Bomara Associates Logo
Bomara Associates Homepage

North American Uninterruptible Power Managers
“A” Case Enclosure

 
ABCE240-11
54024-01G
ABCEG240-11
54024-31G
Type
Standard
Ground Guard®
VA Rating
240
240
Watt Rating
168
168
Inverter Waveform
Low distortion sine wave
Low distortion sine wave
Transfer time
4 ms. typical
4 ms. typical
Frequency
60 Hz.
60 Hz.
BTU/Hr. Output
90
90
T.H.D Max. %
<3% on battery
<3% on battery
On Line Efficiency
90%
90%
Input Voltage
120
120
Input Current
2.5 amps
2.5 amps
Output Voltage
120
120
Output Current
2.0 amps
2.0 amps
Input Voltage Range
Without Using Battery
96-151 volts
96-151 volts
Output Regulation (on line)
+/- 10%
+/- 10%
Output Regulation (on battery)
+/- 5%
+/- 5%
Backup time (full/half load)
6/20 minutes
6/20 minutes
Wall mountable*
No
No
Communications Interface
DB9
DB9
Safety Agency Listing
UL 1778 and cUL 1778
UL 1778 and cUL 1778
Shipping Weight (lbs.)
25
25

 

Front Panel Controls
• Power On/Off
• Test
• On Line
• On Battery LED

Additional Model Specific Information

Ground Guard® Models:
Ground Guard models have all the same technical and performance specifications of the standard POWERVAR UPM models. Ground Guard models are equipped with POWERVAR’s patented ground conditioning technology. Ground Guard models prevent the occurrence of ground loops in networked or interconnected system applications. Ground Guard models can be used in lieu dedicated electrical circuits with isolated ground wiring.

Rear Panel Information and Controls
• 6 foot power cord with NEMA 5-15P plug
• Two (2) NEMA 5-15R receptacles
• Communications Manager DB9 port
• Circuit Breaker
• AC Inlet Module
• Site Wiring Fault LED
Internal Batteries
• User hot-swappable (see instruction manual)
• Type - 12 volt, 4.5 amp-hour
• Quantity - 2 pieces
• Recharge time - 6 hours
Environmental
• Temperature
- 0 - +40° C (32 - 104°F) Operating
- 20 - +60° C (-40 - +140° F) Shipment,
Storage
• Humidity - 5 - 90% non-condensing (Operating,
Shipment, Storage)
• Altitude - 3,000m (10,000 ft.) max. (Operating, Shipment, Storage)

Noise Rejection-Isolation: With unit under power and an ANSI/IEEE C62.41Cat. A pulse applied either normal or common mode at the input, the noise output voltage will be less than 10V normal mode and less than 0.5V common mode in all four quadrants (CM-NM, NM-NM, CM-CM, NM-CM).
Surge Voltage Withstand Capability: Tested under power to ANSI/IEEE C62.41 Cat. A & B (formerly IEEE587-1980). Cat. A - 6000V @ 200 amps, 0.5 µsec risetime, 100 kHZ decay, Cat. B - 6000V @ 500 amps, 0.5 µsec risetime, 100 kHZ decay.



Powervar Home Bomara Homepage Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
email: bobr@bomara.com      web: www.bomara.com