Comparison of
5125 1000-2200 VA Tower Model &
5125 RM 1000-3000 VA Two-in-One (Rackmount and Tower)

Specification
Details
| Model |
Tower Model |
Two-in-One (Rackmount and Tower) |
|
Electrical
Input
|
1000-2200
VA
|
1000-3000
VA
|
| Nominal
Voltage |
120,
208 and 230 Vac; See Model
Selection Guide user-selectable volages
|
120,
208, 230 and 240Vac; See Model
Selection Guide user-selectable volages
|
| Input
voltage ranges for user-selectable voltages |
Low voltage: 77-152V; High voltage: 154-288V
|
| Operating
Frequency |
50/60Hz,
Auto-sensing
|
| Frequency
Range |
46-65Hz
|
|
Electrical
Output
|
| On
Utility Voltage Regulation |
-10%
to +6% of nominal
|
| On
Battery voltage Regulation |
±5%
RMS
|
| Voltage
Wave Shape (on battery) |
Sine
Wave
|
| Output
protection |
Short
circuit protection
|
|
Battery
|
| Battery
Type |
Sealed,
lead-acid; maintenance free |
| Battery
Run time |
See
Battery Run Times Table |
| Battery
Replacement |
Hot-swappable
internal batteries and external batteries modules |
| Recharge
Time |
<3
hours to 90% usable capacity |
| Start-On-Battery |
Allows
start of UPS without utility input |
|
General
|
| Diagnostics |
Full
System self-test on power up |
| UPS
Bypass |
No
Bypass |
Internal
Bypass |
| Transfer
Time |
2-4ms
typical |
| Dimensions
and weights |
See
Model Selection Guide
|
| Overload
(normal operation) |
110%
overload, shut down after 3 minutes. 150% overload,
shut down 10 cycles |
110%
overload for 30 seconds short circuit protected |
|
Communications
|
| User
Interface |
Front Control Panel
|
| Audible
Alarms |
For various UPS alarm conditions, including:
On Battery, Low Battery, Overload, UPS fault
|
| Network
transient Protector |
UL
497 A, In/out jacks RJ45 (high voltage models
network protection) &
RJ11 (low voltage models modem protection)
|
| REPO
Port |
Meets
NEC code 645-11 intent and UL requirements
|
| X-Slot
Interface |
RS-232
Single Serial Module (standard), Other options
available: RS-232 Multi-Port Module (6), SNMP/Web
Module; USB Module; Relay Module
|
| Cable |
6-foot
communications cable included
|
| Power
Management Software |
Powerware
Software Suite CD-ROM (bundled with UPS)
|
|
Environmental
|
| Safety
Certifications |
UL;
cUL; NOM; C-Tick; CE mark
|
| EMC
Compliance |
FCC Part 15, EN50091-2, Class A for 2.2KVA and
RM; Class B for 1000 and 1500VA tower models
|
FCC
Part 15, EN50091-2, Class A
|
| Operating
Temperature |
0
to 40º C (32 to 104º F)
|
| Storage
Temperature |
-15
to 50º C (5 to 122º F)
|
| Relative
Humidity |
0%
to 95% non-condensing
|
| Lightning
& Surge Protection |
ANSI/IEEE
C62.41 (IEEE 587), IEC61000-4-5
|
| Surge
energy rating |
480
Joules
|
| Audible
Noise |
Less than 40 dBA typical
|
| Altitude |
3000m
(10,000 ft) without derating
|
| Note:
Specifications are subject to change without notice
due to continuing product improvement programs. |
Model
Selection Guide
Model
Number1 |
RoHS Part Numbers |
Non-RoHS Part Numbers |
Power
Rating (VA/Watt) |
Input/
Output Voltage
(Vac)2 |
Input Connection |
Output Receptacles4 |
Dimensions
HxWxD (in/mm) |
Weight
(lb/kg) |
| Tower Models (North America) |
PW5125
1000
|
05146629-5591 |
05146629-5501 |
1000/700 |
120 |
5-15P,
6 ft line cord |
(6)
5-15R |
9.45 x 6.38 x 15.79/
240 x 162 x 401 |
34.3/15.6
|
PW5125
1500
|
05146632-5591 |
05146632-5501 |
1440/1050 |
120 |
5-15P,
6 ft line cord |
(6)
5-15R |
9.84 x 6.38 x 18.39/
250 x 162 x 467 |
50.7/23.0
|
PW5125
2200 |
05146635-5591 |
05146635-5501 |
1920/1600 |
120 |
5-20P,
6 ft line cord |
(6)
5-15R,
(2) 5-20R |
9.84 x 8.07 x 19.41/
250 x 205 x 493 |
68.3/31.0 |
PW5125
2200b |
05146636-5591 |
05146636-5501 |
2080/1600 |
208 |
IEC-320-15A,
inlet3 |
(9)
IEC-320-10A
(C13) |
9.84 x 8.07 x 19.41/
250 x 205 x 493 |
68.3/31.0 |
| Tower Models
(International) |
PW5125
1000i
|
05146630-5591 |
05146630-5501 |
1000/700 |
230 |
IEC-320-10A,
inlet3 |
(6)
IEC-320-10A
(C13) |
9.45 x 6.38 x 15.79/
240 x 162 x 401 |
34.3/15.6 |
PW5125
1500i
|
05146633-5591 |
05146633-5501 |
1500/1050 |
230 |
IEC-320-10A,
inlet3 |
(6)
IEC-320-10A
(C13) |
9.84 x 6.38 x 18.39/
250 x 162 x 467 |
50.7/23.0 |
PW5125
2200i
|
05146637-5591 |
05146637-5501 |
2200/1600
|
230 |
IEC-320-10A,
inlet3 |
(9)
IEC-320-10A
(C13) |
9.84 x 8.07 x 19.41/
250 x 205 x 493 |
68.3/31.0 |
Two-i n-One Form Factor
Models5 (North America) |
PW5125
1000 RM
|
05146666-6501 |
05146666-5501 |
1000/900 |
120 |
5-15P,
6 ft line cord |
(6)
5-15R |
3.5 x 17.0 x 19.4/
89 x 432 x 494 |
61.0/27.67 |
PW5125
1500 RM
|
05146669-6501 |
05146669-5501 |
1440/1340 |
120 |
5-15P,
6 ft line cord |
(6)
5-15R |
3.5 x 17.0 x 19.4/
89 x 432 x 494 |
61.0/27.67 |
PW5125
2400 RM
|
05147564-6501 |
05147564-5501 |
2400/2250 |
120 |
L5-30P,
(12' attached) |
(1)
L5-30R,
(6) 5-15R |
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3 |
89.0/40.40 |
PW5125
3000 RM
|
05147152-6501 |
05147152-5501 |
2880/2700 |
120 |
L5-30P,
(12' attached) |
(1)
L5-30R,
(6) 5-15R |
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3 |
89.0/40.40 |
| Two-in-One Form Factor
Models5
(International) |
PW5125
1000i RM
|
05146667-6591 |
05146667-5501 |
1000/900 |
230 |
IEC-320-10A,
inlet3 |
(6)
IEC-320-10A (C13) |
3.5 x 17.0 x 19.4/
89 x 432 x 494 |
61.0/27.67 |
PW5125
1500i RM
|
05146670-6591 |
05146670-5501 |
1500/1340 |
230 |
IEC-320-10A,
inlet3 |
(6)
IEC-320-10A (C13) |
3.5 x 17.0 x 19.4/
89 x 432 x 494 |
61.0/27.67 |
PW5125
2400i RM
|
05147565-6591 |
05147565-5501 |
2400/2250 |
230 |
IEC-309
16A P,
(12' attached) |
(1)
IEC-320-16A (C19)
(9) IEC-320-10A (C13) |
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3 |
89.0/40.40 |
PW5125
3000g RM6
|
05147155-6591 |
05147155-5501 |
3000/2700 |
200-240 |
IEC-320-16A,
receptable |
(1)
IEC-320-16A (C19)
(9) IEC-320-10A (C13) |
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3 |
89.0/40.40 |
PW5125
3000e RM7 |
05147641-6591 |
05147641-5501 |
3000/2700 |
230 |
IEC-320-16A,
receptacle |
(1)
IEC-320-16A (C19)
(9) IEC-320-10A (C13) |
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3 |
89.0/40.40 |
PW5125
3000i RM8 |
05147154-6501 |
05147154-5501 |
3000/2700 |
230 |
IEC-309
16A P,
(12' attached) |
(1)
IEC-320-16A (C19)
(9) IEC-320-10A (C13) |
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3 |
89.0/40.40 |
PW5125
3000j RM9 |
|
|
2400/2250 |
100 |
L5-30P
(12' attached) |
(1)
L5-30R
(6) 5-15R |
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3 |
89.0/40.40 |
|
1.
50/60 automatic frequency selection.
2. 120 V models are 110 V,120 V,127 V user-selectable.230 V models are 220 V,230 V,240 V
user-selectable.208 V models are 208 V,220 V,230 V,240 V
user-selectable.
3. Includes(2) each IEC interconnect cables.
4. 1000-1500VA models divided into (2) Load Segments (receptacle
groups). 2200-3000VA models are divided into
(3) Load Segments (receptacle groups).
5. Unit fits in standard 19-inch racks. Mounting kits are sold separately.
6. g-model carries agency listing cUL; C-Tick; TUV/GS; CE.
7. e-model carries agency listing CE mark only.
8. i-indicating international model, 230 V.
9. j -indicating Japanese model, 100 V.
|
Powerware
5125 Battery Run Time Chart (in minutes full
load/half load)*
| VA |
Standard
Internal
Batteries |
1
EBM |
2
EBMs |
3
EBMs |
4
EBMs |
| Tower
Models |
| 1000 |
5/14 |
25/60 |
55/170
|
83/199 |
109/228 |
| 1500 |
6/17 |
33/79 |
63/146
|
92/174 |
120/201 |
| 2200 |
5/14
|
26/60
|
55/170 |
81/198 |
106/224 |
| Two-in-One
Form Factor |
| 1000 |
7/19 |
33/68 |
58/120 |
82/166 |
105/214 |
| 1500 |
5/13 |
23/57 |
49/161
|
73/172 |
96/205 |
| 2400 |
7/19 |
35/73 |
60/124 |
85/177 |
110/229 |
| 3000 |
5/15 |
25/61 |
49/103
|
69/146 |
90/190 |
*Up
to 4 EBMs can be connected to 1000-3000VA models.
EBM run times include internal batteries.
Run time chart provides typical information. Battery
run times are approximate and may vary with equipment,
configuration, battery age, temperature, etc.
|
|