FE Series 60Hz Specifications

Operation
Part No. FE
500VA
FE
700VA
FE
850VA
FE
1.15kVA
FE
1.4kVA
FE
1.8kVA
FE
2.1kVA
FE
3.1kVA
FE
4.3kVA
FE
5.3kVA
FE
7kVA
FE
10kVA
FE
12.5kVA
FE
18kVA
Nominal Input Voltage 120/208/240 208/240
Input Voltage Range +15%, -20%
Input Power Factor .98
Nominal Output Voltage 120/208/240
Output Voltage Regulation ±3% for input voltages +15% to -20% 
Output Voltage Waveform
Output Voltage THD
Sine Wave

6% or less at rated kW load
Overload Capacity 150% surge and 125% for 10 minutes on-line. 150% surge and 110% for 10 minutes on inverter.
Transfer Time 0 ms
Lightning, Surge, and Noise Protection 2000:1 spike attenuation using ANSI/IEEE C62.41 and C62.45 Category A and Category B tests.
Common Mode ->120 dB.Normal Mode ->60dB
Efficiency %  85 86 85 88 88 90 90 91 90 90 90 90 91 92
Safety Certification UL,CSA (cUL)
EMI Compliance FCC Class A
Testing Standards ANSI/EEE C62.41 (1980);ANSI/EEE C62.45 (1987);IEC 801-2,801-4,801-5
Communication RS-232 serial port (DB-25),plus contact closures
Environmental
Operating Temperature 0 to 40°C
Storage Temperature -20° to +60° C 
Relative Humidity 5 to 95% without condensation
Audible Noise (dBA) 41 41 47 49 49 51 51 51 50 51 52 55 56 57
Altitude 3050 m (10,000 ft.) maximum
Model Guide 500VA 700VA 850VA 1.15kVA 1.4kVA 1.8kVA 2.1kVA 3.1kVA 4.3kVA 5.3kVA 7kVA 10kVA 12.5kVA 18kVA
Part No. FE
500VA
FE
700VA
FE
850VA
FE
1.15kVA
FE
1.4kVA
FE
1.8kVA
FE
2.1kVA
FE
3.1kVA
FE
4.3kVA
FE
5.3kVA
FE
7kVA
FE
10kVA
FE
12.5kVA
FE
18kVA
Capacity (kVA/kW) .5/.35 .7/.5 .85/.6 1.15/.8 1.4/1 1.8/1.25 2.1/1.5 3.1/2.2 4.3/3 5.3/3.7 7/5 10/7.5 12.5/10 18/15
Dimensions
HxWxD

inches
mm

12x10x21.25
305x255x540
15.1x15.2x20.2
385x390x515
21.2x15.25x22.9
540x390x585
29.5x15.5x25
750x395x635
36.5x19x32
930x485x815
Dimensions are for the UPS only on 10-18kVA (does not include battery pack)
Weight 

lb
KG

62
28
79
36
85
39
132
60
154
70
183
83
196
89
256
116
359
163
505
229
604
274
875
397
1089
494
1362
589
Input Connection 6ft Cord w/NEMA 5-15P* 6ft Cord
w/NEMA
5-20P*
6ftCord
w/NEMA
L5-30P*
120V/40A
208V/25A
240V/20A
120V/40A
208V/30A
240V/25A
120V/40A
208V/40A
240V/35A

208V/60A
240V/50A

208V/75A
240V/65A

208V/115A
240V/100A
Output Connection (quantity)
(type)
4
NEMA 5-15R
6
NEMA 5-15R
6
NEMA 5-15R
  Hardwired output is standard. 
Contact Factory for receptacle options
Typical Runtime: (minutes)

Full load

Half load

9

25
14

35
11

28
18

48
14

37
11

30
9

25
14

35
8

20
20

50
12

33
11

26
18

48
10

26
More Info
   
FE Series 50 HZ Spec Details
Model Guide

   
FE Series 60 HZ Spec Details
Model Guide


Rack mount 50 HZ Spec Details
Model Guide


Rack mount 60 HZ Spec Details
Model Guide

   
Bypass Switch info
and
Wiring digrams and tables




Eaton Home Bomara Homepage Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
Phone: 800.5BOMARA (800.526.6272)

Phone: 978.452.2299

 

Fax: 978.452.1169

Email: bobr@bomara.com

  Web: www.bomara.com

3 Courthouse Lane, Chelmsford, MA 01824 USA
Serving the marketplace for over 40 years

© 2014 by Bomara. All rights reserved

 



First Name:
Last Name:
Company:
Address:
Mail Stop:
City:
State (if in US):
Province/Region (if outside US):
Country:
ZIP (Postal) Code:
E-mail:
Telephone:
Fax:
Questions/Comments:
Verification: Please type:
Please have a Bomara Associates representative contact me