| Models |
750VA
|
1050VA
|
1425VA
|
2250VA
|
|
Part
Number |
0520-0750RE
|
0520-1050RE
|
0520-
1425RE |
0520-2250RE
|
Capacity
(VA/Watts) |
750/450 |
1050/670 |
1425/950 |
2250/1600 |
Dimensions
inches
mm
HxWxD |
3.5x17.5x18
88x445x457
|
5.2x17.5x18
133x445x457
|
7x17.5x18
178x445x457
|
Weight
lbs
kg |
31
14
|
44
20
|
50
23
|
81
37
|
| Input
Connection |
C14
(10 amp) plug |
C20
(16 amp) plug |
Output
Connection
quantity
type |
(4)
C13 (10 AMP) |
(4)
C13 (10 amp)
(1)
C19 (16 amp)
|
Typical
Runtime
full load
half load
(minutes) |
8
20 |
8
22 |
8
22 |
5
17 |
| Operation |
| Nominal
Input Voltage |
230
VAC Single-Phase
(220 and 240 volt options, user-selectable) |
Input
Voltage Range
(for on-line operation) |
188
to 270 VAC nominal
(up to 180 to 284 VAC, user-selectable) |
| Operating
Frequency (on-line) |
50/60Hz
± 5Hz, autosensing |
| Nominal
Output Voltage |
230
VAC single-phase
(220 and 240 volt options, user-selectable) |
Output
Voltage Regulation
(on line) |
±
10% of nominal (at factory default setting) |
| Overload
Capacity |
110%
±8% |
| Transfer
Time |
Within
CBEMA limits, undetected by modern computer loads |
| On-Battery
Voltage |
230
VAC ± 7% |
| Operating
Frequency |
50/60Hz
± 5Hz, autosensing |
| Output
Voltage Waveform |
Sine
wave |
| Output
Protection |
Automatic
current and overvolt protection |
| Input
Protection |
Circuit
Breaker |
| Recharge
Time (with half load) |
3
hours to 95% |
| Lightning
& Surge Protection |
Tested
to ANSI/IEEE C62.41 categories A & B |
| Efficiency |
>95%
on-line |
| Safety
Certification |
EN50091-1;
CE low voltage directive |
| EMI
Compliance |
EN55022;
Class B; CE EMC directive |
| Communications |
BestDockô
slot. DB9 male for
RS-232 communications and contact closure
|
| Testing
Standards |
ANSI/IEEE
C62.41 (1991); National Bureau of Standards FIPS-PUB-94;
IEC 801-2, 801-3, 801-4, 801-5
|
| Indicators |
Buck/Boost
status, Battery status, Load level,
Battery discharge level, Alarms (shutdown, battery test
fail)
|
| Audible
Alarms |
Battery
discharge, Low battery, Overload,
Battery replacement needed, UPS fault
|
| Environmental |
| Operating
Temperature |
0†
to 40† (32† to 104†F) |
| Storage
Temperature |
-15†
to 50†C (5† to 122†F) |
| Relative
Humidity |
0-95%
non-condensing |
Audible
Noise at
One Meter |
<40
dbA at 1 meter (<50 dBA for 2250VA units) |
| Altitude |
3,000m
(10,000 ft.) without derating |
| All