ABCE600-22IECR
PN # 57060-23GR
|
| Type |
Medical grade - listed to IEC60601 |
| VA Ratings |
600 |
| Watt Rating |
420 |
| Inverter Waveform |
Low distortion sine wave |
| Transfer Time |
4 ms. typical |
| Frequency |
50/60 Hz. |
| BTU/Hr. Output |
125 |
| T.H.D. Max. % |
<3% on battery |
| On Line Efficiency |
93% |
| Input Voltage |
230 |
| Input Current |
3.1 amps |
| Output Voltage |
230 |
| Output Current |
2.6 |
| Input Voltage Range Without Using Battery |
181-290 volts |
| Output Regulation (on line) |
±10% |
| Output Regulation (on battery) |
±5% |
| Backup time (full/half load) |
6/20 minutes |
| Communications Interface |
DB9, USB |
| Compliance |
UL, IEC60601,CE, RoHS |
| Shipping Weight (kg.) |
25.4 |
|
Front Panel Controls
• Power On/Off
• Test
• Load Level LED Gauge
• Battery Charge LED Gauge
• Output receptacle status
• Voltage Manager Boost LED
• Voltage Manager Nominal LED
• Voltage Manager Buck LED
• On Battery LED
• Replace Battery LED
• Overload LED
Rear Panel Information and Controls
• IEC320 Inlet Module
• Ten (10) IEC320 receptacles controllable via Communications
Manager - spaced for DC power supplies
• Communications Manager DB9 port, USB port
• Circuit Breakers
• Battery enable plugs (also enables cold start on battery)
Internal Batteries
• User hot-swappable (see instruction manual)
• Type - varies by model. See below.
DC Buss Volts: 24
Batteries: 12V, 7AH x 2
• Recharge time - 4 hours to 80% capacity |
Environmental
• Temperature:
0 - +40° C (32 - 104°F) Operating
-20 - +60° C (-40 - +140° F) Shipment,
Storage
• Humidity: 5 - 90% non-condensing (Operating,
Shipment, Storage)
• Altitude: 3,000m (10,000 ft.) max. (Operating,
Shipment, Storage)
Safety Agency Information
North American Standard models are UL and cUL listed to
UL1778. International Standard models are
UL listed. All models for international use carry the CE
mark.
North American medical versions of this uninterruptible
power manager meet all requirements for
UL60601-1 and cUL C22.2 No. 60601.1.
International medical versions of this uninterruptible
power manager meet all requirements for IEC60601-1 and
European derivatives EN60601.
EMC Conformance
Low/High Voltage Models: FCC Part 15 J Class A (Class
B optional)
International Voltage Models: FCC Part 15 J Class A
(Class B optional) EN 55022 Class B/CISPR 22, EN
50091-2, IEC 61000-3-2 |
NOISE REJECTION-ISOLATION: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input,
the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM,
NM-CM).
SURGE VOLTAGE WITHSTAND CAPABILITY: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @
200 amps, 0.5 µsec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 µsec risetime, 100 kHZ decay.
NEMA 5-20P plug. Rear panel has 14 NEMA 5-20R receptacles. Front panel has 2
NEMA 5-20R receptacles. |