Eaton Powerware Home » Three Phase UPS Systems » Eaton BladeUPS  » ZC0811100100000

 Powerware Eaton ZC0811100100000 Specifications: BladeUPS Power System Technical Specs (8 kW models)

3 Phase 208VAC 8KVA/ 8kW (Unity Power Factor) Modular Scalable UPS to


General Characteristics
Part number ZC0811100100000
Power Rating 8 kW per UPS Module
Efficiency Up to 98%

ZC0811100100000-efficiency

* These efficiencies are for guidance only. Actual unit and system efficiencies will vary based on site design/conditions and environmental parameters.

Heat Dissipation 264 watts/903 BTU/hr at 100% rated load
Cooling Fan cooled, temperature microprocessor monitored; front air entry, rear exhaust
Audible Noise, Normal Operation <60 dBA at 1 meter
Altitude before derating 1000 meters (3300 ft. ASL)
Input Characteristics
Input Voltage 208 Vac models
Voltage Range 180 to 265 Vac
Input connection L21-30P
Frequency Range 50 or 60 Hz, ±5 Hz
Input Current Distortion <5% with IT loads (PFC power supplies)
Input Power Factor >0.99 with IT loads (PFC power supplies)
Inrush Current Load dependent
Input Requirements Three-phase, four-wire + ground
Bypass Source Same as input, (single feed)
Generator Compatibility Fast sync slew rate for optimum generator synchronization programmable return to AC source delay
Output Characteristics
Output connection L21-30R, RPM Port
Rated Output Voltage 180 to 225 Vac, phase to phase
Output Configuration Three-phase, four-wire + ground
Output Frequency (nominal) 50 or 60 Hz auto-detection on startup
Frequency Regulation 0.1 Hz free running
Load Power Factor Range Lagging: 0.7
Leading: 0.9
Total Output
Voltage Distortion
<3% with IT loads (PFC power supplies)
<5% non-linear or non-PFC power supplies
Battery Characteristics
Battery Type VRLA - AGM

ZC0811100100000-battery

Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.

Battery Runtime (Internal) 23 minutes at 50% load
9 minutes at 100% load
Battery String Voltage 240 Vdc
Battery Test Automatic battery test standard (remote scheduling capable).
Manual battery test from front display
Battery Recharge Profile ABM three-stage charging technology
Battery Cut-off Voltage Variable from 1.67 VPC at <5 min. runtime to 1.75 VPC at >90 min. runtime
Battery Low Condition Announced with alarm
Extended Battery Capability Yes, add up to four additional 3U battery modules
120 minutes at 50% load; 55 minutes at 100% load
Physical Characteristics
Dimensions H x W x D, in (mm)
UPS
EBM

10.3 (6U) x 17.4 x 26.0 (267 x 442 x 660)
5.2 (3U) x 17.2 x 26.0 (132 x 437 x 660)
Note:
Total Chassis Weight
without batteries or
electronics 
Total Chassis Weight
with batteries or
electronics 

100 lb. (46 kg)


307 lb. (140 kg)
Total UPS Weight without Batteries 135 lb. (61 kg)
Total UPS Weight with Batteries 307 lb. (140 kg)
EBM Shipping Weight 170 lb. (77 kg)
Communications and User Interface
Software Compatibility UPS ships with Software Suite CD containing Intelligent Power Manager supervisory software and Intelligent Power Protector protection software
X-Slot Bays Two available for the cards listed below
Control panel LCD Two lines by 20 characters
Four menu-driven interface buttons
Four status at a glance LEDs
Multi Language English standard; 20 languages available
Configuration Changes User capable, firmware auto configures
Dry Contact Inputs Two, user-configurable
Dry Contact Outputs One, user-configurable
Service
Installation User capable, optional factory service available located in the IT racks
Preventive Maintenance User capable, optional factory service available
Corrective Maintenance User capable, optional factory service available
Serviceability Features Hot-swappable batteries
Hot-swappable electronics module
Automated internal maintenance bypass
Auto-configure firmware
Flash firmware upgradeable
Certifications
Safety UL1778, cUL
EMI FCC Part15 Class A
Surge Protection ANSI C62.41, Cat B-3
Hazardous materials (RoHS) EU Directive 2002/95/EC Category 3 (4 of 5)
Warranty
Standard 18 months from date of shipment
Warranty Repair Factory depot repair or replace
Service Support Agreements2
Depot PowerTrust Express
On-site 5x8 PowerTrust Value
On-site 7x24 PowerTrust eight-, six- or two-hour response
Options and Accessories
Detachable input cord
Detachable input/output cord assembly
Detachable paralleling cord assembly
Extended Battery Modules (EBMs)
3U output sub-distribution module
0U to 3U rack power strips
60 kW BladeUPS Parallel Bar, Top Entry, Bottom Entry & 4-high versions
Four-post rail kit
Environmental Monitoring Probe (EMP) for temperature and humidity monitoring
Environmental Rack Monitor (ERM)
3U Maintenance Bypass Module
External Battery Interconnect for use with 400V models
Optional X-Slot Communication Cards
Application Card
Web/SNMP PowerXpert Gateway Series UPS card
Modbus RTU Modbus Card
Modbus TCP/IP PowerXpert Gateway Series UPS card
IBM eServer (i5, iSeries, or AS/400)
Relay Interface Card
N/O, N/C (dry contacts
Industrial relay card
Parallel Powerware Hot Sync CAN Bridge card
Compatible ePDU models for rackmount power distribution
Basic (BA) EBA304-10 with (30) C13-grip, (6) C19-grip outlets
EBA310-10 with (1) 5-20R, (30) C13-grip, (6) C19-grip outlets
EBA314-10 with (42) C13-grip outlets
PW309BA0U409 with (24) 5-20R outlets
Metered Input (MI) EMI304-10 with (30) C13-grip, (6) C19-grip outlets
EBI310-10 with (1) 5-20R, (30) C13-grip, (6) C19-grip outlets
EBI314-10 with (42) C13-grip outlets
Advanced Monitored (AM): Outlet level eAM004 with (21) C13, (3) C19
Managed (SW): Switched/outlet level monitoring eMA011 with (21) C13, (3) C19
PW309SW0U178 with (24) C13

 




Call Us: 1-978-452-2299
First Name:
Last Name:
Company:
Address:
Mail Stop:
City:
State (if in US):
Province/Region (if outside US):
Country:
ZIP (Postal) Code:
E-mail:
Telephone:
Fax:
Questions/Comments:
Verification: Please type:
Please have a Bomara Associates representative contact me


View Full Site View Mobile Optimized