General
Characteristics |
| Installation |
Line up
and match to UPS Front access only |
| Color |
Same as UPS |
| Construction |
NEMA 1 ventilated |
| Input Voltage |
208, 480 |
Output
Voltage |
| Isolation |
208, 208/120V |
| Distribution |
208/120V |
Dimensions |
| 40 - 80kVA |
35.6"w x 31.6"d x 73.7"h |
| Weight (lbs) |
1200 (max) |
Certification |
| Safety |
UL1778 |
| Markings |
UL, CUL |
User
Interface |
| Cable Entry |
Top or Bottom |
| EPO switch |
Optional |
| Remote Monitoring |
Optional |
Transformer
Option |
| Electrostatic Shield |
Standard |
| Insulation |
150ºC
Rise, Class H |
| Impedance |
5% (maximum) |
| K-factor |
K13
(standard); K20 (optional) |
| Compensation Taps |
2-FCAN, 4-FCBN
standard |
| Overload Protection |
Standard |
Power
Distribution Option - Panelboard Distribution |
| Quantity |
2 (max) |
| Voltage |
208/120V |
| Main Breaker |
225A, 65kAIC |
| Circuits |
84
(max) |
| Power
Distribution Option - Distribution
Breakers (in lieu of panelboards) |
| Quantity |
6 (max) |
| Voltage |
208/120V |
| Size |
225A, 65kAIC |
Maintenance
Bypass Option |
| Maintenance Bypass |
Optional |
|