625-750kVA Spec Details

 


Powerware 9315

Technical Specifications


625 to 750 kVA
  • 9315-625/625 - 625kVA/500kW
  • 9315-750/750 - 750kVA/600kW

  

Input

Voltage Range

 +10% to -15%

Frequency Range

+/-5%

Surge Protection

 Meets ANSI C62.41, Category A & B, EN 50091-2 and EN 50082-2

Power Factor  0.85 Typical at full load
Output

Voltage Regulation

Better than +/- 1%

Voltage THD

 Less than 5% (100% nonlinear load); Less than 3% (100% linear load)

Transient Response

 Less than 5% for 100% load, step full recovery within 1 cycle

Frequency Regulation (Free Run) +/- 0.005 Hz
Frequency Sync Range +/- 0.5 Hz
Frequency Slew Rate 1 Hz/sec.
Load Crest Ratio 3:1

Safety (pending)

  UL 1778 Listed
CUL CAN/CSA C22.2NO.107.1-M91 Listed EN 50091-1
All Cabinets provide seismic mounting features, selectable DC ground fault detection capability

Environmental

Audible Noise

 <75 dBA at 1 meter

Ambient Operating Temperature

 0C to 40C

Ambient Storage Temperature

 -20C to 70C

Altitude 5000 ft. (1500 m) at 40C without derating

Relative Humidity

 5-95% non-condensing

EMC Meet FCC Class A, EN 50091-2 (CISPR 22, Class A, Restricted Access)
Electrostatic Discharge Withstands 25kV without damage or disturbance to load

*Specifications subject to change without notice.

 

 9315-750/750

 9315-750/625

  225kVA/180kW

  225kVA/180kW

Input Voltage  volts

 480

 600

 480

600

Output Voltage  volts

 480

 600

 480

600

Input Voltage Range 

 Minimum

 volts

 408

 510

 408

510

 Maximum

 volts

 528

 660

 528

 600

Input/Output Frequency

 Hz

60

60

 60

 60

AC Input 

 Nominal Amps

 amps

 913

730

 761

609

 Maximum Amps

 amps

 1141

913

 951

761

Bypass Input  

 Nominal Amps

 amps

 902

 722

 752

 601

AC Ouput 

 Nominal Amps

 amps

 902

 722

 752

 601

 10 minutes max

 amps

 1128

 902

 940

 752

DC Link 

 Nominal DC Voltage

 volts

 384

384

 384

 384

Float Voltage

 volts

 432

432

 432

 432

End of Discharge

 volts

 320

320

 320

 320

Nominal Amps

 amps

 1954

9554

 1628

 1628

Physical Attributes (w/o batt.) 
Single Module RT Configurations 

 Installed Weight

 lbs

 13,200

13,200

 13,200

 13,200

 Installed Width

 inches

 149"

 149"

 149"

 149"

 Multimodule Configurations 

 Installed Weight

 lbs

 12,600

 12,600

 12,600

 12,600

 Installed Width

 inches

 126 5/8"

 126 5/8"

 126 5/8"

 126 5/8"

System Efficiencies 

 100% Load

 %

 94

 94

 94

 94

 75% Load

  %

 94

 94

 94

 94

 50% Load

  %

 93

 93

 93

 93

Full Load Heat Dissipation 

 BTU/Hr. (x1000)

 

130.8

130.8

  109.0

 109.0

 KCal/Hr. (x1000)

 

33.0

33.0

 27.5

 27.5

Inverter Efficiency (Full Load)   %

 95

95

 95

 95

 


Powerware Home