UPS
Rating (0.9 power factor) |
| kVA |
40 |
80 |
120 |
160 |
| kW |
36 |
72 |
108 |
144 |
General
Characteristics |
| Efficiency |
94% |
| Parallel Capability |
4x modules w/o
tie cabinet;
8x with tie cabinet |
| Audible Noise |
<65dBA
@ 1 meter |
| Altitude (max) |
2000m at 40º C |
Input
Characteristics |
| Voltage |
208,
480, 600¹ |
| Voltage Range |
+10%
/ -15% |
| Rated Frequency |
45-65 Hz |
| Power Factor |
0.99
(min) |
| Input Current Distortion |
<4.5%
(no input filter required) |
| Inrush |
6
times rated input current |
| Soft Start Capability |
Yes |
| Internal Backfeed Protection |
Yes |
Output
Characteristics |
| Voltage |
208² , 480² ,
600³ |
| Regulation |
+
/ -1% |
| Inverter |
PWM with IGBT Switching |
| Voltage THD |
< 1.5%
(100% linear load);
< 5% (non-linear load) |
| Load Power Factor Range |
0.9
lagging to 0.9 leading |
Battery |
| Battery types |
VRLA, AGM, Gel,
Wet |
| Battery voltage |
384
- 480, variable |
| Temperature Compensation |
Yes |
| Charging method |
Advanced
Battery Management™ technology |
Dimensions |
Size (w x d x h)
40-80 kVA Modules |
18.9" x
31.6" x 73.7" |
Weight (lbs)
40-80 kVA Modules |
600 |
Size (w x d x h)
120-160 kVA Modules |
35.6" x 31.6" x
73.7" |
Weight (lbs)
120-160 kVA Modules |
950 |
User
Benefits |
| Control Panel (LCD) |
8 lines x 40 characters |
| Battery Start-up |
Standard |
| Frequency Conversion |
Standard |
| Remote Display Panel |
Optional |
| Multi-language |
Standard |
| Building Alarm Inputs |
2
(galvanic isolated) |
Service |
| Internal Input Breaker |
Standard |
| Back/Side Against Wall
Installation |
Standard |
Accessories |
| System Parallel Cabinet |
Optional |
External Maintenance
Bypass |
Optional |
| Integrated Distribution Cabinet |
Optional |
| Isolation Transformer |
Optional |
Certification |
| Safety |
UL1778, CUL |
| EMC |
FCC
Class A |
| Surge |
ANSI
C62, 41 Cat. A&B |
Remote
Monitoring |
| Monthly report via RJ45
LAN/Ethernet connection |
Standard |
Communications |
| Software Compatability |
PowerVision®,
LanSafe™,
FORESEER® |
| Communication Cards |
Two
X-Slots standard. Maximum of four
X-slots with the Mini-CSB option. The
following connectivity card options can be installed at any
time:
-ConnectUPS Web/SNMP/xHub Card
-Modbus Card
-Relay Interface Card (Use for AS400 ’s)
-Industrial Relay Card (5A@120V)
-Parallel Card provides CAN communications, isolated RS-484 port
-Environmental Monitoring Probe (EMP)* |
| Remote Inputs/Outputs |
Two building alarms
inputs and one summary alarmcontact (5A@120V)standard |
| Four more building
alarm inputs available with the Mini-CSB option |
| Remote Monitor Panel |
Eight
backlit status indicator lamps plus an audible horn** |