Powerware
9150
Specification
Details
Split Phase North American Model Technical Specifications
| Power |
| Ratings |
8,
10, and 12.5kVA |
| Technology |
Online,
double-conversion topology with static bypass switch
and maintenance bypass switch. Frequency independent
operation |
| Electrical
Input |
| Rated
Voltage |
See
Model Selection Guide |
| Input
Voltage |
Two
Phase; 200, 208, 220, 240. |
| Voltage
Range |
Two
phase; 85-146 V per phase |
| Frequency
Range |
45
- 65 Hz |
| Rated
Frequency |
50/60
HZ selectable, or auto-configuring |
| Power
Factor |
.95
typical |
| Efficiency |
89%
online; 98% with Efficiency Optimizer (optional
setting) |
| Electrical
Output |
| Voltage |
200/100,
208/220, 220/110, 220/127, 240/120
(Auto-configuration at first startup or selectable
through font panel) |
| Frequency |
50/60
Hz, +/-0.5, +/-2.0, +/-3.0 Hz selectable synchronization
to utility; +/-0.005 Hz free running, slew rate
2.5 Hz/sec (programmable) |
| Voltage
Regulation |
+/-2%
static |
| Dynamic
Response |
+/-
5% at 100% load change response time 1ms |
| Voltage
Distortion |
2%
THD on linear load
<5% THD on nonlinear load |
| Overload
Capacity |
150%
30 seconds on inverter
1000% 20 ms on bypass |
| Battery |
| Type |
Sealed
lead-acid batteries |
| Backup
Time |
See
Estimated Backup Times |
| Recharge
Time |
<3
hours to 90% capacity |
| Battery
Test |
Inovative
monitoring with Advanced Battery Management (ABM™) |
| Start-On-Battery |
After
initial startup, UPS can be turned on using internal
batteries |
| Optional
External |
EBC-48:
48 X 7Ah (DC voltage: 288V) |
| Battery
Ratings |
EBC-96;
96 X 7Ah (Dc voltage: 288V) |
| Control
Features |
| User
Interface Monitoring Panel LEDs |
UPPS
on, Line on, Battery operation, Bypass Overload,
Overtemperature, Service required, Load bar graph,
and Audible alarm |
| Serial
Communication Post |
(2)
RS-232 serial communications ports, 1 with full
modem compatible interface and 1 computer interface
port. The computer port provides 24 VDC power, 5
watts maximum, to power the ConnectUPS SL SNMP Adapter.
Both ports are UPSCode-II and BCM compatible |
| Voltage
Free Relays |
Line
failure, low battery, bypass, and alarm. Emergency
power off (input) |
| Environmental |
| Operating
Temperature |
15-25oC
(recommended), 1-40o C |
| Humidity |
5-95%
RH non-condensing |
| Ventilation |
Fan
Cooling, temperature uP monitored; vent holes on
both sides of UPS |
| Audible
Noise |
<50
dBA at 3 feet |
| RFI
Suppression |
FCC
Class A |
| Safey |
UL
1778m cUL C22.2/107.1 |
| Input
surge Immunity |
ANSI
C62.41 Cat B (Formerly IEEE587 Class B) |
| Options |
External
battery cabinets
Remote status panel
Power distribution panel
2" X 16" Alphanumeric Display (ViewUPS) |
| Dimensions
and Weight |
See
Model Selection Guide |
Due to continuing product improvement programs, specification
are subject to change without notice.
Model
Selection Guide
Rating
(kVA) |
Frequency
(Hz)1 |
Input
Voltage
(Vac)2 |
Output
Voltage
(Vac) |
Dimensions
H x W x D (in)3 |
Weight
(lb/kg) |
| 8.04 |
50/60 |
200,
208, 220, 240 |
(200/100,
220/110. 120/240)5
(208/120, 220/127)6 |
28
X 16 X 29.5 |
510/231 |
| 10.04 |
50/60 |
200,
208, 220, 240 |
(200/100,
220/110. 120/240)5
(208/120, 220/127)6 |
28
X 16 X 29.5 |
510/231 |
| 12.5 |
50/60 |
200,
208, 220, 240 |
(200/100,
220/110. 120/240)5
(208/120, 220/127)6 |
28
X 16 X 29.5 |
510/231 |
| External
Battery Cabinet |
| EBC-48 |
|
|
|
28
X 16 X 29.5 |
422/191 |
| EBC-96 |
- |
- |
- |
28
X 16 X 29.5 |
719/326 |
1Selectable,
auto-configuring. Output voltage is auto-configured to match
input.
2Two phases required
3Power Distribution Modeul adds 5" of depth
4Available in 32 and 48 battery models. See Battery
Run Times
5180o phase displacement.
6120o phase displacement.
1 Cabinet
= EBC96
1/2 Cabinet = EBC48
This guide provides typical application information. Battery times are approximate
and may vary with equipment, configuration, disk access, battery age, temperature,
etc.
Battery Run Times
(in minutes)
Basic
32 Battery Model*
| Load
(VA) |
Load
(Watts) |
Time
(minutes) |
| 2000 |
1400 |
47 |
| 3000 |
2100 |
31 |
| 4000 |
2800 |
22 |
| 5000 |
3500 |
17 |
| 6000 |
4200 |
14 |
| 7000 |
4900 |
11 |
| 8000 |
5600 |
10 |
| 9000 |
6300 |
8 |
| 10000 |
7000 |
7 |
*With
no external battery capability
48
Battery Model
| Load
(VA) |
Load
(Watts) |
UPS
with internal batteries |
1/2
Cabinet |
1
Cabinet |
1
1/2
Cabinet |
2
Cabinet |
2
1/2
Cabinet |
3
Cabinet |
4
Cabinet |
5
Cabinet |
6
Cabinet |
7
Cabinet |
8
Cabinet |
9
Cabinet |
10
Cabinet |
| 2000 |
1400 |
80 |
195 |
329 |
477 |
636 |
805 |
--- |
--- |
--- |
--- |
--- |
--- |
--- |
--- |
| 3000 |
2100 |
52 |
127 |
215 |
311 |
415 |
525 |
--- |
--- |
--- |
--- |
--- |
--- |
--- |
--- |
| 4000 |
2800 |
37 |
92 |
156 |
226 |
301 |
381 |
464 |
642 |
--- |
--- |
--- |
--- |
--- |
--- |
| 5000 |
3500 |
29 |
71 |
120 |
175 |
233 |
295 |
359 |
497 |
--- |
--- |
--- |
--- |
--- |
--- |
| 6000 |
4200 |
23 |
58 |
97 |
141 |
188 |
238 |
290 |
401 |
520 |
645 |
775 |
911 |
1051 |
1196 |
| 7000 |
4900 |
19 |
48 |
81 |
117 |
156 |
198 |
241 |
334 |
433 |
536 |
645 |
758 |
875 |
996 |
| 8000 |
5600 |
17 |
41 |
69 |
100 |
133 |
168 |
206 |
284 |
368 |
457 |
550 |
646 |
745 |
848 |
| 9000 |
6300 |
14 |
35 |
60 |
86 |
115 |
146 |
178 |
246 |
319 |
396 |
476 |
560 |
646 |
735 |
| 10000 |
7000 |
13 |
31 |
52 |
76 |
101 |
128 |
157 |
217 |
281 |
348 |
419 |
492 |
568 |
647 |
| 11000 |
7700 |
12 |
28 |
47 |
68 |
90 |
114 |
139 |
193 |
250 |
310 |
373 |
438 |
506 |
575 |
| 12000 |
8400 |
11 |
25 |
42 |
61 |
81 |
103 |
125 |
173 |
224 |
278 |
335 |
393 |
454 |
517 |
| 12500 |
8750 |
9 |
23 |
40 |
58 |
77 |
97 |
119 |
165 |
213 |
265 |
318 |
374 |
431 |
491 |
|