Bomara Associates Logo Bomara Associates Homepage

Eaton Authorized Power Specialist


Products:
5125 RM
5125

1000-3000 VA Specification Details
Model Guide
Battery runtimes


Optional Extended Battery Modules (EBMs)

Available Options

 

Rackmount Comparison Charts:

Features
Specifications
Runtime Matrix

 


Comparison of
5125 1000-2200 VA Tower Model &
5125 RM 1000-3000 VA Two-in-One (Rackmount and Tower)



Specification Details

Model
Tower Model
Two-in-One (Rackmount and Tower)

Electrical Input 

1000-2200 VA

1000-3000 VA 

Nominal Voltage

120, 208 and 230 Vac; See Model Selection Guide user-selectable volages

120, 208, 230 and 240Vac; See Model Selection Guide user-selectable volages

Input voltage ranges for user-selectable voltages

Low voltage: 77-152V; High voltage: 154-288V

Operating Frequency

50/60Hz, Auto-sensing

Frequency Range

46-65Hz

Electrical Output

On Utility Voltage Regulation

-10% to +6% of nominal

On Battery voltage Regulation

 ±5% RMS

Voltage Wave Shape (on battery)

 Sine Wave

Output protection

 Short circuit protection

Battery

Battery Type Sealed, lead-acid; maintenance free
Battery Run time  See Battery Run Times Table
Battery Replacement Hot-swappable internal batteries and external batteries modules
Recharge Time <3 hours to 90% usable capacity
Start-On-Battery Allows start of UPS without utility input

General

Diagnostics Full System self-test on power up
UPS Bypass No Bypass Internal Bypass
Transfer Time 2-4ms typical
Dimensions and weights  See Model Selection Guide
Overload (normal operation) 110% overload, shut down after 3 minutes. 150% overload, shut down 10 cycles 110% overload for 30 seconds short circuit protected

Communications

User Interface

Front Control Panel

Audible Alarms

For various UPS alarm conditions, including: On Battery, Low Battery, Overload, UPS fault

Network transient Protector

 UL 497 A, In/out jacks RJ45 (high voltage models network protection) &
 RJ11  (low voltage models modem protection)

REPO Port

 Meets NEC code 645-11 intent and UL requirements

X-Slot Interface

 RS-232 Single Serial Module (standard), Other options available: RS-232 Multi-Port Module (6), SNMP/Web Module; USB Module; Relay Module

Cable

6-foot communications cable included

Power Management Software

Powerware Software Suite CD-ROM (bundled with UPS)

Environmental 

Safety Certifications

UL; cUL; NOM; C-Tick; CE mark

EMC Compliance

FCC Part 15, EN50091-2, Class A for 2.2KVA and RM; Class B for 1000 and 1500VA tower models

FCC Part 15, EN50091-2, Class A

Operating Temperature

 0 to 40º C (32 to 104º F)

Storage Temperature

-15 to 50º C (5 to 122º F)

Relative Humidity

0% to 95% non-condensing

Lightning & Surge Protection 

ANSI/IEEE C62.41 (IEEE 587), IEC61000-4-5

Surge energy rating

480 Joules

Audible Noise

Less than 40 dBA typical

 Altitude 

3000m (10,000 ft) without derating

Note: Specifications are subject to change without notice due to continuing product improvement programs.



Model Selection Guide

Model
Number1
RoHS Part Numbers Non-RoHS Part Numbers

Power 
Rating (VA/Watt)

Input/
Output Voltage
(Vac)2

Input Connection

Output Receptacles4

Dimensions HxWxD (in/mm)

Weight (lb/kg)

Tower Models (North America)
PW5125
1000
05146629-5591 05146629-5501 1000/700 120 5-15P,
6 ft line cord
(6) 5-15R 9.45 x 6.38 x 15.79/
240 x 162 x 401
34.3/15.6
PW5125
1500
05146632-5591 05146632-5501 1440/1050 120 5-15P,
6 ft line cord
(6) 5-15R 9.84 x 6.38 x 18.39/
250 x 162 x 467

50.7/23.0

PW5125
2200
05146635-5591 05146635-5501  1920/1600  120 5-20P,
6 ft line cord
 (6) 5-15R,
(2) 5-20R
9.84 x 8.07 x 19.41/
250 x 205 x 493
68.3/31.0
PW5125
2200b
05146636-5591 05146636-5501 2080/1600 208 IEC-320-15A,
inlet3
(9) IEC-320-10A
(C13)
9.84 x 8.07 x 19.41/
250 x 205 x 493

68.3/31.0

Tower Models (International)
PW5125
1000i
05146630-5591 05146630-5501 1000/700 230 IEC-320-10A,
inlet3
(6) IEC-320-10A
(C13)
9.45 x 6.38 x 15.79/
240 x 162 x 401
34.3/15.6
PW5125
1500i
05146633-5591 05146633-5501 1500/1050 230 IEC-320-10A,
inlet3
(6) IEC-320-10A
(C13)
9.84 x 6.38 x 18.39/
250 x 162 x 467
50.7/23.0
PW5125
2200i
05146637-5591 05146637-5501

2200/1600

 230 IEC-320-10A,
inlet3
(9) IEC-320-10A
(C13)
9.84 x 8.07 x 19.41/
250 x 205 x 493
68.3/31.0
Two-in-One Form Factor Models5 (North America)
PW5125
1000 RM
05146666-6501 05146666-5501 1000/900 120 5-15P,
6 ft line cord
(6) 5-15R 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67
PW5125
1500 RM
05146669-6501 05146669-5501 1440/1340 120 5-15P,
6 ft line cord
(6) 5-15R 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67
PW5125
2400 RM
05147564-6501 05147564-5501 2400/2250   120 L5-30P,
(12' attached)
 (1) L5-30R,
(6) 5-15R
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40
PW5125
3000 RM 
05147152-6501 05147152-5501 2880/2700 120 L5-30P,
(12' attached) 
(1) L5-30R,
(6) 5-15R
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40
Two-in-One Form Factor Models5 (International)
PW5125
1000i RM 
05146667-6591 05146667-5501 1000/900  230 IEC-320-10A,
inlet3
(6) IEC-320-10A (C13) 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67
PW5125
1500i RM
05146670-6591 05146670-5501 1500/1340  230 IEC-320-10A,
inlet3
(6) IEC-320-10A (C13) 3.5 x 17.0 x 19.4/
89 x 432 x 494
61.0/27.67
PW5125
2400i RM
05147565-6591 05147565-5501 2400/2250  230 IEC-309 16A P,
(12' attached) 
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40
PW5125
3000g RM6
05147155-6591 05147155-5501 3000/2700 200-240 IEC-320-16A,
receptable
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40
PW5125
3000e RM7
05147641-6591 05147641-5501 3000/2700  230 IEC-320-16A,
receptacle
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40
PW5125
3000i RM8
05147154-6501 05147154-5501 3000/2700  230 IEC-309 16A P,
(12' attached) 
(1) IEC-320-16A (C19)
(9) IEC-320-10A (C13)
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40
PW5125
3000j RM9
  2400/2250 100 L5-30P
(12' attached)
(1) L5-30R
(6) 5-15R
3.5 x 19.0 x 24.5/
89 x 482.6 x 622.3
89.0/40.40

1. 50/60 automatic frequency selection.
2. 120 V models are 110 V,120 V,127 V user-selectable.230 V models are 220 V,230 V,240 V user-selectable.208 V models are 208 V,220 V,230 V,240 V user-selectable.
3. Includes(2) each IEC interconnect cables.
4. 1000-1500VA models divided into (2) Load Segments (receptacle groups).  2200-3000VA models are divided into (3) Load Segments (receptacle groups).
5. Unit fits in standard 19-inch racks. Mounting kits are sold separately.
6. g-model carries agency listing cUL; C-Tick; TUV/GS; CE.
7. e-model carries agency listing CE mark only.
8. i-indicating international model, 230 V.
9. j -indicating Japanese model, 100 V.

 

Powerware 5125 Battery Run Time Chart (in minutes full load/half load)*

VA Standard Internal
Batteries
1 EBM 2 EBMs 3 EBMs 4 EBMs
Tower Models
1000

5/14

25/60

55/170

83/199 109/228
1500

6/17

33/79

63/146

92/174 120/201
2200

5/14

26/60

55/170

81/198 106/224
Two-in-One Form Factor
1000 

7/19

33/68

58/120

82/166 105/214
1500 

5/13

23/57

49/161

73/172 96/205
2400 

7/19

35/73

60/124

85/177 110/229
3000 

5/15

25/61

49/103

69/146 90/190

*Up to 4 EBMs can be connected to 1000-3000VA models. EBM run times include internal batteries.