The Eaton 9135 Rack/Tower UPS delivers premium online backup power and scalable battery runtimes for servers, voice and data networks and storage systems. The 9135 UPS provides deployment versatility with a two-in-one form factor. When used as a rack UPS, the 9135 occupies only 3U of rack space. Matching 3U extended battery modules provide additional battery runtime while the energy-efficient design of the 9135 UPS reduces energy consumption.

Click for PPDM (Power Pass Distribution Modules)

9135 UPS

Features and Benefits

  • The 9135 is constantly monitoring power conditions—regulating both voltage and frequency. Even when presented with the most severe power problems, this UPS’s output remains within two percent of nominal voltage.
  • Under normal power conditions, the 9135 can operate in high-efficiency mode at up to 97 percent efficiency thus decreasing utility and cooling bills. In double conversion mode, the UPS operates at up to 91 percent efficiency.
  • With a wide range of acceptable input voltages, this UPS does not depend on batteries to smooth out power fluctuations.
  • Batteries are conserved for those times when utility power is highly unstable or completely out.
  • The 9135 features hot-swappable components and an automatic internal bypass. Users can even remove and replace the battery and power modules without powering down the UPS or interrupting power to loads.
  • Up to four external battery modules (EBMs) can be added to deliver more than an hour of extended runtime at full load— or hours under lighter loads. Each EBM occupies only 3U of rack space.
  • With load segments users can also remotely re-boot locked up network equipment. During a power outage, you could shut down power to less essential loads to extend battery backup time for more critical devices.
  • The 9135 increases power density, delivering 5000 - 6000 VA/4200W in only 3U of rack space, freeing more rack space for IT and telecom equipments.
  • The UPS offers deployment versatility through rack and tower installation options with rail kits and pedestals provided.
  • This UPS is even more user-friendly than its predecessors offering greater distribution capabilities, with eight IEC 10A & two IEC 16A outlets to power multiple pieces of equipment without a PDU.
  • An intuitive LCD interface provides detailed information and menu-driven functions for UPS management. The blue, backlit LCD screen displays four lines of alphanumeric information. LEDs clearly display UPS status.
  • The 9135 comes complete with the Eaton Software Suite CD, including SNMP compatible LanSafe power management software. LanSafe® & Netwatch provide control and visibility over multiple UPSs, using an intuitive, graphical interface.
  • Cuts energy usage and costs with 97% efficiency rating in high efficiency mode
  • Conserves valuable rack space by packing 6000 VA/4200 watts in 3U form factor that includes internal batteries
  • Maximizes availability with extended battery runtime options, hot-swappable batteries, internal bypass and optional maintenance bypass
  • Simplifies UPS monitoring and management with a bright LCD user interface, intuitive power management software and optional eNotify Remote Monitoring service
  • Offers choice of rackmount or tower installation with two-in-one form factor (4-post rail kit and tower pedestals included)
  • Extends battery runtime for critical devices with load segments

Photos

Hot Swappable LCD Rotatable Display
Hot swappable batteries LCD rotatable display
  1. Multilingual graphical LCD display
  2. Panel for replacing batteries
  3. USB & Serial ports, Contact port, EPO connector
  4. EBM battery unit connector
  5. Load segments
  6. Communications card slot

Technical Specifications

General
User Interface Graphical LCD with blue backlight and text in English, French, German, Portuguese, Italian and Spanish
LEDs Four status-indicating LEDs
Topology Double-conversion
Diagnostics Full system self-test
UPS Bypass Automatic bypass
Dimensions See model selection guide
Rail Kit Included with all units
Electrical Input
Nominal Voltage 230V
(208V, 220V, 230V, 240V and 250V user-selectable)
Voltage Range 156–280 Vac (output PF 0.7)
Power Draw of UPS (full load) 5000 VA: 21.7A @230V
6000 VA: 26.0A @208V
Recommended Input Breaker Rating 35A
Frequency 50/60 Hz autoselect
Frequency Range 40–70 Hz
Electrical Output
Power Factor 0.7
On Utility Voltage Regulation ±2% of nominal
On Battery Voltage Regulation ±2% of nominal
Efficiency >97% in high-efficiency mode; 91% in normal mode
Frequency Regulation ±3% Hz online
Load Crest Factor 3 to 1
Battery
Internal Battery Type 5.5 Ah, sealed, lead-acid; maintenance free
External Battery Modules Up to four per 9135, rail kits included for rack mounting
EBM Battery Type 5.5 Ah, sealed, lead-acid; maintenance free
Battery Runtime Four (4) minutes with internal batteries @100% load (0.7 PF)
For additional details, see battery runtime chart
Battery recharge time Six (6) hours to recover 90 percent of nominal backup time after 100 percent RCD load discharge
Battery Replacement Hot-swappable internal and external batteries
Start-On-Battery Allows start of UPS without utility input
Communications
Serial Port RS-232 as standard, RS-232 cable provided
USB Port As standard (HID)
Relay Output DB-9 Dry Contact—common alarm as standard
Communications Slot Optional communication slots (MS-Slot)
Software LanSafe UPS monitoring and management software
Environmental
Safety Markings CE, C-Tick, UL, GS
EMC Markings IEC/EN 62 040-2 class A
Audible Noise Max 46 dB
Ambient Operating 0˚C to +40˚C
Storage Temperature -20˚C to +40˚C with batteries and -25˚C to +55˚C without batteries
Relative Humidity 5–90% non-condensing

Heat dissipation (BTUs/hour)

Operating mode Efficiency 5 kVA 6 kVA
Normal 91% 1150 1350
Battery 86% 1650 1960
High efficiency 97% 370 450

Model Selection Guide

Catalog Number Rating (VA/Watts) Input connection Output Receptacles Dimensions
H x W x D, mm
Weight
kg
PW9135G5000-XL3UEU 5000/3500 Hardwired Hardwired + (2) C19, (8) C13 130 x 444 x 741 57.0
PW9135G6000-XL3UEU 6000/4200 Hardwired Hardwired + (2) C19, (8) C13 130 x 444 x 741 57.0

Battery Backup Times (in minutes)

Load (VA/Watts) Standard Internal Batteries +1 EBM +2 EBMs +3 EBMs +4 EBMs
1000/700 36 132 232 332 433
2000/1400 13 52 95 140 184
3000/2100* 10 40 74 110 146
4000/2800 7 29 53 80 107
5000/3500 5 22 41 62 83
6000-4200* 4 18 33 50 68

* Runtimes available for the 6 kVA model only.

 

 