Split Phase North American Model Technical Specifications
Power
Ratings 8, 10, and 12.5kVA
Technology Online, double-conversion topology with static bypass switch and maintenance bypass switch. Frequency independent operation
Electrical Input
Rated Voltage See Model Selection Guide
Input Voltage Two Phase; 200, 208, 220, 240.
Voltage Range Two phase; 85-146 V per phase
Frequency Range 45 - 65 Hz
Rated Frequency 50/60 HZ selectable, or auto-configuring
Power Factor .95 typical
Efficiency 89% online; 98% with Efficiency Optimizer (optional setting)
Electrical Output
Voltage 200/100, 208/220, 220/110, 220/127, 240/120
(Auto-configuration at first startup or selectable through font panel)
Frequency 50/60 Hz, +/-0.5, +/-2.0, +/-3.0 Hz selectable synchronization to utility; +/-0.005 Hz free running, slew rate 2.5 Hz/sec (programmable)
Voltage Regulation +/-2% static
Dynamic Response +/- 5% at 100% load change response time 1ms
Voltage Distortion 2% THD on linear load
<5% THD on nonlinear load
Overload Capacity 150% 30 seconds on inverter
1000% 20 ms on bypass
Battery
Type Sealed lead-acid batteries
Backup Time See Estimated Backup Times
Recharge Time <3 hours to 90% capacity
Battery Test Inovative monitoring with Advanced Battery Management (ABM™)
Start-On-Battery After initial startup, UPS can be turned on using internal batteries
Optional External EBC-48: 48 X 7Ah (DC voltage: 288V)
Battery Ratings EBC-96; 96 X 7Ah (Dc voltage: 288V)
Control Features
User Interface Monitoring Panel LEDs UPPS on, Line on, Battery operation, Bypass Overload, Overtemperature, Service required, Load bar graph, and Audible alarm
Serial Communication Post (2) RS-232 serial communications ports, 1 with full modem compatible interface and 1 computer interface port. The computer port provides 24 VDC power, 5 watts maximum, to power the ConnectUPS SL SNMP Adapter. Both ports are UPSCode-II and BCM compatible
Voltage Free Relays Line failure, low battery, bypass, and alarm. Emergency power off (input)
Environmental
Operating Temperature 15-25oC (recommended), 1-40o C
Humidity 5-95% RH non-condensing
Ventilation Fan Cooling, temperature uP monitored; vent holes on both sides of UPS
Audible Noise <50 dBA at 3 feet
RFI Suppression FCC Class A
Safey UL 1778m cUL C22.2/107.1
Input surge Immunity ANSI C62.41 Cat B (Formerly IEEE587 Class B)
Options External battery cabinets
Remote status panel
Power distribution panel
2" X 16" Alphanumeric Display (ViewUPS)
Dimensions and Weight See Model Selection Guide


Due to continuing product improvement programs, specification are subject to change without notice.

Model Selection Guide

Rating
(kVA)
Frequency
(Hz)1
Input Voltage
(Vac)2
Output Voltage
(Vac)
Dimensions
H x W x D (in)3
Weight
(lb/kg)
8.04 50/60 200, 208, 220, 240 (200/100, 220/110. 120/240)5
(208/120, 220/127)6
28 X 16 X 29.5 510/231
10.04 50/60 200, 208, 220, 240 (200/100, 220/110. 120/240)5
(208/120, 220/127)6
28 X 16 X 29.5 510/231
12.5 50/60 200, 208, 220, 240 (200/100, 220/110. 120/240)5
(208/120, 220/127)6
28 X 16 X 29.5 510/231
External Battery Cabinet
EBC-48       28 X 16 X 29.5 422/191
EBC-96 - - - 28 X 16 X 29.5 719/326

1Selectable, auto-configuring. Output voltage is auto-configured to match input.
2Two phases required
3Power Distribution Modeul adds 5" of depth
4Available in 32 and 48 battery models. See Battery Run Times
5180o phase displacement.
6120o phase displacement.

1 Cabinet = EBC96
1/2 Cabinet = EBC48
This guide provides typical application information. Battery times are approximate and may vary with equipment, configuration, disk access, battery age, temperature, etc.


Battery Run Times
(in minutes)

Basic 32 Battery Model*

 Load (VA)  Load (Watts)  Time (minutes)
 2000  1400  47
 3000 2100  31
 4000  2800  22
 5000  3500  17
6000  4200  14
7000  4900  11
8000  5600  10
9000  6300  8
 10000  7000 7

*With no external battery capability


48 Battery Model

Load (VA) Load (Watts) UPS with internal batteries 1/2
Cabinet
1
Cabinet
1 1/2
Cabinet
2
Cabinet
2 1/2
Cabinet
3
Cabinet
4
Cabinet
5
Cabinet
6
Cabinet
7
Cabinet
8
Cabinet
9
Cabinet
10
Cabinet
2000 1400 80 195 329 477 636 805 --- --- --- --- --- --- --- ---
3000 2100 52 127 215 311 415 525 --- --- --- --- --- --- --- ---
4000 2800 37 92 156 226 301 381 464 642 --- --- --- --- --- ---
5000 3500 29 71 120 175 233 295 359 497 --- --- --- --- --- ---
6000 4200 23 58 97 141 188 238 290 401 520 645 775 911 1051 1196
7000 4900 19 48 81 117 156 198 241 334 433 536 645 758 875 996
8000 5600 17 41 69 100 133 168 206 284 368 457 550 646 745 848
9000 6300 14 35 60 86 115 146 178 246 319 396 476 560 646 735
10000 7000 13 31 52 76 101 128 157 217 281 348 419 492 568 647
11000 7700 12 28 47 68 90 114 139 193 250 310 373 438 506 575
12000 8400 11 25 42 61 81 103 125 173 224 278 335 393 454 517
12500 8750 9 23 40 58 77 97 119 165 213 265 318 374 431 491