ABC2000-2S
Part # 95083-XX**
|
| VA Ratings |
2.0 kVA |
| Frequency |
60 Hz. |
| BTU/Hr. Output |
171 |
| T.H.D Max. % |
<1% |
| Load Surge Current @ |
|
1/2 cycle |
200 amps |
1 second |
40 amps |
10 seconds |
21 amps |
| Input Voltage |
208 or 240 |
| Output Voltage |
120/240 |
| Input Current 208/240 |
9.8 amps/ 8.5 amps |
| Output Current |
8.33 amps per leg |
| Efficiency |
97.5% |
| Voltage Drop No Load to Full Load |
2.5% |
| Wall mountable* |
|
| Safety Agency Listing |
UL and cUL |
| Shipping Weight (lbs.) |
73 |
|
* When ordering by model number, add "W" to model number above for wall mount option.
ABC2000-2S - Part # 95083-XX**
**When ordering, add two digit number from below in place of XX to specify receptacle option desired.
Available Plug/Receptacle Options

-04 - L14-20 plug, one L14-20R receptacle and
two 5-20R duplex receptacle
-07 - 14-20P plug, one L14-20R receptacle and
two 5-20R duplex receptacle
-11 - L6-20P plug, one L6-20R receptacle, and
two 5-20R duplex receptacle
-14 - 6-20P plug, one L6-20R receptacle, and
two 5-20R duplex receptacles
-24 - L14-20 plug, one L14-20R receptacle, and
two 5-20R duplex receptacle with cUL
listing
-27 - 14-20P plug, one L14-20R receptacle and
two 5-20R duplex receptacle with cUL
listing
-31 - L6-20P plug, one L6-20R receptacle, and
two 5-20R duplex receptacles with cUL
listing
-34 - 6-20P plug, one L6-20R receptacle, and
two 5-20R duplex receptacles with cUL
listing
|
Noise Rejection-Isolation: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input,
the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM,
NM-CM).
Surge Voltage Withstand Capability: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @
200 amps, 0.5 µsec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 µsec risetime, 100 kHZ decay
|