Electrical
Input
|
| Voltage |
120
and 230 Vac Nominal; see Model
Selection Guide for user-selectable voltages |
| On
Line Voltage Range |
+20%
for nominal voltage at full load |
| Nominal
Input Frequency |
45-65
Hz, 50/60 Hz; auto-sensing
|
| Input
Protection |
120V
models: Resettable circuit breaker
230V models: AC source overcurrent protection device
(required)
|
| Connection |
120V
models: 6 ft. cord w/5-I5P
230V models: IEC-320, 10A male connector
|
|
Electrical
Output
|
| Power
Levels |
500-1400
VA
|
| Online
Regulation |
-10%,
+6% of nominal voltage
|
| On
Battery Voltage Regulation |
+/-5%
of nominal voltage; -10% after low battery warning
|
| On
Battery Frequency Regulation |
+/-0.1
Hz of nominal frequency
|
| Voltage
Wave Shape |
Sine
wave (during normal and battery operation)
|
| Connections |
See
Model Selection Guide
|
| Interconnecting
Cords (230V models) |
2
ea. IEC-320, 10A
|
|
Indicators
and Controls
|
| Front
Panel LEDs |
Power
on, on battery, overload, and battery fault
|
| Front
Panel Buttons |
On/Off
and alarm silence/self-test
|
| Communications
Port |
DB9
female (UPS ships with communications cable); USB Interface
Adapter is optional
|
| Power
Factor |
500
VA: 0.64
750/1000 VA: 0.67
1400 VA: 0.68
|
|
Battery
|
| Battery
Type |
Sealed,
maintenance-free lead-acid; starved electrolyte
|
| Battery
Description |
500
VA: (1) 12V, 9 Ah
750 VA: (2) 12V, 7.2 Ah
1000 VA: (2) 12V, 9 Ah
1400 VA: (3) 12V, 9 Ah
|
| Battery
Recharge |
<
3 hours to 90% capacity
|
| Battery
Runtime |
5
minutes minimum; See Battery Runtimes table
|
| Start-On-Battery |
Startup
with UPS batteries in absence of utility power
|
|
General
|
| Topology |
Line-interactive
|
| Dimensions
and Weight |
see
Model Selection Guide
|
| Network
Transient Protector |
In
and out RJ11 jack for telephone/modem protection (120V
models only) or RJ45 for 10Base-T network cable; UL497A
tested
|
|
Environmental
and safety
|
| Operating
Temperature |
0oC
to 40oC (32oF to 104oF) UL tested at 25oC (77oF)
|
| Safety
Markings |
UL,
cUL, and CSA; 230V models also CE and TUV
|
| Safety
Conformance |
UL
1778, CAN/CSA C22.2, No. 107.1; 230V models also EN
50091-1-1 and IEC 60950
|
| EMC
Markings |
FCC
Class B; 230V models also CE (EN50091-2) and C-Tick
|
| Surge
Suppression |
ANSI
C62.41 Category A (formerly IEEE 587)
|
| Immunity |
IEC
801-2, -3, -4
|
| Transit/Storage
Temp. |
-15oC
to 55oC (5oF to 131oF)
|
| Audible
Noise |
<
45 dBA typical
|
| Relative
Humidity |
5-95%
non-condensing
|
| *
Due to continuing product improvement programs, specifications