Perfect for rack servers enclosure and industrial environment


  • Servers, whether rack-mounted or standing
  • Networking & VOIP
  • Storage
  • Telecom equipment
  • Medical equipment
  • Sensitive electronic equipment in industrial environment
  • High-Density Server virtualization environment
  • 5/7/11 kVA (6U)
  • True On Line
  • Software Inc.
  • Fully Hot Swappable
  • Density optimized

Model numbers and configuration guide:

EX RT POWER MODULES*
Catalog
Number
Style
Number
Description  List
Price
EXRTG5000-PWRMS 86056 EXRT 5 kVA Power Module $3,026
EXRTG7000-PWRMS 86076 EXRT 7 kVA Power Module $3,608
EXRTG11000-PWRMS 86116 EXRT 11 kVA Power Module $4,752
* Rail kit included

 

EX RT OPTIONS
Catalog
Number
Style
Number
Description Dimensions
(H x W x D, inches)
Weight
(lb)
List
Price
EX RT Modules*
EXRTL7000-XFMR3U 86311 EXRT 5/7 kVA Transformer Module 5.16 (3U) x 17.49 x 25.00 173.0 $2,522
EXRTL9140-XFMR3U 103007853-6591  EXRT 11 kVA Transformer Module 5.16 (3U) x 17.49 x 25.00 173.0 $2,677
EXRTG11000-CHR3U 86004 EXRT 5/7/11 kVA Charger Module 5.16 (3U) x 17.49 x 23.75 25.4 $748
Battery Integration
86005 86005 Battery Integration Kit / Caster Kit - - $577
86006 86006 EXRT 6-ft Battery Extension Cable - - $48
Optional Mounting Hardware
86001 86001 EXRT Power Module Rail Kit - - $87
86002 86002 EXRT EBM/Transformer Rail Kit - - $58
Cabling
72-153653-01 72-153653-01 8’ Cord with L6-30 - - $159
Extended Battery Modules*
EXRTG7000-EBM3U 86079 EX RT EBM - 5/7 kVA 5.16 (3U) x 17.49 x 25.00 142.0 $1,300
EXRTG11000-EBM3U 86119 EX RT EBM - 11 kVA 5.16 (3U) x 17.49 x 25.00 151.0 $1,404
* Rail kit included

 

 
Specifications
5 KVA / 4 kW
7 kVA/4.9 kW
11 kVA/8 kW
Performances
Technology
Online double conversion with PFC (Power Factor Correction) system
Nominal Input Voltage
120-280 V at <70% rated output
Input Voltage Range
156-280 V at 100 % rated output
Input Frequency Range
40-70 Hz, frequency converter as a standard
Output Voltage/Frequency
200/208*/220/230/240/250 Volts; 120 V Output Voltage available with transformer; 50/60 Hz autoselect
Overall Efficiency (Online Mode-ECO Mode)/Harmonic Current Distortion
90% - 97% /<5%
Crest Factor/Overload Capacity
3:1 / 2 min if 102%<overload<110%, 1 min if 110%<overload<125%, 30 sec if 125%<overload<150%, 500msec. If overload >150%
Battery Test
weekly without load interruption(1)
Operating Temperature
45°C for 8 Hrs. 0°C to 40°C continuous
Back-up Times (in minutes at 50% /100% loads)
5 kVA/4 kW
7 kVA/4.9 kW
11 kVA/8 kW
Standard Battery
25/9
21/7
14/5
Standard Battery + 1 EXB
60/25
53/20
30/14
Standard Battery + 2 EXB
100/45
83/32
53/22
Standard Battery + 3 EXB
122/60
108/45
84/30
Standard Battery + 4 EXB
170/84
132/57
102/42
Standard Battery + 5 EXB
225/100
164/72
113/53
More back-up time available with CLA module, on request
Connection
Power Module Input/Output Terminal Block
Hardwired
Hardwired
Hardwired
Maximum Wire Size (Solid or Stranded Wire)
10 mm / 6 AWG
10 mm / 6 AWG
13 mm / 4 AWG
Step-Down Transformer
120/208/240 VAC Output
Output Configuration
Terminal Block, plus (2) NEMA L6-30R (208V) (8) NEMA 5-15/20R
 
Optional PDUs for additional NEMA or IEC receptacles
Communication
Port Type
6 voltage free dry contacts DB-9 rated at 2 A 48V DC, (1) RS 232, (1) RJ11 for RPO (Remote Power Off)
Slot
1 slot for MGE transverse communication card (HTTP, XML, Webcard, Jbus…)
Standards and Certification
Performance and Safety
IEC 62040-1/CEI 60950/UL 1778 and CSA 22.2 Standards
EMC
IEC 62040-2; EN 50091-2; FCC class A
Certification
UL/TÜV, GS mark, CB, C-Tick, CE
Dimensions (H x W x D) in inches/Weight in pounds
Standard EX RT (Power Module + Battery Module) Form Factor (High Voltage)
10.32 (6 U) X 17.49 X 26.25/192 for 5/7 kVA System, 211 for 11kVA System
Standard EX RT (Power Module + Battery Module + Transformer Module) Form Factor (Low Voltage)
15.48 (9U) X 17.49 X 26.5/365 for 5/7 kVA Systems/384 for 11 kVA System
Power Module EX RT
5.16 (3 U) X 17.49 X 26.25/49.6 for 5/7kVA Unit, 60.6 for 11kVA Unit
Battery Module EXB RT
5.16 (3 U) X 17.49 X 25 / 142 for 5/7kVA Unit, 151 for 11kVA Unit
Charger Module EX RT CLA
5.16 (3 U) X 17.49 X 23.75/25.40
Transformer Module EX RT
5.16 (3 U) X 17.49 X 25/173
Part Number and Description
5 kVA/4 kW
7 kVA/4.9 kW
11 kVA/8 kW
EX RT Standard Pack without Transformer (HV)
86050
86070
86110
EX RT Standard Pack with Transformer (LV)
86201
86203
86205
EX RT Power and Battery Modules
Power Module with rails
86215
86216
86217
Battery Module with rails
86207
86207
86209
EX RT Transformer
Transformer with rails
86211
86211
86211
EX RT CLA Charger Module
CLA Charger with rails
86214
86214
86214
Battery Integration Kit with Casters (max. 8 modules)
Stack kit with inter-module fastening, swivel wheels, brakes, leveling feet
86005
86005
86005
Installation Rack Kits for EX RT/EXB 5/7/11 kVA
Power Module Rail Kit
86001
86001
86001
Battery Module, Transformer and CLA Charger Rail Kit
86002
86002
86002
Input Cord for 5 kVA System
8 foot cord with NEMA L6-30P
72-153653-01
-
-
Warranty/Parts and Labor (US and Canada)
Two year product warranty
* : Default Voltage 1: Configurable

1: At 70% load. 2: Economy mode, 91% in normal mode. 3: At 70% nominal rating with power factor 0.7 typical values after 3 charge/discharge cycles, with 3-5 year old batteries. Weekly battery test without interrupting the load (daily or monthly if required). EXB compatible with 0.8 power factor loads. 4: Solution-Pac CDROM supplied as standard. 5: 50 dbA above 5 kVA. 6: Depending on the country, see www.mgeups.com/service. 7: 87415 = 87021 (empty Pulsar MX Frame) + (3) 87100 + (3) 87101. 8: 87420 = 87021 (empty Pulsar MX Frame) + (4) 87100 + (4) 87101

 

 