Powerware 9335 - Three Phase UPS

Specification Details

Input Specifications

80kVA
120kVA

Input Power w/ charged battery &
rated output power

KW
67.4
101
Maximum input power w/ rated output power
KW
80
120
Input voltage
Voltage tolerance with 100% load
Voltage tolerance with 75% load
V
V(%)
V(%)
480Y/277 V (Four wire + GND)
(-20%, +15%)
(-30%, +15%)
Input frequency
Hz
40-100 Hz
Input power factor
PF
0.98
Input current waveform
Sinewave
Input current distortion
Thd
<9%
Inrush current
Soft-start (inrush current=load current)
Output Specifications
Output rating
kVA
80 kVA
120 kVA
Output voltage
V
480 Y/277 V (four wire + ground)
Output power factor
PF
0.8
Inverter technology
IGBT bridge
Output voltage regulation
Static
Load step (0-100%, 100-0%)
Distortion with linear load
Distortion with non-linear load


%
%
%
%


<±1.5
<±4
±1.5
<±4
Recovery time after load step (0-100%, 100-0%)
ms
20
Permissible unbalanced load
%
100%
Output waveform
Sine wave
Output frequency
Hz
60
Output frequency tolerance
Free-running, quartz oscillator
Synchronized with input (adjustable)

%
%

±0.1
±4
Frequency slew rate
Hz/s
1
Overload capability
110% 10 min., 125% 6 min., 150% 30 sec.
Short circuit capability
Yes
Crest factor
3 to 1
Bypass Specifications
Overload capacity
%
150% continuous, 200% for 1 min., 1000% for 10 ms
Load transfer time from inverter to bypass
(ms)
0 ms
Load transfer time from bypass to inverter
(ms)
<1 ms
Minimum input voltage before inhibiting the bypass
V
229
Integrated maintenance bypass
Yes
Input terminals
Four wire, input plus ground
Efficiencies
Double conversion A
efficiency with battery fully charged
100/75/50/25% linear load 0.8 pf
100/75/50/25% linear load 1.0 pf
AC-AC

%
%
80 kV

94.5/94.4/94/90
94.5/93.5/92/87
120 kVA

94/94/93/90
93/93/92/87
Heat dissipation with 100% load (cos = 0.8 ind)
With 100% linear load (cos = 0.8 ind)
With 100% linear load (cos = 1)

W
W

2000
3500

3000
5200

Battery Times

Model Number
Weight (lbs.)
Dimensions WxDxH (inches)
80kVA
120kVA
1CR440TC065480
1CR440TC100480
2698
3543
40x32.5x77
7 min.
15 min.
1CR548TC090576
1CR548TC120576
3643
4642
48x32.5x77
5 min.
15 min.


Powerware Home
Bomara Homepage
Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
email: bobr@bomara.com      web: www.bomara.com
Serving the marketplace for over 35 years