| Input |
| Input
for rectifier |
380/220V:
400/230V or 415/240V |
| Input
for bypass |
380/220V:
400/230V or 415/240V |
| Voltage
range |
294/170V
- 478/276V |
| Frequency |
50/60
Hz |
| Power
Factor |
0.96 |
| Efficiency |
94%
(online)
99% (Efficiency optimizer) |
| Output |
| Voltage |
380/220V:
400/230V or 415/240V ±1% field selectable |
| Frequency |
50/60
Hz ±0.5 ±1.0 or ±2.0 Hz selectable synchronized to
mains
±0.005 Hz free running, slew rate 1Hz/sec. |
| Dynamic
response |
±5%
at 100% load change response time 1ms to steady state |
| Voltage
disortion |
<2%
THD on linear load
<5% THD on nonlinear load |
| Overload
capacity |
150%
30 sec. on inverter |
| Battery |
| Type |
Sealed
lead-acid batteries |
| Back-up
time |
typical
10-20 min at full load |
| Recharge
time |
<5
hr up to 90% capacity |
| Battery
management |
ABM™
Technology (Advanced Battery Management™) |
| Battery
Test |
DC
Expert™ |
| Control
Features |
| User
interface |
Monitoring
panel with LCD display: LED's: UPS on, Line on, Battery
operation
Bypassed, and Audible alarm |
| Remote
interface |
2
pcs RS232 ports - one with modem interface
Voltage free relays: Line failure, Low battery, Bypass
and Alarm
Emergency power off - input, Building alarm signal
- inputs |
| Environmental |
| Temperature |
0-40°C,
recommended 15-25°C |
| Humidity |
5-90%
RH non-condensing |
| Ventilation |
Fan
cooling, temperature µP monitored |
| Audible
noise |
<50dB(A)
at 1 metre |
| Safety |
EN50091-1 |
| EMC |
EN50091-2
(IEC801) |
| Protection
class |
IP21 |
| |
| Weight
(kg) |
215 |
| Dimensions
WxDxH (mm) |
382x775x1530 |
| Software |
| |
-LanSafe v.5 with Cross Platform shutdown
-PowerVision monitoring compatible
-PowerCare®
-Sentinel - FORS
(Full Online Remote Service) compatible |
| Options |
| |
-External
Battery Cabinets
-10 year batteries
-Remote Status Panel
-Isolation transformer
-input filter for <10% THD
-LanQuattro
-Alarm Extension Unit
-ConnectUPS SNMP adapter
-External LCD Panel |