Electrical
Input |
| Nominal
Voltage |
120V
Models are 110V or 120V user-selectable; 230V models are 220V,
230V or 240V user-selectable |
| Input voltage ranges for
user-selectable voltages |
+\- 20% for nominal voltage
at full load |
| Operating
Frequency |
50/60Hz,
Auto-sensing |
| Frequency Range |
46-65Hz |
Electrical
Output |
| On Utility
Voltage Regulation |
-10%
to +6% of nominal |
| On Battery voltage Regulation |
±5%
RMS |
| Voltage
Wave Shape (on battery) |
Sine
Wave |
| Over Current Protection |
Electronic current limit |
Battery |
| Battery Type |
Sealed, lead-acid; maintenance
free |
| Battery Run time |
See Battery Run Time Chart |
| Battery Replacement |
Hot-swappable internal batteries |
| Recharge Time |
<3
hours to 90% usable capacity |
| Start-On-Battery |
Allows UPS operation without utility
input |
General |
| Diagnostics |
Self-test @ power up |
| Transfer Time |
2-4ms typical |
| Dimensions and weights |
See Model Selection Guide |
| Overload (normal operation) |
110% overload, shutdown after 3 minutes; 150% overload,
shut down 10 cycles |
Communications |
| User
Interface |
LED status
display with AC power on, load Group, Overload, On Battery and
General Alarm indicators, Site Wiring Fault Indicator on rear panel
for low volt models. |
| Audible Alarms |
For various UPS alarm conditions,
including: On Battery, Low Battery, Overload, UPS fault |
| Network
transient Protector |
UL
497 A, In/out jacks RJ45 (high voltage models network protection) & RJ11
(low voltage models modem protection) |
| X-Slot Optional Communication
cards |
ConnectUPS-X Web/SNMP/xHub
Card; USB card ; Relay card |
| Standard
Communications |
1
x RS-232 Serial Port & 1 x xUSB Port |
| Cable |
6-foot communications cable
included |
| Power
Management Software |
Powerware
Software Suite CD-ROM (bundled with UPS) |
Environmental |
| Safety
Markings |
120V
Models: UL; cUL
230V Models: C-Tick; CE, TUV, cUL, UL |
| Safety Conformance |
120V Models: UL
1778; UL497A; cUL (CAN/CSA C22.2,
No. 107.1)
230V Models: UL1778, UL 497A (data line only);
cUL (CAN/CSA C22.2, No. 107.1); EN 50091-1-1 and
IEC 60950 |
| EMC Compliance |
120V
Models: FCC Part 15 subpart J Class A, ICES-003;
230V Models: EN 50091-2. FCC Part 15 subpart J Class A, ICES-003 |
| Operating Temperature |
0
to 40° C (32 to 104° F) |
| Storage
Temperature |
-15
to 50° C (5 to 122° F) |
| Relative Humidity |
5% to 95% non-condensing |
| Surge
Suppression |
ANSI
C62.41 Category A (formerly IEEE 587) |
| Audible Noise |
Less than 40 dBA typical |
| Altitude |
Up to
3000M (10,000 ft) without derating |
| 1 Specifications
typical and are subject to change without notice due to continuing
product improvement programs. |