Spec Details

Integrated Distribution Cabinet

Cabinet Spec Details


Powerware 9390 UPS - Three Phase UPS
Double Conversion, Scalable, N+1 Redundancy

Specification Details

UPS Rating (0.9 power factor)

kVA 40 80 120 160
kW 36 72 108 144

General Characteristics

Efficiency

94%

Parallel Capability

4x modules w/o tie cabinet;
 8x with tie cabinet

Audible Noise <65dBA @ 1 meter
Altitude (max) 2000m at 40º C

Input Characteristics

Voltage

208, 480, 600¹

Voltage Range

+10% / -15%

Rated Frequency 45-65 Hz
Power Factor 0.99 (min)
Input Current Distortion

<4.5% (no input filter required)

Inrush

6 times rated input current

Soft Start Capability

Yes

Internal Backfeed Protection

Yes

Output Characteristics

Voltage 208² , 480² , 600³
Regulation

+ / -1%

Inverter PWM with IGBT Switching
Voltage THD

< 1.5% (100% linear load);
 < 5% (non-linear load)

Load Power Factor Range

0.9 lagging to 0.9 leading

Battery

Battery types VRLA, AGM, Gel, Wet
Battery voltage 384 - 480, variable
Temperature Compensation

Yes

Charging method

Advanced Battery Management™ technology

Dimensions

Size (w x d x h)
40-80 kVA Modules

18.9" x 31.6" x 73.7"

Weight (lbs)
40-80 kVA Modules

600

Size (w x d x h)
120-160 kVA Modules
35.6" x 31.6" x 73.7"
Weight (lbs)
120-160 kVA Modules
950

User Benefits

Control Panel (LCD) 8 lines x 40 characters
Battery Start-up Standard
Frequency Conversion Standard
Remote Display Panel

Optional

Multi-language

Standard

Building Alarm Inputs

2 (galvanic isolated)

Service

Internal Input Breaker

Standard

Back/Side Against Wall Installation

Standard

Accessories

System Parallel Cabinet Optional
External Maintenance
Bypass

Optional

Integrated Distribution Cabinet Optional
Isolation Transformer Optional

Certification

Safety UL1778, CUL
EMC FCC Class A
Surge ANSI C62, 41 Cat. A&B

Remote Monitoring

Monthly report via RJ45 LAN/Ethernet connection Standard

Communications

Software Compatability PowerVision®, LanSafe, FORESEER®
Communication Cards Two X-Slots standard. Maximum of four X-slots with the Mini-CSB option. The following connectivity card options can be installed at any time:
 -ConnectUPS Web/SNMP/xHub Card
-Modbus Card
-Relay Interface Card (Use for AS400 ’s)
-Industrial Relay Card (5A@120V)
-Parallel Card provides CAN communications, isolated RS-484 port
-Environmental Monitoring Probe (EMP)*
Remote Inputs/Outputs Two building alarms inputs and one summary alarmcontact (5A@120V)standard
Four more building alarm inputs available with the Mini-CSB option
Remote Monitor Panel Eight backlit status indicator lamps plus an audible horn**

* Not an X-Slot card.Requires the ConnectUPS Web/SNMP/xHub card.
** Requires the Parallel Card option (RS-485 port)and requires an external 120V power supply to drive the RMP.

¹ 600V applications require an input transformer.
² Output transformers are required if the desired output voltage is not the same as the input voltage.
³ 600V applications require an output transformer.
¹²³ Please refer to Integrated Distribution Cabinet brochure 9390IDC for more information.