5125 RM 5000-6000 VA |

5000-6000 VA Model |
Rackmount Only Model

Specification Details
| Electrical Input |
5000 VA |
6000 VA |
| Nominal Voltage |
200/208 and 230 Vac |
| Input Voltage Ranges (for user-selectable voltages) |
160-288 |
| Operating Frequency |
50/60Hz, Auto-sensing |
| Frequency Range |
46-54hz for 50 hz; 56-64 hz for 60 hz |
| Electrical Output |
| On Utility Voltage Regulation |
-10% to +6% of nominal |
| On Battery Voltage Regulation |
±5% RMS |
| Voltage Wave Shape (on battery) |
Sine Wave |
| Output Protection |
Short circuit protection |
| Battery |
| Battery Type |
Sealed, lead-acid; maintenance free |
| Battery Run time |
See Battery Run Times Table |
| Battery Replacement |
Hot-swappable internal batteries and external batteries modules |
| Recharge Time |
<3 hours to 90% usable capacity |
| Start-On-Battery |
Allows start of UPS without utility input |
| General |
| Diagnostics |
Full System self-test on power up |
| UPS Bypass |
Internal Bypass |
| Transfer Time |
2-4ms typical 6ms max |
| Dimensions and Weights |
See Model Selection Guide |
| Overload (normal operation) |
100-102% indefinite, 103-112% 2 minutes and >112% 12 line cycles |
| Communications |
| User Interface |
Front Control Panel |
| Audible Alarms |
For various UPS alarm conditions, including: On Battery, Low Battery, Overload, UPS fault |
| Network Transient Protector |
No |
| REPO Port |
Meets NEC code 645-11 intent and UL requirements |
| Communication ports |
Native USB and serial port |
| Communication slot |
Web/SNMPPxHub card factory installed; other options also available |
| Cable |
6-foot communications cable included |
| Power Management Software |
Powerware Software Suite CD-ROM (bundled with UPS) |
| Environmental |
| Safety Certifications |
UL; cUL; NOM; C-Tick; CE marking TUV/VDE, GS |
| EMC Compliance |
FCC Part 15, EN50091-2, Class A |
| Operating Temperature |
10 to 40º C |
| Storage Temperature |
-25 to 50º C |
| Relative Humidity |
0% to 95% non-condensing |
| Lightning & Surge Protection |
ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5 |
| Surge Energy Rating |
High-energy 6500 A peak |
| Audible Noise |
Less than 45 dBA typical |
| Altitude |
3000m (10,000 ft) without derating |
| Note: Specifications are subject to change without notice due to continuing product improvement programs. |
Model Selection Guide
Model
Number1 |
Power
Rating (VA/Watt) |
Input/
Output Voltage
(Vac)2 |
Input Connection |
Output Receptacles4 |
Dimensions HxWxD (in/mm) |
Weight (lb/kg) |
| Rackmount Models Only |
PW5125
5000 RM |
5000/4500 |
200/208, 220, 230, 240 |
L6-30p |
L6-30R on short cord, (2) L6-20, (4) C13 |
5.25 x 17.50 x 26.0 / 133 x 445 x 661 |
161/73 |
PW5125
1500 |
6000/5400 |
200-240 |
HW (terminal block) |
HW, (4) C19, (4) C13 |
5.25 x 17.50 x 26.0 / 133 x 445 x 661 |
161/73 |
PW5125
2200 |
6000/5400 |
220, 230, 240 |
IEC309-32A |
IEC309-32A on short cord,
(4)C19, (4)C13 |
5.25 x 17.50 x 26.0 / 133 x 445 x 661 |
161/73 |
1. 50/60 automatic frequency selection.
2. 230 V models are 220 V,230 V,240 V user-selectable.208 V models are 208 V,220 V,230 V,240 V user-selectable.
3. Includes(2) each IEC interconnect cables.
4. 5000-6000VA ship with both black and beige front panel bezels; models include rail kits and mounting hardware; factory installed ConnectUPS Web/SNMP/xHub card available by inserting –5507 for -5501
5. Unit fits in standard 19-inch racks. Mounting kits are sold separately. |
Powerware 5125 Battery Run Time Chart (in minutes full load/half load)*
| VA |
Standard Internal
Batteries |
1 EBM |
2 EBMs |
3 EBMs |
4 EBMs |
| Rackmount Models |
| 5000 |
7/19 |
24/61 |
46/106 |
67/156 |
89/210 |
| 6000 |
5/15 |
19/49 |
36/85 |
53/125 |
71/168 |
*Up to 4 EBMs can be connected to all models. EBM run times include internal batteries. Run time chart provides typical information. Battery run times are approximate and may vary with equipment, configuration, battery age, temperature etc.. |