Eaton Powerware Home » Surge Protection » Surge Protection Devices (SPD)

 Surge Protection Devices (SPD): SURGE PROTECTION


SPD Type 1 CHSP Service Entrance Surge Protection — UL 1449 3rd Ed. SPDListed

• Commercial grade AC power protection
• Type 1 surge device for installation before or after the main service disconnect
• Convenient mounting options—universal fit to any manufacturer's equipment
• Clear, visible LED indication displaying status of the surge protector


SPD TYPE 1 CHSP
Catalog Number Enclosure Voltage  Phase Frequency (Hz) MCOV1 VPR2  In3 SCCR4 Surge Current Capacity, Per Phase Rating5 List Price
CHSPT1ULTRA NEMA 4 100/200, 110/220, 120/240 Single 50/60 L-L 300, L-N 150 L-L 1000, L-N 600 20 kA 200 kA 50 kA Contact Bomara
CHSPT1MAX NEMA 4 100/200, 110/220, 120/240 Single 50/60 L-L 300, L-N 150 L-L 1000, L-N 600 20 kA 200 kA 45 kA Contact Bomara
CHSPT1MICRO NEMA 4 100/200, 110/220, 120/240 Single 50/60 L-L 300, L-N 150 L-L 1000, L-N 600 20 kA 200 kA 36 kA Contact Bomara
CHSPT1-208Y NEMA 4 120/208 Three-phase Wye 50/60 L-L 300, L-N 150 L-L 1000, L-N 600 20 kA 200 kA 50 kA Contact Bomara
Notes:
1. MCOV: Maximum Continuous Operating Voltage that may be applied to the device per mode.
2. VPR: Voltage Protection Rating is the measured limiting voltage after a surge event.
3. In: Nominal Discharge Current is the current that the device can withstand for 15 impulses.
4. SCCR: The amount of current the product can withstand under short-circuit conditions
5. Surge Current Capacity: The maximum one time surge current rating per phase



SPD Type 2 CHSP Service Entrance Surge Protection — UL 1449 3rd Ed.; cUL

SPD Type 2• AC power protection
• Universally connects to any manufacturer's loadcenter (breaker box)
• Quick connect design—easy to mount telephone and cable protection modules
• LED status indication
• This product should be connected on the load side of the loadcenter main service
disconnect through a dedicated circuit breaker (follow NEC Guidelines)


SPD TYPE 2 CHSP
Catalog Number Enclosure Voltage  Phase Frequency (Hz) MCOV1 VPR2  In3 SCCR4 Surge Current Capacity, Per Phase Rating5 List Price
CHSPT2ULTRA NEMA 4 120/240 Vac rated line voltage Single 60 150V L-N, 300V L-L 600V L-N, 1000V L-L, 800V N-G, 600V L-G 20 kA 22 kA 108 kA (L1-N 54 kA, L1-G 54 kA, L2-N 54 kA, L2-G 54 kA) Contact Bomara
CHSPT2MAX NEMA 4 120/240 Vac rated line voltage Single 60 150V L-N, 300V L-L 600V L-N, 1000V L-L, 800V N-G, 600V L-G 10 kA 22 kA 72 kA (L1-N 36 kA, L1-G 36 kA, L2-N 36 kA, L2-G 36 kA) Contact Bomara
CHSPT2MICRO NEMA 4 120/240 Vac rated line voltage Single 60 150V L-N, 300V L-L 600V L-N, 1000V L-L, 800V N-G, 600V L-G 5 kA 22 kA 36 kA (L1-N 18 kA, L1-G 18 kA, L2-N 18 kA, L2-G 18 kA) Contact Bomara
Notes:
1. MCOV: Maximum Continuous Operating Voltage that may be applied to the device per mode.
2. VPR: Voltage Protection Rating is the measured limiting voltage after a surge event.
3. In: Nominal Discharge Current is the current that the device can withstand for 15 impulses.
4. SCCR: The amount of current the product can withstand under short-circuit conditions
5. Surge Current Capacity: The maximum one time surge current rating per phase



Accessories for CHSP Type 2 Service Entrance Protection

CHSP TYPE 2 Accessories
Catalog Number Description Installation Surge Current Capacity DC Breakdown Voltage  Voltage  List Price
CHSPCABLE Quick Connect design—add additional telephone and AC protection modules; protects two quad shield cables Indoor installation; or rain-tight when used with recommended enclosure 10 kA per line 145V - Contact Bomara
CHSPTELE Quick Connect design—add additional AC and cable protection modules; protects two four telephone lines, bi-directional Indoor installation; or rain-tight when used with recommended enclosure 20 kA per line 230V Ring 90–120 Vac/Tone 48-52 Vdc Contact Bomara
CHSPT23PACK 3-Pack: CHSPT2ULTRA+CHSPTELE+CHSPCABLE; Surge protection for AC power, telephone and cable - see individual product features - See individual product ratings - - Contact Bomara




Call Us: 1-978-452-2299
First Name:
Last Name:
Company:
Address:
Mail Stop:
City:
State (if in US):
Province/Region (if outside US):
Country:
ZIP (Postal) Code:
E-mail:
Telephone:
Fax:
Questions/Comments:
Verification: Please type:
Please have a Bomara Associates representative contact me