Power Distribution Unit
The Powerware PDU provides reliable data center power distribution for both raised and non-raised floor applications. To deliver effective power management and monitoring, the Powerware PDU incorporates the Powerware Energy Management System, optimizing both utilization and availability down to the branch circuit level. The optional Power Xpert® Gateway Series 1000 Card provides Web-enabled, real-time monitoring for power quality status and fast response to power-related events.
To ensure the high performance required for today’s data centers, this Eaton®-designed and manufactured PDU delivers maximum flexibility in an integrated, factory-tested package:
Features and Benefits
- Integrated isolation, monitoring, distribution and a wide array of options
- Scalable architecture and space-saving design
- Comprehensive monitoring and connectivity options
- Unparalleled ease of use through front-access only design, top and bottom cable access, and spacious wire-ways
| Electrical Characteristics |
Input ratings: |
| Voltage: |
208V, 480V or 600V:
Three-phase, three-wire plus ground (Transformerless: three-phase, four-wire plus ground) |
| Frequency: |
60 Hz |
| Output ratings: |
| Voltage: |
208V/120V, 480V or 600V: Three-phase, four-wire plus ground |
| Frequency: |
60 Hz |
| Distribution |
| Cutler-Hammer® 42 pole panelboards with 225A main breaker |
| Cutler-Hammer® Series C molded case subfeed breakers up to 225A |
| Up to eight subfeed breakers |
| Custom subfeed ratings available |
| Factory installed branch circuit breakers |
| Options |
| Dual main input breakers |
| High kAIC input breakers |
| TVSS (80 kA-200 kA) |
| Lightning arrestor |
| Transient suppression plate |
| Floor Stands (12”, 18”, 24” & 36”) |
| Junction box |
| Manual restart |
| Isolated ground |
| Powerware Energy Management System |
| Branch circuit monitoring |
| Remote power panels |
| Distribution cables (WHIPS) |
| Communication X-Slots™ (Two) |
| Physical Characteristics |
| 30 to 50 kVA (K1-K20): |
36"W x 32"D x 76"H |
| 200 to 225 kVA (K1-K13): |
36”W x 32”D x 76”H |
| 200 to 225 kVA (K20): |
41”W x 35”D x 76”H |
| 300 kVA (K1-K20): |
41”W x 35”D x 76”H |
| Monitoring Features |
Metered Values: |
| Input voltage: L-L |
| Output voltage: L-L & L-N |
| Phase output current |
| Neutral current |
| Ground current |
| kVA, KW, Hz |
| Total Harmonic Distortion (THD) |
| Power factor / phase |
| Percent load / phase |
| Load Profiling |
| Min & Max V, I, Hz, KW recorded over a four hour period |
| Captures highest reading on monthly basis, with trend information over last 23 months |
| Alarms |
| Transformer over-temp. & shutdown |
| Over-and under-voltage (input & output) |
| High current (Three-phases, N, G) |
| Phase rotation (input & output) |
| Phase loss |
| Building alarms (Two - programmable) |
| Voltage THD |
| Current THD |
| Over/Under frequency |
| Output overload (3-Levels) |
| Modem call |
| Control |
| EPO (Optional) |
Custom shutdowns on alarms:
-
Phase rotation
-
Phase loss
-
Ground fault
-
Site wiring fault
-
Building alarms
|
| Connectivity |
| Modbus |
| Modem |
| Optional Power Xpert(R) PDU card for network interface |