| Models |
400VA
|
750VA
|
1000VA
|
| Part Number |
0325-0400U
|
0325-0750U
|
0325-1000U
|
| Capacity
(VA/Watts) |
400/250
|
750/470
|
1000/630
|
Dimensions (inches)
H x W x D (mm) |
6
x 4 x 14.25
155 x 100 x 363
|
8.25
x 6.5 x 14.25
213 x 163 x 363
|
Weight
(lbs)
(kg)
|
17.5
7.5
|
31
14.1
|
35.5
16.2
|
| Input Connection |
C14
(10A) Plug
|
| Output
Receptacle Quantity & Type |
(4) C13 (10A) |
(6)
C13 (10A) |
| Typical
Runtime: (Full Load) |
7 |
7 |
7 |
| (minutes)
(Half Load) |
16 |
16 |
18 |
| Operation |
| Nominal
Input Voltage |
230 VAC
Single phase (208 and 240 volt options, user-selectable) |
| Input Voltage
Range (for on-line operation) |
188 to
270VAC nominal (180 to 284 VAC, user-selectable) |
| Operating
Frequency (on-line) |
50/60
Hz ±5 Hz, autosensing |
| Nominal
Output Voltage |
230VAC
single phase (208 and 240 volt options, user-selectable) |
| Output
Voltage Regulation (On-line) |
+/- 10%
of nominal (at factory default setting) |
| Overload
Capacity |
110% ±8% |
| Transfer
Time |
4 ms typical |
| On-Battery Voltage |
230VAC
± 10% |
| Frequency
(On-Battery) |
50 or 60
Hz +/- 0.5 Hz auto-sensing |
| Operating
Output Voltage Waveform |
Stepped
sine-wave |
| Output
Protection |
Automatic
current and overvoltage protection |
| Input Protection |
Fuse |
| Recharge
Time (to 90% capacity) |
8 hours |
| Lightning
& Surge Protection |
Tested
to ANSI/IEEE C62.41 Category A |
| Efficiency |
>95%
on-line |
| Safety
Certification |
EN50091-1;
CE low voltage directive |
| EMI Compliance |
EN55022,
Class B; CE EMC directive |
| Communications |
DB9 male with RS-232 communication and contact closure |
| Testing
Standards |
ANSI/IEEE C62.41 (1991), National Bureau Of Standards
FIPS-PUB-94; IEC 801-2, 801/3, 801-4, 801-5 |
| Indicators |
Buck/Boost status, Battery status, Load level, Battery
discharge level, Alarms (shutdown, battery test fail) |
| Audible
Alarms |
Battery discharge, Low battery, Overload, Battery replacement
needed, UPS fault |
| Environmental |
| Operating
Temperature |
0† to 40†
(32† to 104†F) |
| Storage
Temperature |
-15† to
50†C (5† to 122†F) |
| Relative
Humidity |
0-95% non-condensing |
| Audible
Noise at One Meter |
<40
dbA at 1 meter |
| Altitude |
3,000m (10,000 ft.) without derating |
| All
specifications subject to change without notice. |
|
| Patriot
Pro II Runtimes for Typical Applications in Minutes |
| Load (VA) |
50 |
100 |
200 |
300 |
400 |
500 |
600 |
700 |
800 |
900 |
1000 |
| 1000VA |
225 |
142 |
69 |
41 |
26 |
18 |
16 |
13 |
11 |
9 |
7 |
| 750VA |
104 |
60 |
35 |
21 |
15 |
12 |
9 |
8 |
-- |
-- |
-- |
| 400VA |
68 |
33 |
16 |
10 |
7 |
-- |
-- |
-- |
-- |
-- |
-- |