Powerware
5119
Specification
Details
Cabinet Specification
Details
|
Electrical
Input
|
| Voltage |
120
and 230 VAC Nominal; see Model
Selection Guide for user selectable voltages
|
| On
Line Voltage Range |
-30%,
+20% for nominal voltages; user selectable extended
range of -35%, +20% (-30%, +15% for 127 and 240 VAC)
|
| Nominal
Input Frequency |
50/60
Hz; auto-selection (60 Hz only for 120 and 127 VAC)
|
| Frequency
Tolerance |
Nominal
+/-3 Hz
|
|
Electrical
Output
|
| Power
Levels |
1000-3000
VA
|
| On
Line Regulation |
-10%,
+6%; within Computer Business Equipment Manufacturers
Association's Guidelines (-15%; +10% using extended
range)
|
| On
Battery Regulation |
<
+/-5% RMS
|
| Voltage
Wave Shape (on battery) |
Sine
wave, 3% THD
|
| Overload
(Normal Operation) |
Minimum
200% of full load for 15 cycles
|
| No
Load Sleep Mode (Battery Mode) |
Outputs
are turned off if <5% load is detected (selectable)
|
| Interconnecting
Cords ( 230 VAC Models only) |
2
ea. IEC-320 (10 A); PRC3000i also includes 1 ea. IEC-320
(16A) with stripped male end for rewirable plug
|
| Backup
Time |
See
Backup Times table
|
| Battery
Charging |
<3
hrs. to 90% usable capacity
|
| Battery
Type |
Sealed,
maintenance-free lead-acid; starved electrolyte
|
| Start-On-Battery |
Startup
with UPS batteries in absence of utility power
|
|
Environmental
and safety
|
| Operating
Temperature |
0oC
to 40oC (32oF to 104oF) UL
tested at 25oC (77oF)
|
| Storage
Temp. |
-20oC
to 60oC (-4oF to 140oF)
|
| Audible
Noise |
<
45 dBA typical
|
| Relative
Humidity |
5
to 95% non-condensing
|
| Operating
Altitude |
Up
to 3,000 meters above sea level
|
| Safety
Markings |
UL
and CSA; 230 volt models also CE,VDE,S,FI,N, and D
|
| Safety
Certifications |
UL
1778, CSA 22.2, No. 107.1; 230 volt models also EN 50091-1
and IEC 60950
|
| EMC
Markings |
FCC;
120 volt models also VCCI; 230 volt models also CE
|
| Emissions |
FCC
Class B (2000-3000 VA Class A); 230 volt models also EN
50091-2, EN 55022 and IEC 61000-3-2 |
| Immunity |
EN
50091-2, IEC 61000-4-2,3,4,5 and ANSI C62.41 Cat B (formerly
IEEE 587)
|
| Surge
Suppression |
Manufactured
with surge suppressors that meet UL1449
|
| Network
Transient Protector (cabinet models) |
In
and out RJ11 jack for telephone/modem protection (120
VAC models only) or RJ45 for 10Base-T network cable
|
| *
Due to continuing product improvement programs, specifications
subject to change without notice |
Model Selection Guide
| 120
VAC1, 60 Hz Models |
|
Product
Name
|
Power
Out (VA/Watt) |
Input
Connection
|
Output
Connections
|
Maximum
Output Current (Amp) |
Dimensions
WxHxD (in/cm) |
Unit
Weight (lb/kg) |
Ship
Weight (lb/kg) |
| PW5119
1000 |
1000/670 |
5-15P |
(6)5-15R2 |
8.3 |
7.0x8.8x17.1
/ 17.8x22.3x43.4 |
43/20 |
48/22 |
| PW5119
1500 |
1440/960 |
5-15P |
(6)5-15R2 |
12.0 |
7.0x8.8x17.1
/ 17.8x22.3x43.4 |
57/26 |
62/28 |
| PW5119
2000 |
1920/1400 |
5-20P |
(6)5-15R
& (2)5-20R4 |
16.0 |
7.0x8.8x17.1
/ 17.8x22.3x43.4 (x2)3 |
32/15 |
91/41 |
| Pw5119
2400 |
2400/1600 |
L5-30P |
(6)5-15R
& (1)L5-30R4 |
20.0 |
7.0x8.8x17.1
/ 17.8x22.3x43.4 (x2)5 |
36/16 |
110/50 |
| PW5119
3000 |
2880/2250 |
L5-30P |
(6)5-15R
& (1)L5-30R4 |
24.0 |
7.0x8.8x17.1
/ 17.8x22.3x43.4 (x2)5 |
41/19 |
115/52 |
|
230 VAC6, 50/60 Hz Models
|
| PW5119
1000i |
1000/670 |
IEC-320,
10A |
(6)IEC-3202 |
4.4 |
7.0x8.8x17.1
/ 17.8x22.3x43.4 |
43/20 |
48/22 |
| PW5119
1500i |
1500/960 |
IEC-320,
10A |
(6)IEC-3202 |
6.5 |
7.0x8.8x17.1
/ 17.8x22.3x43.4 |
57/26 |
62/28 |
| PW5119
2000i |
2000/1400 |
IEC-320,
10A |
(9)IEC-3204 |
8.7 |
7.0x8.8x17.1
/ 17.8x22.3x43.4 (x2)3 |
31/14 |
90/41 |
| PW5119
2400i |
2300/1600 |
IEC-320,
10A |
(9)IEC-3204 |
10.0 |
7.0x8.8x17.1
/ 17.8x22.3x43.4 (x2)5 |
34/15 |
108/49 |
| PW5119
3000i |
3000/2250 |
IEC-320,
16A |
(9)IEC-3204 |
13.0 |
7.0x8.8x17.1
/ 17.8x22.3x43.4 (x2)5 |
39/18 |
113/51 |
|
Battery
Boxes (for 2000-3000 VA models only)
|
| PW5119
1048 BP |
48
VDC, 10 AHr |
cord
w/ connector |
--- |
--- |
7.0x8.8x17.1
/ 17.8x22.3x43.4 |
47/21 |
---7 |
| PW5119
1748 BP |
48
VDC, 17 AHr |
cord
w/ connector |
--- |
--- |
7.0x8.8x17.1
/ 17.8x22.3x43.4 |
63/29 |
---7 |
|
|
|
|
|
|
|
|
|
1User
selectable for 100,110,120, or 127 VAC. With 100 or
110 V selected, 120 VAC units can
operate at 50 Hz.
2Divided into 2 load segments (receptacle
groups).
3Includes Battery Box PW5119 1048 BP.
4Divided into 3 load segments (receptacle
groups).
5Includes Battery Box PW5119 1748 BP.
6User selectable for 208,220,230, or 240
VAC.
7Battery box and electronics ship together
in one box. |
Battery Run Times
(in minutes)
|
Load
|
PW5119
1K(i) RM |
PW5119
1.5K(i) RM |
PW5119
2K(i) RM |
PW5119
2.4K(i) RM |
PW5119
3K(i) RM |
| 300
VA |
40 |
67 |
112 |
187 |
187 |
| 500
VA |
20 |
32 |
68 |
112 |
112 |
| 700
VA |
12 |
23 |
48 |
80 |
80 |
| 1000
VA |
7 |
13 |
27 |
45 |
45 |
| 1500
VA |
|
7 |
18 |
30 |
30 |
| 2000
VA |
|
|
11 |
19 |
19 |
| 2400
VA |
|
|
|
14 |
14 |
| 3000
VA |
|
|
|
|
11 |
*This
guide provides typical application information. Battery times
are approximate and may vary with equipment, configuration,
disk access, battery age, temperature.etc.
|