Network Management Card & Modbus/Jbus
Part Number 103006827
Mini-Slot: Part Number 66103
The Network Management Card & Modbus/Jbus (66103) is recommended for central UPSs
protecting entire networks or for UPS units backing up critical loads. With the card installed, the UPS has its own IP address and uses the local computer capabilities to:
● Supply web pages (http or https (SSL)) with information on status conditions and measurements/settings/alarms,
● Integrate an SNMP-based NMS such as HP OpenView, IBM Tivoli Netview and Computer Associates Unicenter,
● Communicate with shutdown modules installed on the protected servers (Network Shutdown Module),
● Send e-mail and SMS messages,
● Control the ON/OFF function of the UPS and the outlets,
● Monitor the Environment Sensor (optional, cat. no. 66846).

| Technical Characteristics |
Physical characteristics
|
Dimensions (W x D x H)
|
132 x 66 x 42 mm
|
Weight
|
70 g
|
RoHS
|
100% compatible
|
Storage
|
Storage temperature range
|
-10°C to 70°C
|
Ambient conditions
|
Operating temperature range
|
0°C to 40°C
|
Relative humidity
|
90% RH max. without condensation
|
Card performance
|
Supply voltage
|
5V ±5%
|
Supply current (all LEDs ON and
Environment Sensor connected)
|
300 mA max.
|
Functions
|
Web supervision
|
5 browsers max. (http),
3 browsers max. (https)
|
Languages
|
English, French, German, Italian, Spanish
|
Alarms
|
E-mail, SNMP TRAP, Web page
|
Log
|
400 measurements or events
|
Server protection
|
Up to 100 servers protected
|
Network
|
Fast ETHERNET, 10/100 Mbits, auto-negotiation
HTTP 1.1, SNMP V1, NTP, TFTP, SMTP, BOOTP/DHCP
|
Identification
|
User name and password
|
Security
|
SSL 3.0, TLS 1.0
|
Browsers
|
Microsoft Internet Explorer 6.x or higher
|
NMS
|
Enterprise Power Manager (EPM) Management-Pac 2
|
MIB
|
MIB II standard - UPS EATON MIB V1.7
|
Settings (default values)
|
IP network
|
BOOTP/DHCP enabled
IP address: 172.17.16.16 (manual configuration) Subnet mask: 255.255.0.0
Gateway: 0.0.0.0
NTP server: pool.ntp.org
|
Web-page access control
|
User name: EATON Password: EATON
|
Service-port menu access control
|
Password: EATON or eaton (not modifiable)
|
Date and time
|
Synchronise with an NTP server (GMT)
|
Service port
|
9600 bits/s, 8 bits, 1 bit stop, no parity
|
RS485 port
|
Slave nb:0x01, 9600 bits/s, 8 bits, 1 bit stop, no parity
|
|