Bomara Associates Logo Bomara Associates Homepage

Eaton Authorized Power Specialist


Product Page
120VAC Spec
Model Guide
Battery Runtime
120-276VAC Spec
Model Guide
Battery Runtime

Optional Extended Battery Modules (EBMs)

Available Options

 

Powerware 1920

Specification Details

Low voltage details
Electrical Input
Nominal Voltage For user-selectable voltages see Model Selection Guide
Input Voltage Range 80-144 Vac
Input Power Factor >.95%
Operating Frequency 50/60 Hz, Auto-sensing
Frequency Range 45 - 65 Hz
Input Protection Fuse or circuit breaker
Electrical Output
On Utility Voltage Regulation +/-2% of nominal
On Battery Voltage Regulation +/-3% of nominal
Nominal Output Voltage Same as selected input voltage
Output Voltage Waveform Sine Wave
Output Voltage Distortion <3%THD
Output protection Electronic overload sensing,and circuit breaker protection
Efficiency Online Mode:>86%;
Hi-Efficiency Mode:>90%
Battery
Internal Battery type Sealed, lead-acid; maintenance free
EBM Battery Type Sealed, lead-acid; maintenance free
On Battery Runtime See Battery Runtimes
Battery Replacement Hot-swappable internal and external batteries
Recharge Time <4 hours to 90%capacity
Start-On-Battery Allows start of UPS without utility input
Communications
User Interface LCD status screen
Audible Alarms UPS alarm conditions,including:
On-Battery,Low Battery,Overload, UPS Fault
Network transient Protector In and out jack for all models.
UL497A tested
REPO Port Meets NEC code 645-11 intent and UL requirements
Communications One RS232 Serial Port;One Communications Slot; One USB Port
Communications cable 6-foot communications cable included
Power Management Software  Powerware Software Suite CD
General
Topology True online, double-conversion
Diagnostics Full system self-test on power up
UPS Bypass Automatic on Overload or UPS failure <4ms
Transfer Time to battery 0 ms
Dimensions and Weights See Model Selection Guide
Overload Capacity  125% for 10 minutes before transfer to bypass;
150% for 10 seconds before transfer to bypass
Environmental and Safety
Safety Certifications UL1778;cUL22.2 NO.107.1
EMI Compliance FCC Part 15, Class B (700-1500), Class A (2000-3000) 230V, 
EN 50091-2 Class B (700-1500), Class A (2000-3000)
Operating Temperature 0 to 40 C (32 to 104 F)
Storage Temperature -15 to 50 C (5 to 122 F)
Storage Temperature 0o to 25o C (32o to 77o F)
Relative Humidity 0%to 95%non-condensing
Immunity EEE C62.41,
IEC 61000-4 -2, -3, -4, -5
Network Transient Protector UL497A
Audible Noise at 1 meter 700-1000VA: <45dB;1500VA <50dB; 2000-3000 <52dB
Altitude  3000m (10,000 ft) without deteriorating
Note: Due to continuing product improvement programs, specifications are subject to change without notice.

Model Selection Guide

Model
Number
Power Out
(VA/Watt)
Input/Output
Voltage (Vac)
Frequency
(Hz)2
Input
Connection3
Output
Receptacles4
Dimensions
(HxWxD)
in/mm
Weight
(lb/kg)
120 Vac Models1
PW9120 700

700/490

120

50/60

5-15P

(4) 5-15R

9.6 x 6.2 x 16.2/
243 x 158 x 412

29/13.2

PW9120 1000

1000/700

120

50/60

5-15P

(4) 5-15R,
(2) 5-20R

9.6 x 6.2 x 16.2/
243 x 158 x 412

35.5/16.1

PW9120 1500

1500/1050

120

50/60

5-15P

(4) 5-15R,
(2) 5-20R

10.8 x 6.7 x 17.5/
275 x 170 x 444

46.5/21.1

PW9120 2000

2000/1400

120

50/60

5-20P

(6) 5-20R

14.2 x 8.6 x 18.6/
361 x 217 x 472

82/37.2

PW9120 3000

3000/2100

120

50/60

L5-30P

(4) 5-15R,
(2) 5-20R
(1) L5-30R

14.2 x 8.6 x 18.6/
361 x 271 x x 472

89/40.5

208 Vac Models

PW9120 3000

3000/2100

208

50/60

L6-20P

(2)L6-15R,
(1)L6-20R,
(1)L6-30R

14.2 x 8.6 x 18.6/
361 x 217 x 472

89/40.5

230 Vac Models5
PW9120 700i

700/490

230

50/60

IEC-C14

(4)IEC-C13

9.6 x 6.2 x 16.2/
243 x 158 x 412

28/12.6

PW9120 1000i

1000/700

230

50/60

IEC-C14

(4)IEC-C13

9.6 x 6.2 x 16.2/
243 x 158 x 412

34/15.3

PW9120 1500i

1500/1050

230

50/60

IEC-C14

(4)IEC-C13

10.8 x 6.7 x 17.5/
275 x 170 x 444

44/19.8

PW9120 2000i

2000/1400

230

50/60

IEC-C14

((4)IEC-C13,
(1)IEC-C19

14.2 x 8.6 x 18.6/
361 x 217 x 472

81.6/37

PW9120 3000i

3000/2100

230

50/60

IEC-C20

(4)IEC-C13,
(1)IEC-C19

14.2 x 8.6 x 18.6/
361 x 217 x 472

85/38.5

Optional Extended Battery Modules (EBMs)
PW9120 BATT 700

-

-

-

Standard
Connector

-

9.6 x 6.2 x 16.2/
243 x 158 x 412

31/14

PW9120 BATT 1000

-

-

-

Standard
Connector

-

9.6 x 6.2 x 16.2/
243 x 158 x 412

44/20

PW9120 BATT 1500

-

-

-

Standard
Connector

-

10.8 x 6.7 x 17.5/
275 x 170 x 444

57/26

PW9120 BATT 2000

-

-

-

Standard
Connector

-

14.2 x 8.6 x 18.6/
361 x 217 x 472

110/50

PW9120 BATT 3000

-

-

-

Standard
Connector

-

14.2 x 8.6 x 18.6/
361 x 217 x 472

110/50

1 Also user-selectable for 100, 110, and 127 Vac.
2 Automatic frequency selection.
3 120V models have 6-ft. attached line cord. 230V models have 6-ft. detachable line cord.
4 Divided into 2 Load Segments (receptacle groups).
5 Also user-selectable for 220 and 240 Vac

Available Options

Order Number Description
IPK-0329 ConnectUPS-BD SNMP/WEB Card
1014018 AS/400 Relay Card

Battery Run Times (in minutes full load/half load)

VA Standard
Internal
Battery
1 EBM 2 EBMs 3 EBMs 4 EBMs 5 EBMs
700

7/18

34/70

64/140

-

-

-

1000

7/18

36/80

66/155

-

-

-

1500

7/18

29/67

56/130

-

-

-

2000

12/34

49/107

93/195

140/310

192/403

240/504

3000

6/15

30/70

57/128

87/191

120/264

148/325

Up to 2 EBMs can be connected to 700/1000/1500VA models and up to 5 EBMs can be connected to 2000/3000VA models.Run time chart provides typical information.Run times are approximate and may vary with equipment,configuration,battery age,temperature,etc.



Powerware Home
Bomara Homepage
Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
email: bobr@bomara.com      web: www.bomara.com
Serving the marketplace for over 35 years