*UPS with 1 EBM module

*US Model Shown, other plug types available
Powerware Index > Series 9 Index > 9130 Rackmount UPS
Powerware 9130 Rackmount Uninterruptible Power Supply
Also available in a tower version
Click for PPDM (Power Pass Distribution Modules)
The Powerware 9130 rackmount UPS is 2U high and includes a four-post rail kit (two-post rail kit optional). It is a double conversion UPS with 95% efficiency. The unit has all 9 levels of power protection. The 9130 ranges from 700VA to 3000VA (3KVA) and has extended runtime batteries. These extended battery modules (EBM) allow over 4 hours of runtime. The Powerware 9130 is available in both hardwire models or with plug and receptacles. It is also equipped with hot swappable internal batteries. The UPS can be started on battery power only if there is no external power (black start).
The 9130 UPS has a bright, front panel LCD for easy monitoring and management. LEDs also show system status. With optional PDUs (power distribution units) and/or a HotSwap MBP maintenance bypass switch, you can create a low cost N+1 redundant UPS system. It includes two individually controlled load segmentation outlets allow selective load shedding. The 9130 rackmount UPS is also equipped with Remote Emergency Power Off (REPO) and standard relay output contacts. Included NetWatch 5.0 software enables automatic shutdown of UPS protected devices including virtualized servers and is compatible with Cisco Unified Communications Manager 4.3.
9130 UPS units have a communications bay with a standard communications slot for web, SNMP, Modbus, or serial connectivity. This allows you to connect directly to the Ethernet network and the Internet to monitor and manage the UPS with a standard web browser. Through the web interface you can monitor power conditions in real time through existing facilities or building management systems. You can also monitor multiple servers on various operating systems (Unix, Linux, Windows 20XX server) to shut down running server applications before the UPS shuts down (due to lack of power). This is compatible with Oracle, Microsoft Exchange, etc. Receive alarm notifications via SNMP or other interface warning you of dangerous from your environmental monitoring devices or security systems.
Features and Benefits
- Green power UPS with 95% efficiency
- UPS startup on battery power (black start)
- 50/60Hz (auto sensing)
- Offers premium performance with a 0.9 power factor and >95 percent efficiency
- Increases battery service life and system uptime with ABM battery charging technology
- Enables prolonged runtime of essential equipment during power outages by allowing for orderly, remote shutdown of non-critical systems or processes
- Provides installation flexibility with a choice of rack or tower designs, both conserving valuable space
- Ensures data and system integrity with LanSafe power management software
- Provides a two-year limited warranty, an extended warranty, Flex and PowerTrust service contracts, and a $250,000 load protection guarantee (US and Canada)
 |
 |
 |
| Four-post rail kit included (two-post rail kit optional) |
Hot swappable internal batteries in only 2U |
Optional FlexPDU and HotSwap MBP for greater flexibility and uptime |
Technical Specifications
| General |
| User Interface |
Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish |
| LEDs |
Four status-indicating LEDs |
| Topology |
True online, double-conversion |
| Diagnostics |
Full system self-test |
| UPS Bypass |
Automatic bypass |
| Dimensions |
See models table |
| Rail Kit |
Included with all rackmount units |
| Electrical Input |
| Nominal Voltage |
120V: 208–240V |
| Voltage Range |
120V: 90–138 Vac (with load PF of 0.7)
208/230V: 160–276 Vac (with load PF of 0.7) |
| Power Draw of UPS (full load) |
700: 5.8A @120V, 3.4A @208V, 3.0A @230V
1000: 8.3A @120V, 4.8A @208V, 4.3A @230V
1500: 12.5A @120V, 7.2A @208V, 6.5A @230V
2000: 16.6A @120V, 9.6A @208V, 8.7A @230V
2500: 20.8A @120V, 12.0A @208V, 10.9A @230V
3000: 25.0A @120V, 14.4A @208V, 13.0A @230V |
| Dedicated Circuit Breaker Rating |
120V:
700–1500 VA: 15A
2000 VA: 20A
2500–3000 VA: 30A
208/230V:
700–2000 VA: 10A
3000 VA: 16A |
| Frequency |
50/60 Hz (Auto sensing) |
| Frequency Range |
45–65 Hz |
| Electrical Output |
| Power Factor |
0.9 |
| On Utility Voltage Regulation |
±3% of nominal |
| On Battery Voltage Regulation |
±3% of nominal |
| Efficiency |
>95% in high-efficiency mode; >86% in online mode |
| Frequency Regulation |
±3% Hz online |
| Load Crest Factor |
3 to 1 |
| Battery |
| Battery Type |
VRLA 12V/9 Ah (both internal and external) |
| Battery Runtime |
>3 minutes with internal batteries @100% load (0.7 PF) |
| Battery Replacement |
Hot-swappable internal and external batteries |
| Start-On-Battery |
Allows start of UPS without utility input |
| Communications |
| Serial Port |
RS-232 standard, for interface to power management software |
| USB Port |
HID standard, for communicating with Windows 98 and ME computers |
| Relay Output |
Common alarm standard |
| Communications Slot |
Optional communication slots (BD Slot) |
| Optional Communication Cards |
SNMP/Web card for direct control and monitoring in SNMP-based networks, monitoring of UPS status and meters through Web browser interface Relay card for integration to industrial environment and building management systems, remote shutdown for IBM AS/400 systems |
| Environmental |
| Safety Markings |
120/208V: UL, CUL, VCCI
230V: CE, GS |
| EMC Markings |
120V: FCC Class B, EN55022 Class B (1.5 kVA and below); FCC Class A, EN55022 Class A (2.0 kVA and above)
230V: CE (per IEC/EN62040-2: Emissions, Category C1; Immunity, Category C2) |
| Audible Noise |
<50 dB |
| Ambient Operating |
-20˚C (-4˚F) to +40˚C (104˚F) with batteries and -25˚C (-13˚F) to +55˚C (131 ˚F) without batteries |
| Storage Temperature |
5–90% non-condensing |
Heat Dissipation
For all voltages: 230/208 and 120V
| Eaton 9130 Model |
Normal Mode, BTUs/hr |
On Battery, BTUs/hr |
| 700 VA |
350 |
554 |
| 1000 VA |
500 |
674 |
| 1500 VA |
750 |
1011 |
| 2000 VA |
838 |
1348 |
| 2500 VA |
1047 |
146 |
| 3000 VA |
1257 |
1755 |
Model Selection Guide
| Catalog Number |
Rating (VA/Watts) |
Input connection |
Output Receptacles |
Dimensions
H x W x D, in (mm) |
Weight
lb (kg) |
| North American Rack Models: 120V, 50/60 Hz |
| PW9130L700R-XL2U |
700/630 |
5-15P |
(6) 5-15R |
3.4 x 17.2 x 17.7
(86.5 x 438 x 450) |
49.4 (22.4) |
| PW9130L1000R-XL2U |
1000/900 |
5-15P |
(6) 5-15R |
3.4 x 17.2 x 17.7
(86.5 x 438 x 450) |
49.4 (22.4) |
| PW9130L1500R-XL2U |
1500/1350 |
5-15P |
(6) 5-15R |
3.4 x 17.2 x 17.7
(86.5 x 438 x 450) |
54.9 (24.9) |
| PW9130L2000R-XL2U |
2000/1800 |
5-20P |
(6) 5-15/20R, (1) L5-20R |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
68.1 (30.9) |
| PW9130L2500R-XL2U |
2500/2250 |
L5-30P |
(6) 5-15/20R, (1) L5-30R |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
69.2 (31.4) |
| PW9130L3000R-XL2U |
3000/2700 |
L5-30P |
(6) 5-15/20R, (1) L5-30R |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
69.2 (31.4) |
| North American Rack Models: 120V, 50/60 Hz [TAA Compliant] |
| PW9130L700R-XL2US |
700/630 |
5-15P |
(6) 5-15R |
3.4 x 17.2 x 17.7
(86.5 x 438 x 450) |
49.4 (22.4) |
| PW9130L1000R-XL2US |
1000/900 |
5-15P |
(6) 5-15R |
3.4 x 17.2 x 17.7
(86.5 x 438 x 450) |
49.4 (22.4) |
| PW9130L1500R-XL2US |
1500/1350 |
5-15P |
(6) 5-15R |
3.4 x 17.2 x 17.7
(86.5 x 438 x 450) |
54.9 (24.9) |
| PW9130L2000R-XL2US |
2000/1800 |
5-20P |
(6) 5-15/20R, (1) L5-20R |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
68.1 (30.9) |
| PW9130L2500R-XL2US |
2500/2250 |
L5-30P |
(6) 5-15/20R, (1) L5-30R |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
69.2 (31.4) |
| PW9130L3000R-XL2US |
3000/2700 |
L5-30P |
(6) 5-15/20R, (1) L5-30R |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
69.2 (31.4) |
| Global Rack Models: 208V, 50/60 Hz |
| PW9130G1000R-XL2U |
1000/900 |
L6-20P* |
(1) L6-20R, (2) 6-20R |
3.4 x 17.2 x 17.7
(86.5 x 438 x 450) |
49.4 (22.4) |
| PW9130G2000R-XL2U |
2000/1800 |
L6-20P* |
(1) L6-20R, (4) 6-20R |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
54.9 (24.9) |
| PW9130G2500R-XL2U |
2500/2250 |
L6-20P** |
(1) L6-30R, (1) L6-20R, (2) 6-20R |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
69.2 (31.4) |
| PW9130G3000R-XL2U |
3000/2700 |
L6-20P** |
(1) L6-30R, (1) L6-20R, (2) 6-20R |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
69.2 (31.4) |
| PW9130G1000R-XL2UEU |
1000/900 |
L6-20P* |
(6) C13 |
3.4 x 17.2 x 17.7
(86.5 x 438 x 450) |
49.4 (22.4) |
| PW9130G2000R-XL2UEU |
2000/1800 |
L6-20P* |
(8) C13, (1) C19 |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
54.9 (24.9) |
| PW9130G2500R-XL2UEU |
2500/2250 |
L6-20P** |
(8) C13, (1) C19 |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
69.2 (31.4) |
| PW9130G3000R-XL2UEU |
3000/2700 |
L6-20P** |
(8) C13, (1) C19 |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
69.2 (31.4) |
| International Rack Models: 230V, 50/60 Hz |
| PW9130i1000R-XL2U |
1000/900 |
C14 |
(6) C13 |
3.4 x 17.2 x 17.7
(86.5 x 438 x 450) |
49.4 (22.4) |
| PW9130i1500R-XL2U |
1500/1350 |
C14 |
(6) C13 |
3.4 x 17.2 x 17.7
(86.5 x 438 x 450) |
54.9 (24.9) |
| PW9130i2000R-XL2U |
2000/1800 |
C14 |
(8) C13, (1) C19 |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
68.1 (30.9) |
| PW9130i3000R-XL2U |
3000/2700 |
C20 |
(8) C13, (1) C19 |
3.4 x 17.2 x 23.6
(86.5 x 438 x 600) |
68.1 (30.9) |
* C14, w/ detachable L6-20P
** C20, w/ detachable L6-20P
Battery Runtimes
|