GLOBAL POWER INTERFACE SERIES 2000 SPECIFICATIONS

General Specifications - Model ABC35.0-XD20Y

Input Voltage

208/240/480/600 delta connection (4 wire)

Output Voltage
208/120 wye (5 wire)
Frequency
60 Hz. only
Continuous Capacity
35 kVA
BTU/Hr. Output
3585
Efficiency
> 97% (at full load, unity power factor)
Step Load Change
+ 0.8% (at unity power factor)
Noise Rejection

With unit under power and the isolation transformer configured for a transformation ratio of 1:1 and with an ANSI/IEEE C62.41, Category A pulse applied either normal mode
or common mode at the input, the noise output voltage will be less than 10 volts normal
mode and less than .5 volts (½ of one volt) common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).

Surge Voltage Withstand
Tested under power to ANSI/IEEE C62.41, Category A & B (formerly IEEE587-1980). Power conditioner tested to withstand up to 6000 volts @ 3000 amp ringwave and unipo lar impulse.
Construction Materials
Transformer wires are copper and insulated with Class H materials. Windings are insu lated with Nomex paper insulation before vacuum varnishing. Internal wiring is a minimum of 200 degree C rated and sleeved with Class H materials. Grain oriented silicon iron cores are constructed using 14 mil. laminations interleaved one to one. Eddy currents are minimized and external magnetic fields are below 0.1 oersted (at 12 inches distance in any direction).
Physical Dimensions
H x W x D - inches (mm.)
35 x 22 x 39 (889 x 559 x 990)
Weight in lbs. (kg.)
910 (414)

 

Input Connection Requirements*

Input Voltage
Input Current (FLA)
Supply Breaker Rating @ Switchgear
AIC (Current Interrupt Capacity of Input Circuit Breaker)
Minimum Input Conductor Size (includes ground)
Input Lug Maximum Wire Size
208
97
125
25 kAmps
2 AWG
2 AWG
240
84
110
25 kAmps
3 AWG
2 AWG
480
42
60
25 kAmps
6 AWG
2 AWG
600
34
45
25 kAmps
8 AWG
2 AWG

* Supply breaker ratings are determined by NEC guidelines limiting breaker loading to 80% of rated breaker capacity. Calculations for supply breaker recommended ratings are based on input full load amps multiplied by 1.25 and then selecting the next larger standard size breaker. Wire sizes shown in the input and output connection tables of this specification sheet are the minimum sizes allowed by electrical codes for each supply breaker rating and are taken from the 2002 National Electrical Code Article 310.16 table references for use in 90° C installations.

 

Output Connection Requirements

Output Voltage
Output Current (FLA)
Minimum Output Conductor Size (includes ground)
Output Lug Maximum Wire Size
208/120
97
3 AWG
2/0 AWG

 

Input Voltage Changes

This power conditioner is equipped with a fixed input circuit breaker. If changes are required to the input voltage setting of the
power conditioner, it will be necessary to replace the fixed breaker and set input voltage taps appropriately per the following
diagram. Please contact POWERVAR Technical Support to order a replacement breaker and for assistance in making any
required changes.

VAC
Connect each phase
208
H1 to H3-4, H2 to H1-4 and H3 to H2-4
240 H1 to H3-3, H2 to H1-3 and H3 to H2-3
480 H1 to H3-2, H2 to H1-2 and H3 to H2-2
600 H1 to H3-1, H2 to H1-1 and H3 to H2-1

 

H1, H2, H3 to the Main Input Circuit Breaker