
| Efficiency |
>95%
on-line |
| Safety
Certification |
UL1778,
cUL; tested to UL 1449 |
| EMI
Compliance |
FCC
Class B |
FCC
Class A |
| Communications |
BestDockô
slot. DB9 male for RS-232 communications and contact
closure. |
| Testing
Standards |
ANSI/IEEE
C62.41 (1991); National Bureau of Standards FIPS-PUB-94;
IEC 801-2, 801-3, 801-4, 801-5 |
| Indicators |
Buck/Boost
status, Battery status, Load level,
Battery discharge level, Alarms (shutdown, battery test
fail) |
| Audible
Alarms |
Battery
discharge, Low battery, Overload,
Battery replacement needed, UPS fault |
| Environmental |
| Operating
Temperature |
0†
to 40† (32† to 104†F) |
| Storage
Temperature |
-15†
to 50†C (5† to 122†F) |
| Relative
Humidity |
0-95%
non-condensing |
| Audible
Noise at One Meter |
<45
dbA at 1 meter (<50 dBA for 1800VA and 2250VA units) |
| Altitude |
3,000m
(10,000 ft.) without derating |
| All