Powerware
3115

Specification
Details
|
Electrical
Input
|
|
Power
Levels
|
300,
420, and 650 VA; See Model
Selection Guide below. |
|
Topology
|
Standby |
|
Operating
Voltage Range
|
120
Vac Models: 103 to 142 (default)
120 Vac Models: 88 to 142 Vac (user-selectable)
230 Vac models: 196 to 260 (default)
230 Vac models: 166 to 260 Vac (user-selectable)
|
|
Frequency
|
50/60
Hz |
|
Frequency
Range
|
57
to 63 Hz @ 60 Hz
47 to 53 Hz @ 50 Hz |
|
Current
|
300,
420 and 650 models: 3.5 A @ 120 Vac; 1.8A @ 230
Vac |
|
Protection
|
Resettable
circuit breaker or replaceable |
|
Total
Harmonic Distortion (THD)
|
Same
as input |
|
TVSS
Rating
|
Total
energy rating more than 240J, 6500A Surge voltage
let-through (percentage of applied ANSI C62.41 Cat.
A +6kV test waveform) less than or equal to 5% |
|
AC
Output, Normal Mode
|
|
Voltage
|
120
and 230 Vac; See Model Selection
Guide below. |
|
Frequency
|
50/60
Hz auto-selectable; same as input |
|
Frequency
Regulation
|
Same
as input |
|
Overload
|
110%
+ 10% overload for 3 minutes. SMPS load, pure sine
wave input 120% + 10% for 10 cycles |
|
Efficiency
|
96%
straight through mode @ full load and fully charged
battery |
|
AC
Output, Battery Mode
|
|
Voltage
Regulation
|
Nominal
voltage +/- 5%, -10% at low battery |
|
Waveform
|
Step
wave (synthesized sine) |
|
Frequency
Regulation
|
50/60
Hz +/- 1 Hz of auto-selected nominal frequency |
|
Transfer
Time
|
4
milliseconds, typical |
|
Efficiency
|
>70%,
100% SMPS load |
|
Battery
|
|
Backup
Time
|
See
Battery Run Times table |
|
Battery
Recharge Time
|
12
hours to 95% usable capacity @ nominal line after
full load discharge |
|
Start-On-Battery
|
Startup
with UPS batteries in absence of utility power |
|
Battery
|
12
and 16 Vdc batteries; Valve-Regulated Lead acid
(VRLA), minimum 3 year float service life at 25oC |
|
Battery
Protection
|
Internal
batteries protected by either a fuse or circuit
breaker. Fuse ratings: 30A/32 Vdc and 40A/32 Vdc |
|
Charger
voltage
|
13.5
to 13.8 Vdc |
|
Maximum
Charge Current
|
12V
battery = 0.7 +/- 0.1A
6V battery = 1.2 +/- 0.1A |
|
Replacement/Service
|
User-replaceable |
|
Regulatory
Standards and Requirements
|
|
Safety
|
120
Vac models: UL1778, CAN/CSA C22.2 No. 107.1
230 Vac models: EN50091-1 |
|
EMI/EMC
|
120
Vac models: FCC Part 15 Class B
230 Vac models: EN50091-2 |
|
Immunity
|
IEC-801-2,
-3, -4, -5 |
|
Audible
Noise
|
<40
dBA |
|
Operating
Altitude
|
3000m
(10,000 ft. max.) |
|
Operating
Temperature
|
0oC
to 40oC, 0 to 1500 meters above sea level
0oC to 35oC, 1500 to 3000
meters above sea level |
|
Transit
and Storage Temperature
|
-15oC
to +55oC |
|
Relative
Humidity
|
0
to 95% noncondensing |
|
Mechanical
Dimensions and Weight
|
See
Model Selection Guide
below |
Model
Selection Guide
|
Model
Number
|
Power
Out
(VA/Watts)
|
Input
Connection
|
Output
Connections
|
Dimensions
WxHxD
(cm/in)
|
Weight(kg/lb)<>
|
|
120
V1; 50/60Hz Models for North America,
Central America and parts of South America
|
| PW3115
300 |
300/180 |
5-15P2 |
(2)
5-15R |
15.5
x 8.6 x 32.3
6.1 x 3.4 x 12.7 |
5.2/11.5 |
| PW3115
420 |
420/252 |
5-15P2 |
(2)
5-15R |
15.5
x 8.6 x 32.3
6.1 x 3.4 x 12.7 |
5.2/11.5 |
| PW3115
650 |
650/400 |
5-15P2 |
(4)
5-15R |
16.3
x 11.7 x 35.6
6.4 x 4.6 x 14.0 |
7.5/16.5
|
230V3; 50/60 Hz Models for Europe, Middle
East, Africa, Asia, Australia, & parts of South
America. |
| PW3115
300i |
300/180 |
IEC320,
10A |
(2)
IEC-3204 |
15.5
x 8.6 x 32.3
6.1 x 3.4 x 12.7 |
5.2/11.5 |
| PW3115
420i |
420/252 |
IEC-320,
10A |
(2)
IEC-3204 |
15.5
x 8.6 x 32.3
6.1 x 3.4 x 12.7 |
5.2/11.5 |
| PW3115
650i |
650/400 |
IEC-320,
10A |
(4)
IEC-3204 |
16.3
x 11.7 x 35.6
6.4 x 4.6 x 14.0 |
7.5/16.5 |
1.
120V default; 110V and 127V user-selectable.
2. 6' line cord.
3. 230V default; 220V and 240V user-selectable.
4. Ships with two IEC interconnecting cords.
|
Battery Run Times
(in
minutes)
|
Application
|
Load
(Connected Equipment) |
PW3115
300(i) |
PW3115
420(i) |
PW3115
650(i) |
| Electronic
Cash Register |
75
VA/45 Watts |
30 |
35 |
41 |
| Stackable
Hub |
150
VA/90 Watts |
24 |
25 |
32 |
| Router |
200
VA/120 Watts |
16 |
17 |
27 |
| Intelligent
Terminal or POS |
300
VA/180 Watts |
10 |
11 |
18 |
| Pentium
PC or Power Mac w/15" monitor |
350
VA/210 Watts |
|
7 |
16 |
| Moderately
configured Pentium PC or Power Mac w/15" monitor |
420
VA/252 Watts |
|
6 |
12 |
| Moderately
configured Pentium PC or Power Mac w/17" monitor |
500
VA/300 Watts |
|
|
9 |
| Heavily
configured Pentium PC or Power Mac w/19" monitor |
600
VA/360 Watts |
|
|
7 |
| Heavily
configured Pentium PC or Power Mac w/21" monitor |
650
VA/390 Watts |
|
|
6.5 |
| Backup
times are approximate and may vary considerably
due to modifed configurations, environmental conditions,
ambient temperature, battery age, and other factors.
|
|
|
|