Bomara Associates Logo Bomara Associates Homepage Eaton Authorized Power Specialist

EX RT

Perfect for rack servers enclosure and industrial environment


  • Servers, whether rack-mounted or standing
  • Networking & VOIP
  • Storage
  • Telecom equipment
  • Medical equipment
  • Sensitive electronic equipment in industrial environment
  • High-Density Server virtualization environment
  • 5/7/11 kVA (6U)
  • True On Line
  • Software Inc.
  • Fully Hot Swappable
  • Density optimized
 
Specifications
5 KVA / 4 kW
7 kVA/4.9 kW
11 kVA/8 kW
Performances
Technology
Online double conversion with PFC (Power Factor Correction) system
Nominal Input Voltage
120-280 V at <70% rated output
Input Voltage Range
156-280 V at 100 % rated output
Input Frequency Range
40-70 Hz, frequency converter as a standard
Output Voltage/Frequency
200/208*/220/230/240/250 Volts; 120 V Output Voltage available with transformer; 50/60 Hz autoselect
Overall Efficiency (Online Mode-ECO Mode)/Harmonic Current Distortion
90% - 97% /<5%
Crest Factor/Overload Capacity
3:1 / 2 min if 102%<overload<110%, 1 min if 110%<overload<125%, 30 sec if 125%<overload<150%, 500msec. If overload >150%
Battery Test
weekly without load interruption(1)
Operating Temperature
45°C for 8 Hrs. 0°C to 40°C continuous
Back-up Times (in minutes at 50% /100% loads)
5 kVA/4 kW
7 kVA/4.9 kW
11 kVA/8 kW
Standard Battery
25/9
21/7
14/5
Standard Battery + 1 EXB
60/25
53/20
30/14
Standard Battery + 2 EXB
100/45
83/32
53/22
Standard Battery + 3 EXB
122/60
108/45
84/30
Standard Battery + 4 EXB
170/84
132/57
102/42
Standard Battery + 5 EXB
225/100
164/72
113/53
More back-up time available with CLA module, on request
Connection
Power Module Input/Output Terminal Block
Hardwired
Hardwired
Hardwired
Maximum Wire Size (Solid or Stranded Wire)
10 mm / 6 AWG
10 mm / 6 AWG
13 mm / 4 AWG
Step-Down Transformer
120/208/240 VAC Output
Output Configuration
Terminal Block, plus (2) NEMA L6-30R (208V) (8) NEMA 5-15/20R
 
Optional PDUs for additional NEMA or IEC receptacles
Communication
Port Type
6 voltage free dry contacts DB-9 rated at 2 A 48V DC, (1) RS 232, (1) RJ11 for RPO (Remote Power Off)
Slot
1 slot for MGE transverse communication card (HTTP, XML, Webcard, Jbus…)
Standards and Certification
Performance and Safety
IEC 62040-1/CEI 60950/UL 1778 and CSA 22.2 Standards
EMC
IEC 62040-2; EN 50091-2; FCC class A
Certification
UL/TÜV, GS mark, CB, C-Tick, CE
Dimensions (H x W x D) in inches/Weight in pounds
Standard EX RT (Power Module + Battery Module) Form Factor (High Voltage)
10.32 (6 U) X 17.49 X 26.25/192 for 5/7 kVA System, 211 for 11kVA System
Standard EX RT (Power Module + Battery Module + Transformer Module) Form Factor (Low Voltage)
15.48 (9U) X 17.49 X 26.5/365 for 5/7 kVA Systems/384 for 11 kVA System
Power Module EX RT
5.16 (3 U) X 17.49 X 26.25/49.6 for 5/7kVA Unit, 60.6 for 11kVA Unit
Battery Module EXB RT
5.16 (3 U) X 17.49 X 25 / 142 for 5/7kVA Unit, 151 for 11kVA Unit
Charger Module EX RT CLA
5.16 (3 U) X 17.49 X 23.75/25.40
Transformer Module EX RT
5.16 (3 U) X 17.49 X 25/173
Part Number and Description
5 kVA/4 kW
7 kVA/4.9 kW
11 kVA/8 kW
EX RT Standard Pack without Transformer (HV)
86050
86070
86110
EX RT Standard Pack with Transformer (LV)
86201
86203
86205
EX RT Power and Battery Modules
Power Module with rails
86215
86216
86217
Battery Module with rails
86207
86207
86209
EX RT Transformer
Transformer with rails
86211
86211
86211
EX RT CLA Charger Module
CLA Charger with rails
86214
86214
86214
Battery Integration Kit with Casters (max. 8 modules)
Stack kit with inter-module fastening, swivel wheels, brakes, leveling feet
86005
86005
86005
Installation Rack Kits for EX RT/EXB 5/7/11 kVA
Power Module Rail Kit
86001
86001
86001
Battery Module, Transformer and CLA Charger Rail Kit
86002
86002
86002
Input Cord for 5 kVA System
8 foot cord with NEMA L6-30P
72-153653-01
-
-
Warranty/Parts and Labor (US and Canada)
Two year product warranty
* : Default Voltage 1: Configurable

1: At 70% load. 2: Economy mode, 91% in normal mode. 3: At 70% nominal rating with power factor 0.7 typical values after 3 charge/discharge cycles, with 3-5 year old batteries. Weekly battery test without interrupting the load (daily or monthly if required). EXB compatible with 0.8 power factor loads. 4: Solution-Pac CDROM supplied as standard. 5: 50 dbA above 5 kVA. 6: Depending on the country, see www.mgeups.com/service. 7: 87415 = 87021 (empty Pulsar MX Frame) + (3) 87100 + (3) 87101. 8: 87420 = 87021 (empty Pulsar MX Frame) + (4) 87100 + (4) 87101

 

 



Powerware Home
Bomara Homepage
Request Information

Bomara Associates Phone: 800.5BOMARA (800.526.6272) Phone: 978.452.2299 Fax: 978.452.1169 3 Courthouse Lane, Chelmsford, MA 01824 USA
email: bobr@bomara.com      web: www.bomara.com
Serving the marketplace for over 35 years