ABC830-11
Part # 61100-XX
|
ABC1000-11
Part # 61120-XX
|
ABC1200-11
Part #61144-XX
|
ABC1600-11
Part # 61192-XX
|
ABC2000-11
Part # 61240-XX |
| VA Ratings |
1000 |
1200 |
1440 |
1920 |
2000 |
| Frequency |
60 Hz. |
60 Hz. |
60 Hz. |
60 Hz. |
60 Hz. |
| BTU/Hr. Output |
171 |
205 |
246 |
263 |
328 |
| T.H.D Max. % |
<1% |
<1% |
<1% |
<1% |
<1% |
| Load Surge Current @ |
|
|
|
|
|
1/2 cycle |
325 amps |
375 amps |
400 amps |
500 amps
|
500 amps |
1 second |
156 amps |
180 amps |
192 amps |
240 amps
|
240 amps |
10 seconds |
45 amps |
52 amps |
55 amps |
70 amps
|
70 amps |
| Input Voltage |
120 |
120 |
120 |
120 |
120 |
| Output Voltage |
120 |
120 |
120 |
120 |
120 |
| Output Current |
8.3 amps |
10.0 amps |
12.0 amps |
16.0 amps |
20.0 amps |
| Efficiency |
95% |
95% |
95% |
96% |
96% |
| Voltage Drop No Load to Full Load |
5% |
5% |
4% |
4% |
4% |
| Wall mountable* |
|
No |
No |
No |
No |
| Safety Agency Listing |
UL and cUL |
UL and cUL |
UL and cUL |
UL and cUL |
UL and cUL |
| Shipping Weight (lbs.) |
34 |
38 |
43 |
52 |
63 |
|
* When ordering by model number, add "W" to model number above for wall mount option.
Noise Rejection-Isolation: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input,
the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NMCM).
Surge Voltage Withstand Capability: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @
200 amps, 0.5 µsec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 µsec risetime, 100 kHZ decay.
POWERVAR Part #
ABC830-11 - 61100-XX**
ABC1000-11 - 61120-XX**
ABC1200-11 - 61144-XX**
ABC1600-11 - 61192-XX**
ABC2000-11—61240-XX**
**When ordering, add two digit number from below in place of XX to specify receptacle option desired.
Standard Rear Panel Configuration for Models ABC830-11 through ABC1200-11

Option 1 - Standard Plugs/Receptacles
-03 - 5-15P plug and three 5-15R duplex
Option 2 - Hospital Grade Plugs/Receptacle
-13 - 5-15P plug and two 5-15R duplex hospital grade
|
Standard Rear Panel Configuration for Model ABC1600-11

Option 1 - Standard Plugs/Receptacles
-04 - 5-20P plug and three 5-20R duplex
-24 - 5-20P plug and three 5-20R duplex (cUL)
Option 2 - Hospital Grade Plugs/Receptacle
-14 - 5-20P plug and three 5-20R duplex hospital grade
|
Standard Rear Panel Configuration for Model ABC2000-11

Option 1 - Twistlock plug with combination of twistlock
and standard receptacles
-07 - L5-30P plug, one L5-30R, two 5-20R duplex
-08 - L5-30P plug, one L5-20R, two 5-20R duplex
-27 - L5-30P plug, one L5-30R, two 5-20R duplex (cUL)
-28 - L5-30P plug, one L5-20R, two 5-20R duplex (cUL)
Option 2 - Twistlock plug with standard receptacles
-09 - L5-30P plug and three 5-20R duplex
-29 - Lr-30P plug and three 5-20R duplex (cUL)
Option 3 - Twistlock plug and twistlock receptacles
-10 - L5-30P plug and three L5-20R duplex
|
Special Twistlock Configurations for Models ABC830-11 through ABC1200-11

Option 1 - Twistlock plug and twistlock receptacles
-43 - L5-15P plug and three L5-15R duplex |
Combination Configurations for Models ABC1000-11 only

Option 1 - Twistlock plug with standard receptacles
-05 - L5-20P plug with L5-20R and two 5-20R duplex
-44 - L5-20P plug with L5-20R and two 5-15R duplex
|
Special Twistlock Configurations for Model ABC1600-11

Option 1 - Twistlock plug with standard receptacles
-06 - L5-20P plug and three 5-20R duplex
-26 - L5-20P plug and three 5-20R duplex (cUL)
-09 - L530P plug and three 5-20R duplex
Option 2 - Twistlock plug with combination of twistlock
and standard receptacles
-25 - L5-20P plug, one L5-20R and two 5-20R duplex
(cUL) |
|