| Electrical
Input |
| Nominal
Voltage |
For
user-selectable voltages see Model
Selection Guide |
| Input
Voltage Range |
80-144
Vac |
| Input
Power Factor |
>.95% |
| Operating
Frequency |
50/60
Hz, Auto-sensing |
| Frequency
Range |
45
- 65 Hz |
| Input
Protection |
Fuse
or circuit breaker |
| Electrical
Output |
| On
Utility Voltage Regulation |
+/-2%
of nominal |
| On
Battery Voltage Regulation |
+/-3%
of nominal |
| Nominal
Output Voltage |
Same
as selected input voltage |
| Output
Voltage Waveform |
Sine
Wave |
| Output
Voltage Distortion |
<3%THD |
| Output
protection |
Electronic
overload sensing,and circuit breaker protection |
| Efficiency |
Online
Mode:>86%;
Hi-Efficiency Mode:>90% |
| Battery |
| Internal
Battery type |
Sealed,
lead-acid; maintenance free |
| EBM
Battery Type |
Sealed,
lead-acid; maintenance free |
| On
Battery Runtime |
See
Battery Runtimes |
| Battery
Replacement |
Hot-swappable
internal and external batteries |
| Recharge
Time |
<4
hours to 90%capacity |
| Start-On-Battery |
Allows
start of UPS without utility input |
| Communications |
| User
Interface |
LCD
status screen |
| Audible
Alarms |
UPS
alarm conditions,including:
On-Battery,Low Battery,Overload, UPS Fault |
| Network
transient Protector |
In
and out jack for all models.
UL497A tested |
| REPO
Port |
Meets
NEC code 645-11 intent and UL requirements |
| Communications |
One
RS232 Serial Port;One Communications Slot; One USB Port |
| Communications
cable |
6-foot
communications cable included |
| Power
Management Software |
Powerware Software Suite CD |
| General |
| Topology |
True
online, double-conversion |
| Diagnostics |
Full
system self-test on power up |
| UPS
Bypass |
Automatic
on Overload or UPS failure <4ms |
| Transfer
Time to battery |
0
ms |
| Dimensions
and Weights |
See
Model Selection Guide |
| Overload
Capacity |
125%
for 10 minutes before transfer to bypass;
150% for 10 seconds before transfer to bypass |
| Environmental
and Safety |
| Safety
Certifications |
UL1778;cUL22.2
NO.107.1 |
EMI
Compliance |
FCC
Part 15, Class B (700-1500), Class A (2000-3000) 230V,
EN 50091-2 Class B (700-1500), Class A (2000-3000) |
| Operating
Temperature |
0
to 40 C (32 to 104 F) |
| Storage
Temperature |
-15
to 50 C (5 to 122 F) |
| Storage
Temperature |
0o
to 25o C (32o to 77o
F) |
| Relative
Humidity |
0%to
95%non-condensing |
| Immunity |
EEE
C62.41,
IEC 61000-4 -2, -3, -4, -5 |
| Network
Transient Protector |
UL497A |
| Audible
Noise at 1 meter |
700-1000VA:
<45dB;1500VA <50dB; 2000-3000 <52dB |
| Altitude |
3000m
(10,000 ft) without deteriorating |
| Note:
Due to continuing product improvement programs, specifications
are subject to change without notice. |