Powerware
5140

Specification
Details
|
Electrical
Input
|
| Voltage |
200,
208, 220, 230 and 240 Vac user selectable; see Model
Selection Guide for default settings
|
| Nominal
Voltage Range |
+/-20%
of nominal voltage without using batteries
|
| Extended
Voltage Range |
160
- 288V without using batteries (set bia front panel)
|
| Frequency |
50/60Hz,
+/-3 Hz (+5/-3 Hz with extended voltage range)
|
| Connection |
Hardwired
|
| Efficiency |
96%
|
|
Electrical
Output
|
| Power
Out |
6000
VA/6000Watts
|
| Voltage |
200,
208, 220, 230, 240
|
| Voltage
Range (online) |
+/-10%
of nominal voltage
|
| Voltage
Range (on battery) |
+/-5%
of nominal voltage
|
| Wave
Form (on battery) |
Sine
Wave
|
| Frequency |
Same
as input (+/-0.5% during battery operation)
|
| Connections |
Receptacles
or hardwired; see Model Selection
Guide
|
| Maximum
Current |
29A
at 208 Vac; 26A at 230 Vac
|
| Output
Protection |
Resettable
circuit breakers
|
|
Battery
|
| Type |
Maintenance-free,
sealed, valve-regulated lead-acid (VRLA), (28), 12V 5Ah |
| Extended
Batteries |
<Maximum
of 2 Extended Battery Modules (EBMs) |
| Backup
Time |
See
Battery Run Times Table |
| Recharge
Time |
<3
hours to 80% usable capacity |
| Extended
Battery Recharge Time |
<10
hours to 80% usable capacity |
|
Communications
|
| Serial
Ports |
(2)
Serial communication ports for use with power management
software and installable option cards, including ConnectUPS
SLC-EM SNMP Adapter and the Port Expander Card
|
| User
LEDs |
Normal
Operation (green), On Battery (yellow), On Bypass (yellow),
and Alarm (red)
|
| LCD |
Two-line
LCD with three button control
|
| LCD
Languages |
Danish,
Dutch, English, French, German, Spanish, Italian, and
Japanese
|
| Front
Panel Buttons |
On,
Off, and Alarm Silence/Self Test
|
| Connunication
Cable |
6-foot
communication cable included
|
|
Environmental
and safety
|
| Operating
Temperature |
10oC
to 40oC (25oC for optimal performance)
|
| Transit
Temperature |
-20oC
to 55oC
|
| Storage
Temperature |
0oC
to 25oC
|
| Humidity
(Operation) |
20
to 80% (noncondensing)0
|
| Humidity
(Non-operating) |
5
to 95%
|
| Operating
Altitude |
0
to 10,000 feet (non-operating: 0 to 30,000 feet)
|
| Audible
Noise |
55
dBA at 1 meter
|
| Safety
Markings |
UL,
CSA, NOM, Models PW5140 6000i and PW5140 6000 HW also
CE and VDE
|
| Safety
Certifications |
UL1778;
CSA22.2 No. 107.2, No.107.2, No. 950; CB Bulletin No.86AI;
EN50091-1; EN60950; EMKO-TSE207/95; NOM-019-SCFI-1993
|
| EMC
Markings |
FCC-A,
CISPR-A; VCCI
|
| Immunity |
IEC
801-2, IEC 801-3, IEC 801-4, IEC 801-5
|
| Surge
Suppression |
Conforms
to IEEE 587B and ANSI C62.41
|
| REPO
Port |
Meets
NEC code 645-11 intent and UL requirements
|
| *
Due to continuing product improvement programs, specifications
subject to change without notice |
Model
Selection Guide
|
Model
Number
|
Power
Out (VA/Watt)
|
Input/Output
Voltage (Vac)
|
Frequency
(Hz)
|
Input
Connection
|
Output
Receptacles
|
Dimensions
WxHxD (in/cm)
|
Weight
(kg/lb)
|
| PW5140
6000i |
6000/6000 |
208/2302 |
50/603 |
Hardwired |
(12)
IEC-320, C13 & (3) IEC-320, C194 |
10.5
x 17.25 x 24.3 in
26.7 x 43.8 x 61.7 cm |
136/3006 |
| PW5140
6000 |
6000/6000 |
208/2302 |
50/603 |
Hardwired |
(2)
L6-30R & (2) IEC-3205 |
10.5
x 17.25 x 24.3 in
26.7 x 43.8 x 61.7 cm |
136/3006 |
| PW5140
6000 HW |
6000/6000 |
208/2302 |
50/603 |
Hardwired |
Hardwired
and (2) IEC-3205 |
10.5
x 17.25 x 24.3 in
26.7 x 43.8 x 61.7 cm |
136/3006 |
| PW5140
BATT |
|
|
|
Custom
Adapter |
|
5.25
x 17.25 x 22.5 in
13.3 x 43.8 x 57.2 cm |
81.6/180 |
| PW5140
PDU7 |
250/250 |
120 |
60 |
Custom
Adapter |
(2)
5-15R |
1.98
x 19.28 x 9.90 in
5.03 x 48.97 x 25.15 cm |
8.6/19 |
|
119-inch
wide front panel with a 17.25-inch wide chassis; depth
doesn not include front panel (0.5 inches). All models
ship with rail mounting kit.
2208/230 Vac auto-sensing default. User selectable
via LCD interface for 200, 208, 220, 230, and 240 Vac
3Automatic frequency synchronization.
4Divided into 5 Load Segments.
5Divided into 2 Load Segments; IEC-320 receptacles
are used to connect optional PW5140 PDU.
6Shipping weight is 325 pounds (147 kg)
7Sidewall design occupies 0U of rack space.
|
Battery Run Times
| Load
(Watts) |
Standard
Batteries |
One
Additional
Extended Battery
Module |
Two
Additional
Extended Battery
Modules |
| 1000
|
1
hr 2 mins
|
2
hrs 24 mins
|
3
hrs 56 mins
|
| 2000
|
28
mins
|
1
hr 6 mins
|
1
hr 47 mins
|
| 3000
|
18
mins
|
40
mins
|
1
hrs 6 mins
|
| 4000
|
12
mins
|
28
mins
|
47
mins
|
| 5000
|
8
mins
|
21
mins
|
36
mins
|
| 6000
|
6
mins
|
18mins
|
28mins
|
*This
guide provides typical application information. Battery times
are approximate and may vary with equipment, configuration,
disk access, battery age, temperature.etc.
|