Powerware 9125

Specification Details
High voltage details
| Electrical Input |
| Nominal Voltage |
230 Vac (user-selectable for 200, 220, 230, and 240 Vac
See Model Selection Guide |
| Power Ratings |
700 - 2000VA; See Model Selection Guide |
| Voltage Range |
160 - 288V (without using batteries) |
| Input Power Factor |
>.95, typical |
| Frequency |
50/60 Hz, autosensing |
| Frequency Range |
45 - 65 Hz |
| Electrical Output |
| On Utility Voltage Regulation |
+/-3% of nominal |
| On Battery Voltage Regulation |
+/-3% of nominal |
| Efficiency |
89 - 92%, depending on load |
| Frequency Regulation |
+/- 3 Hz online; +/- 0.1 Hz on battery |
| Load Crest Factor |
3 to 1 ratio |
| Battery |
| Internal Battery type |
Sealed, lead-acid; maintenance free
700/1000VA: (2) 12V, 9 Ah
1250-2000VA: (4) 12V, 9 Ah |
| EBM Battery Type |
PW9125 24 EBM: (8) 12V, 9 Ah
PW9125 48 EBM: (8) 12V, 9 Ah |
| On Battery Runtime |
See Battery Runtimes |
| Battery Replacement |
Hot-swappable internal and external batteries |
| Recharge Time |
<2 hrs. from complete discharge to 80% capacity at nominal line conditions |
| Start-On-Battery |
Allows start of UPS without utility input |
| Communications |
| Serial Port |
RS-232 communications port standard |
| Communications Cable |
6-foot communications cable included |
| ConnectUPS-M SNMP Module (Optional)2 |
SNMP card adds direct control and monitoring capabilities in SNMP-based networks |
| RS-232 Multi-Port Module (Optional)2 |
Equipped with (6) communications ports to provide serial communication to multiple devices |
| USB Module (Optional)2 |
Allows UPS to communicate with Windows 98 computers via USB port; factory-installed option only |
| General |
| Topology |
True online, double-conversion |
| Diagnostics |
Full system self-test on power up |
| UPS Bypass |
Automatic on overload or UPS failure |
| Dimensions and Weights |
See Model Selection Guide |
| Environmental and Safety |
| Safety Markings |
UL, CSA, CB, CE, S, D, N, FI, B, R |
| EMC Markings |
FCC Class B and VCCI Class II, CE, NZ, TAIWAN |
| Surge Suppression |
IEEE/ANSI C62.41 Category B (formerly 587) |
| Audible Noise |
<45 dBA (on utility); <50 dBA (on battery) |
| Storage Temperature |
0o to 25o C (32o to 77o F) |
| Relative Humidity |
5 to 90%%, non-condensing |
| REPO Port |
Meets NEC code 645-II intent and UL requirements |
| Network Transient Protector |
In and out jack for telephone/modem protection of 10Base-T network cable; UL497A tested |
1Due to continuing product improvement programs, specifications are subject to change without notice.
2Optional in place of RS-232 serial port. |
Model Selection Guide
RoHS Products
Model
Number1 |
Part Number2 |
Power Rating
(VA/Watt) |
Input
Connection4 |
Output
Receptacles |
Dimensions HxWxD
(in / mm) |
Unit Wt.
(lb/kg)6 |
| 120 Vac Models3 |
PW9125
700 |
05146012-6591 |
700/490 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
34/15 |
PW9125
1000 |
05146002-6591 |
1000/700 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
34/15 |
PW9125
1250 |
05146008-6591 |
1250/875 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
1500 |
05146005-6591 |
1500/1050 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
2000 |
05146001-6591 |
2000/1400 |
5-20P |
(6) 5-15R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
2000 20R |
05146001-6516 |
2000/1400 |
5-20P |
(2) 5-15R,
(4) 5-20R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
2500 |
103002716-6591 |
2500/1750 |
L5-30P |
(2)5-15R,
(2)5-20R
(1)L5-30R |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
PW9125
3000 |
103002717-6591 |
3000/2100 |
L5-30P |
(2)5-15R,
(2)5-20R
(1) L5-30R |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
| 208 Vac Models4 |
PW9125
2500EU |
103002718-6591 |
2500/1750 |
Detachable L6-20 |
(4) IEC-320 C13
(1) IEC-320 C19 |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
PW9125
3000EU |
103002719-6591 |
3000/2100 |
Detachable L6-20 |
(4) IEC-320 C13
(1) IEC-320 C19 |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
PW9125
2500EUHW |
103002720-6591 |
2500/1750 |
Hardwired |
Hardwired |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
PW9125
3000EUHW |
103002721-6591 |
3000/2100 |
Hardwired |
Hardwired |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
| 230 Vac Models5 |
PW9125
700i |
05146622-6591 |
700/490 |
IEC 320-C14 |
(6) IEC 320-C13 |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
34/15 |
PW9125
1000i |
05146011-6591 |
1000/700 |
IEC 320-C14 |
(6) IEC 320-C13 |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
34/15 |
PW9125
1250i |
05146009-6591 |
1250/875 |
IEC 320-C14 |
(6) IEC 320-C13 |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
1500i |
05146006-6591 |
1500/1050 |
IEC 320-C14 |
(6) IEC 320-C13 |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
2000i |
05146003-6591 |
2000/1400 |
IEC 320-C14 |
(6) IEC 320-C13 |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
2500E |
103002722-6591 |
2500/1750 |
IEC 32-C20 |
(4) IEC 320-C13
(1) IEC 320-C19 |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
50/23 |
PW9125
3000E |
103002723-6591 |
3000/2100 |
IEC 32- C20 |
(4) IEC 320-C13
(1) IEC 320-C19 |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
| PW9125 2500EH |
103002724-6591 |
2500/1750 |
Hardwired |
Hardwired |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
| PW9125 3000EH |
103002725-6591 |
3000/2100 |
Hardwired |
Hardwired |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
PW9125
5000g HW |
103003623-6591 |
5000/3500 |
Hardwired |
(Hardwired |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
5000g HW FC |
103003624-6591 |
5000/3500 |
Hardwired |
Hardwired |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
5000g |
103003633-6591 |
5000/3500 |
L6-30P |
L6-30R |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
5000g FC |
103003634-6591 |
5000/3500 |
L6-30P |
L6-30R |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
6000g HW |
103003625-6591 |
6000/4200 |
Hardwired |
Hardwired |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
6000g HW FC |
103003626-6591 |
6000/4200 |
Hardwired |
Hardwired |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
6000g |
103003635-6591 |
6000/4200 |
L6-30P |
L6-30R |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
6000g FC |
103003636-6591 |
6000/4200 |
L6-30P |
L6-30R |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
1 50/60 automatic frequency selection.
2 120V models are 110V, 120V, 127V user-selectable.
3 208V models are 208V, 220V, 230V, 240V user-selectable.
4 230V models are 208V, 220V, 230V, 240V user-selectable.
5 Add 8.5 lb. for shipping weight. |
Available Options
| Order Number |
Description |
| 05146288-5501 |
X-Slot ConnectUPS-M SNMP Module |
| 05146447-5501 |
X-Slot Multi-Port Module |
| 05141562-0021 |
4 post rack-mount kit (fits 19-inch racks) |
| 05146726-5501 |
2 post rack-mount kit (fits 19-inch racks) |
| 05146871-5501 |
Seismic Kit, Three Unit (for combination of up to 3 UPSs and/or EBMs) |
| 05146875-5501 |
Seismic Kit, Five Unit (for combination of up to 5 UPSs and/or EBMs) |
| 05146520-001 |
2000 VA Low Voltage PowerPass Distribution Module |
| 05146519-001 |
700, 1000, 1250, 1500 VA Low Voltage PowerPass Distr. Module |
| 05146519-002 |
All 230V Models, PowerPass Distribution Module |
Battery Runtimes (in minutes)
| 700/1000 VA Models |
| Load |
Standard
Internal
Batteries |
1 EBM |
2 EBMs |
| 200VA/140W |
37 |
271 |
546 |
| 400VA/280W |
19 |
142 |
278 |
| 700VA/490W |
9 |
72 |
156 |
| 850VA/595W |
6 |
59 |
124 |
| 1000VA/700W |
5 |
48 |
104 |
1250-2000 VA Models |
| Load |
Standard
Internal
Batteries |
1 EBM |
2 EBMs |
3 EBMs |
4 EBMs |
400VA/280W |
46 |
177 |
331 |
501 |
682 |
| 700VA/490W |
25 |
96 |
180 |
272 |
370 |
| 850VA/595W |
21 |
76 |
142 |
214 |
292 |
| 1000VA/700W |
16 |
61 |
115 |
174 |
237 |
| 1250VA/875W |
11 |
46 |
87 |
131 |
179 |
| 1500VA/1050W |
8 |
37 |
70 |
106 |
144 |
| 1800VA/1260W |
6 |
30 |
57 |
85 |
116 |
| 2000VA/1400W |
5 |
26 |
49 |
74 |
100 |
Battery Times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.
Legacy Products
Model
Number1 |
Part Number2 |
Power Rating
(VA/Watt) |
Input
Connection4 |
Output
Receptacles |
Dimensions HxWxD
(in / mm) |
Unit Wt.
(lb/kg)6 |
| 120 Vac Models3 |
PW9125
700 |
05146012-5501 |
700/490 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
34/15 |
PW9125
1000 |
05146002-5501 |
1000/700 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
34/15 |
PW9125
1250 |
05146008-5501 |
1250/875 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
1500 |
05146005-5501 |
1500/1050 |
5-15P |
(6) 5-15R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
2000 |
05146001-5501 |
2000/1400 |
5-20P |
(6) 5-15R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
2000 20R |
05146001-5516 |
2000/1400 |
5-20P |
(2) 5-15R,
(4) 5-20R |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
2500 |
103002716-5501 |
2500/1750 |
L5-30P |
(2)5-15R,
(2)5-20R
(1)L5-30R |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
PW9125
3000 |
103002717-5501 |
3000/2100 |
L5-30P |
(2)5-15R,
(2)5-20R
(1) L5-30R |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
| 208 Vac Models4 |
PW9125
2500EU |
103002718-5501 |
2500/1750 |
Detachable L6-20 |
(4) IEC-320 C13
(1) IEC-320 C19 |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
PW9125
3000EU |
103002719-5501 |
3000/2100 |
Detachable L6-20 |
(4) IEC-320 C13
(1) IEC-320 C19 |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
PW9125
2500EUHW |
103002720-5501 |
2500/1750 |
Hardwired |
Hardwired |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
PW9125
3000EUHW |
103002721-5501 |
3000/2100 |
Hardwired |
Hardwired |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
| 230 Vac Models5 |
PW9125
700i |
05146622-5501 |
700/490 |
IEC 320-C14 |
(6) IEC 320-C13 |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
34/15 |
PW9125
1000i |
05146011-5501 |
1000/700 |
IEC 320-C14 |
(6) IEC 320-C13 |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
34/15 |
PW9125
1250i |
05146009-5501 |
1250/875 |
IEC 320-C14 |
(6) IEC 320-C13 |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
1500i |
05146006-5501 |
1500/1050 |
IEC 320-C14 |
(6) IEC 320-C13 |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
2000i |
05146003-5501 |
2000/1400 |
IEC 320-C14 |
(6) IEC 320-C13 |
3.5 x 17.0 x 19.4 /
89 x 432 x 494 |
50/23 |
PW9125
2500E |
103002722-5501 |
2500/1750 |
IEC 32-C20 |
(4) IEC 320-C13
(1) IEC 320-C19 |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
50/23 |
PW9125
3000E |
103002723-5501 |
3000/2100 |
IEC 32- C20 |
(4) IEC 320-C13
(1) IEC 320-C19 |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
| PW9125 2500EH |
103002724-5501 |
2500/1750 |
Hardwired |
Hardwired |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
| PW9125 3000EH |
103002725-5501 |
3000/2100 |
Hardwired |
Hardwired |
3.5 x 17.0 x 23.9 /
89 x 432 x 607 |
81.5/37 |
PW9125
5000g HW |
103003623-5501 |
5000/3500 |
Hardwired |
(Hardwired |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
5000g HW FC |
103003624-5501 |
5000/3500 |
Hardwired |
Hardwired |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
5000g |
103003633-5501 |
5000/3500 |
L6-30P |
L6-30R |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
5000g FC |
103003634-5501 |
5000/3500 |
L6-30P |
L6-30R |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
6000g HW |
103003625-5501 |
6000/4200 |
Hardwired |
Hardwired |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
6000g HW FC |
103003626-5501 |
6000/4200 |
Hardwired |
Hardwired |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
6000g |
103003635-5501 |
6000/4200 |
L6-30P |
L6-30R |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
PW9125
6000g FC |
103003636-5501 |
6000/4200 |
L6-30P |
L6-30R |
8.63 x 17.37 x 24.94 /
219 x 441 x 633 |
206/93.4 |
1 50/60 automatic frequency selection.
2 Black Chassis Option, change order number from -5501 to -6501 (for 700 VA - 2000VA & 5000/6000 VA models only)
3 120V models are 110V, 120V, 127V user-selectable.
4 208V models are 208V, 220V, 230V, 240V user-selectable.
5 230V models are 208V, 220V, 230V, 240V user-selectable.
6 Add 8.5 lb. for shipping weight. |
|