Powerware
9104

Specification
Details
| Power |
| Ratings
(RS) |
3.1/5.0/6.0
kVA 5.0 units upgradeable) |
| Electrical
Output |
| Voltage
(RS) |
120
VAC for 3.1 kVA
120/208 or 120/240 VAC for 3.1/5.0/6.0 kVA |
| Voltage
Range |
-27
to +22% |
| Frequency
Range |
45
to 65 Hz (auto-sensing) |
| Current
distortion |
Sinusoidal
active correction |
| Power
Factor |
.96
(active correction) |
| Connections
(RS) |
Hardwire
to terminal blocks on rear of unit is standard (line cord/plug
options available) |
| Electrical
Input |
| Voltage
(RS) |
120
VAC for 3.1 kVA
120/208 or 120/240 VAC for 3.1/5.0/6.0 kVA |
| Regulation |
+/-2% |
| Efficiency
(RS) |
92%
@ typical load |
| Wave
Form |
Sinusoidal,
<2% THD; <5% non-linear load |
| Frequency |
50
or 60 Hz, selectable sync window of +/-3, 1 or .5 Hz |
| Crest
Factor |
3:1 |
| Isolation
(RS) |
Advanced
Power Isolation |
| Connections
(RS) |
Hardwired,
5-15R duplex receptacles are standard (various receptacle
options available) |
| Battery |
| Type
(RS) |
Internal
battery; valve regulated, sealed lead-acid type |
| Recharge
Time |
<3
hours to 90% capacity |
| Backup
Time |
10
- 15 minutes at typical load (standard internal battery
pack or an RSi with one external battery pack) |
Model Selection Guide
Model
Number |
kVA
Rating |
Input
Voltage (VAC) |
Output
Voltage (VAC) |
AC
Line Cord
Option (15') |
Recommended
Input Service |
Dimensions
H x W x D (in) |
Weight
(lb/kg) |
| RS
Standard Hardwired Models |
| RST31
(Tower) |
3.1 |
120 |
120 |
L5-30P |
30
A |
16
x 6.8 x 24 |
125/56.9 |
| RST32
(Tower) |
3.1 |
120/208
or 120/240 |
Same
as input |
L14-20P |
20
A |
16
x 6.8 x 24 |
125/56.9 |
| RST52
(Tower) |
5.0 |
120/208
or 120/240 |
Same
as input |
L14-30P |
30
A |
24
x 6.8 x 24 |
180/86 |
| RST62
(Tower) |
6.0 |
120/208
or 120/240 |
Same
as input |
L14-30P |
30
A |
24
x 6.8 x 24 |
180/86 |
| RSR31
(Rack) |
3.1 |
120 |
120 |
L5-30P |
30
A |
6.8
x 19 x 24 |
135/61.2 |
| RSR32
(Rack) |
3.1 |
120/208
or 120/240 |
Same
as input |
L14-20P |
20
A |
6.8
x 19 x 24 |
135/61.2 |
| All
models are 50 and 60 Hz capable and are auto-sensing. |
Battery Run Times (in minutes)
|
3.1
kVA Models
|
| Typical
Applications |
Load |
RS
w/Standard Internal Batteries |
RS
and one Battery Pack |
| RISC
Workstation |
1000VA |
37 |
135 |
| Mini
Computer |
1500
VA |
22 |
82 |
| Telecom
equipment |
2100
VA |
14 |
48 |
| Midrange
Systems |
2500
VA** |
10 |
41 |
| Multiple
Servers |
3100
VA ** |
8 |
31 |
5.0 and 6.0kVA Models |
| Typical
Applications |
Load |
RS
w/Standard Internal Batteries |
RS
& One Battery Pack |
RS
& Two Battery Packs |
RS
& Three Battery Packs |
| Telecom
Equipment |
2000
VA |
44 |
100 |
150 |
200 |
| Multiple
Servers |
3000
VA |
25 |
60 |
93 |
126 |
| Multiple
Servers |
4000
VA |
17 |
42 |
67 |
99 |
| Multiple
Servers |
5000
VA |
12 |
28 |
46 |
64 |
| **Backup
times for 3.1 kVA units only. |
| This
guide provides typical application information. Battery
times are approximate and may vary with equipment, configuration,
disk access, battery age, temperature, etc. See the External
Battery Packs table below for more details. |
External Battery Packsa
|
Model
Number
|
Style
|
kVA
rating of compatible UPS
|
Dimensions
H x W x D (in/cm)
|
Weight
(lb/kg)
|
| RS3-RP2T |
Tower |
3.1 |
16
x 6.3 x 24
40.6 x 17.2 x 61 |
166/175 |
| RS6-RP1T |
Tower |
5.0/6.0 |
16
x 6.3 x 24
40.6 x 17.2 x 61 |
166/175 |
| RS3-RP2R |
Rack |
3.1 |
6.8
x 19 x 24
17.2 x 48.3 x 24 |
166/175 |
|
|
|
|