Powerware Index > Series 9 Index > 9130 PPDM
Powerware 9130 PowerPass Power Distribution Module
| Product snapshot |
| Power rating: |
2500–3000 VA
|
| Voltage: |
120–240 Vac
|
| Frequency: |
50–60 Hz
|
| Configuration: |
Plug-and-play
and hardwire |
 |
.jpg) |
UPS is on top
PPDM is on bottom
|
The Eaton® PowerPass® power distribution module (PPDM) is designed to enhance the flexibility of the Eaton 9130 3 kVA UPS. The PPDM enables you to upgrade or replace the UPS while continuously providing power to your critical equipment. With the 9130 UPSs, Eaton delivers a best-in-class power solution for maximum system availability and peace of mind. Use the questions in this guide to correctly specify a PPDM.
Features
-
Maintenance Bypass Switch to perform maintenance or upgrade your UPS without powering down your critical systems
- Expanded receptacle and hardwire configurations
- Galvanic isolation for increased protection
- Step-down transformer allows power output of 120V
and a combination of 120V and 208–240V
Model Chart (1)
|
Style Number |
Description
|
Input Voltage (Vac)
|
Output Voltage (Vac)
|
Input Connection (2)
|
Output Receptacles
|
Dimensions
(H x W x D, in)
|
Weight
(lb)
|
EPPDMG3000R-2U-13 (3)
|
103007535-6591
|
PPDM1-HV-US-P2 3 kVA
|
208–240
|
120 |
IEC320-C20
|
(1) L5-30R & (6) 5-20R
|
3.5 (2U) x 17.0 x 23.9
|
76 |
EPPDMG3000R-2U-HW3 (3)
|
103007536-6591
|
PPDM1-HV-US-HW
3 kVA (ROHS)
|
208–240
|
208–240/120
|
Hardwire
|
Hardwire
|
3.5 (2U) x 17.0 x 23.9
|
76 |
EPPDML3000R-2U-HW4 (4)
|
103007537-6591
|
PPDM2-LV-US-HW
3 kVA (ROHS)
|
120 |
120 |
Hardwire
|
Hardwire
|
3.5 (2U) x 17.0 x 23.9
|
20 |
EPPDML3000R-2U-44 (4)
|
103006843-6591
|
PPDM2-LV-US-P1
3 kVA
|
120 |
120 |
L5-30P
|
(1) L5-30R & (6) 5-20R
|
3.5 (2U) x 17.0 x 23.9
|
20 |
1. All models fit in 19-inch rack enclosures and come with a four-post rail kit.
2. Connection cables to the UPS are included with the PPDM; use the input cord from the UPS as input to the PPDM, except for hardwire units.
3. These PPDMs work with the following 9130 models: PW9130G2500R-XL2UEU, PW9130G3000R-XL2UEU and PW9130i3000R-XL2U.
4. This PPDM works with the following 9130 models: PW9130L2500R-XL2U and PW9130L3000R-XL2U.
|
Technical Specifications
| |
PDM1 Models |
PDM2 Models
|
Overcurrent Protection Fuses
|
Two 20A Fuses
PDM1–HV–US: Two 20A fuses
PDM1–HV–US–P1 and PDM1–HV–US–HW:
15A circuit breaker
|
PDM2–LV–US–P1: Two 20A fuses |
Isolation Transformer
|
3 kVA: 208–240V Switch Selectable
120/208–240V Output
|
None |
| Bypass Switch |
30A, 600V |
30A, 600V
|
| Operating Temperature |
0ºC to 40ºC (32ºF to 104ºF) |
0ºC to 40ºC (32ºF to 104ºF)
|
| Relative Humidity |
5–95% noncondensing |
5–95% noncondensing |
Safety Conformance
|
UL 1778
CAN/CSA C22.2, No. 107.1, 107.2; NOm–019–SCFI
|
UL 1778
CAN/CSA C22.2, No. 107.1, 107.2
|
| Agency Markings |
UL, cUL |
UL, cUL |
| EMC (Class A) |
EMC (Class A) |
EN 50091–2, FCC Part 15 Class A, ICES–003 |
| Specifications typical and subject to change without notice |
|