ABC830-11R
|
| VA Ratings |
1000 |
| Frequency |
60 Hz. |
| BTU/Hr. Output |
171 |
| T.H.D Max. % |
<1% |
| Load Surge Current @ |
|
1/2 cycle |
325 amps |
1 second |
156 amps |
10 seconds |
45 amps |
| Input Voltage |
|
| Output Voltage |
120 |
| Output Current |
8.3 amps |
| Efficiency |
95% |
| Voltage Drop No Load to Full Load |
5% |
| Wall mountable* |
|
| Safety Agency Listing |
UL and cUL |
| Shipping Weight (lbs.) |
45 |
|
NOISE REJECTION-ISOLATION: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input,
the noise output voltage will be less than 10V normal mode (-60 db) and less than 0.5V common mode (greater than –80 db from 1 Hz to 5 MHz)
in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM) .
SURGE VOLTAGE WITHSTAND CAPABILITY: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @
200 amps, 0.5 µsec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 µsec risetime, 100 kHZ decay.
ABC830-11R - 98100-XX
NEMA5-15P plug. Rear panel has 14 NEMA 5-15R receptacles. Front panel has 2
NEMA 5-15R receptacles. |